Laserfiche WebLink
w w�^ <br /> TESTING Al Ca A~Ry <br /> SERVICES <br /> • EVERGREEN MANOR <br /> • • EVERETT,WA <br /> • • 2220161 <br /> • <br /> BRUCE HURLBUT <br /> UNIT DATA <br /> UNIT ID ERV-3(SUPPLY) ERV-3(EXHAUST) <br /> EQUIP. LOCATION CEILING CEILING <br /> AREA SERVED LVL 1 DINING RM LVL 1 DINING RM <br /> MANUFACTURER LOSSNAY LOSSNAY <br /> MODEL NUMBER TLGHF120ORVX02A TLGHF120ORVX02A <br /> SERIAL NUMBER 22040012546179 22040012546179 <br /> FAN DATA <br /> DESIGN CFM 955 955 <br /> ACTUAL CFM 993 1003 <br /> T.S.P."W.C. 0.59 0.59 <br /> TESTED SPEED HIGH HIGH <br /> STATIC SETTING N./APPL. N./APPL. <br /> MOTOR DATA <br /> MANUFACTURER MITSUBISHI MITSUBISHI <br /> HORSEPOWER 0.42 0.41 <br /> NAMEPLATE VOLTS 208-230 208-230 <br /> TESTED VOLTS 209 209 <br /> NAMEPLATE AMPS 1.37 1.34 <br /> TESTED AMPS 0.9 0.8 <br /> MOTOR RPM VARIABLE VARIABLE <br /> SPEED 4-SPEED 4-SPEED <br /> PHASE/ HZ 1/60 1/60 <br /> OVERLOAD SIZE THERMAL THERMAL <br /> AREA SERVED NO. CODE SIZE AK • OF OF <br /> FPM CFM FPM CFM DESIGN FPM CFM DESIGN <br /> DINING 1 SG-1 12X10 F. H. 410 650 1590/0 394 96% <br /> DINING 2 CD-2 6X6 F. H. 15 it 73% 15 1000/0 <br /> DINING 3 SG-1 12X10 F. H. 410 384 94% 452 1100/0 <br /> DINING 4 CD-1 8X8 F. H. 120 179 149% 132 1100/0 <br /> SUPPLY 955 1224 128% 993 104% <br /> DINING E1 EG-1 6X6 F.H. 30 65 217% 33 1100/0 <br /> DINING E2 RG-1 18X10 F.H. 910 728 80% 970 107% <br /> EXHAUST 940 793 84% 1003 107% <br /> Jill <br /> FORM:DIRECT DRIVE TEST DATA <br /> 10/24/2023 <br /> Page 29 of 56 <br />