Laserfiche WebLink
w w�^ <br /> TESTING Al Ca A~Ry <br /> SERVICES <br /> • EVERGREEN MANOR <br /> • • EVERETT,WA <br /> • • 2220161 <br /> • <br /> BRUCE HURLBUT <br /> UNIT DATA <br /> UNIT ID ERV-2(SUPPLY) ERV-2(EXHAUST) <br /> EQUIP. LOCATION CEILING CEILING <br /> AREA SERVED SOUTH WING OFFICES SOUTH WING OFFICES <br /> MANUFACTURER LOSSNAY LOSSNAY <br /> MODEL NUMBER TLGHF030ORVX02A TLGHF030ORVX02A <br /> SERIAL NUMBER 22030020546174 22030020546174 <br /> FAN DATA <br /> DESIGN CFM 285 285 <br /> ACTUAL CFM 288 272 <br /> T.S.P."W.C. 0.46 0.46 <br /> TESTED SPEED HIGH HIGH <br /> STATIC SETTING N./APPL. N./APPL. <br /> MOTOR DATA <br /> MANUFACTURER MITSUBISHI MITSUBISHI <br /> HORSEPOWER 0.25 0.34 <br /> NAMEPLATE VOLTS 208 208 <br /> TESTED VOLTS 208 208 <br /> NAMEPLATE AMPS 0.8 1.03 <br /> TESTED AMPS 0.8 1.0 <br /> MOTOR RPM VARIABLE VARIABLE <br /> SPEED 4-SPEED 4-SPEED <br /> PHASE/ HZ 1/60 1/60 <br /> OVERLOAD SIZE THERMAL THERMAL <br /> AREA SERVED NO. CODE SIZE AK • OF OF <br /> FPM CFM FPM CFM DESIGN FPM CFM DESIGN <br /> MEETING 1 CD-2 8X8 F. H. 65 112 172% 65 1000/0 <br /> LOBBY 2 CD-2 8X8 F. H. 85 51 60% 82 96% <br /> OSA FCU-1 3 DUCT 8" F. H. 135 185 137% 141 104% <br /> SUPPLY 285 348 122% 288 1010/0 <br /> RR El EG-1 6X6 F. H. 85 100 1180/0 78 92% <br /> MEETING E2 RG-1 8X8 F. H. 65 88 135% 70 1080/0 <br /> UA RR E3 EG-2 10X10 F. H. 135 135 1000/0 124 92% <br /> EXHAUST 285 323 113% 272 95% <br /> Jill <br /> FORM:DIRECT DRIVE TEST DATA <br /> 10/24/2023 <br /> Page 28 of 56 <br />