Laserfiche WebLink
w w�^ <br /> TESTING Al Ca A~Ry <br /> SERVICES <br /> • EVERGREEN MANOR <br /> • • EVERETT,WA <br /> • • 2220161 <br /> • <br /> BRUCE HURLBUT <br /> UNIT DATA <br /> UNIT ID ERV-4(SUPPLY) ERV-4(EXHAUST) <br /> EQUIP. LOCATION CEILING CEILING <br /> AREA SERVED BUILDING VENTILATION BUILDING EXHAUST <br /> MANUFACTURER LOSSNAY LOSSNAY <br /> MODEL NUMBER TLGHF060ORVX02A TLGHF060ORVX02A <br /> SERIAL NUMBER 22100043546177 22100043546177 <br /> FAN DATA <br /> DESIGN CFM 580 580 <br /> ACTUAL CFM 589 592 <br /> T.S.P."W.C. 0.66 0.66 <br /> TESTED SPEED HIGH HIGH <br /> STATIC SETTING N./APPL. N./APPL. <br /> MOTOR DATA <br /> MANUFACTURER MITSUBISHI MITSUBISHI <br /> HORSEPOWER 0.42 0.41 <br /> NAMEPLATE VOLTS 208-230 208-230 <br /> TESTED VOLTS 208 208 <br /> NAMEPLATE AMPS 1.37 1.34 <br /> TESTED AMPS 1.3 1.3 <br /> MOTOR RPM VARIABLE VARIABLE <br /> SPEED 4-SPEED 4-SPEED <br /> PHASE/ HZ 1/60 1/60 <br /> OVERLOAD SIZE THERMAL THERMAL <br /> AREA SERVED NO. CODE SIZE AK • OF OF <br /> FPM CFM FPM CFM DESIGN FPM CFM DESIGN <br /> DIRECTOR 1 CD-2 6X6 F.H. 15 14 93% 15 1000/0 <br /> RECEP 2 CD-2 6X6 F.H. 15 15 1000/0 16 107% <br /> GROSS ART RM 3 CD-1 18X12 F.H. 550 383 70% 558 1010/0 <br /> SUPPLY 580 412 71% 589 102% <br /> GROSS ART RM El RG-1 18X10 F.H. 510 322 63% 523 103% <br /> RR E2 EG-1 6X6 F.H. 70 98 140% 69 990/0 <br /> EXHAUST 580 420 72% 592 102% <br /> Jill <br /> FORM:DIRECT DRIVE TEST DATA <br /> 10/24/2023 <br /> Page 30 of 56 <br />