MODULE SPECIFICATIONS
<br />REC Solar REC420AA PURE-R DESIGN LOCATION AND TEMPERATURES
<br />CONDUCTOR SIZE CALCULATIONS
<br />RATED POWER (STC)
<br />420 W
<br />MODULE VOC
<br />59.4 V DC
<br />MODU LE VMP
<br />50 V DC
<br />MODULE IMP
<br />8.4 ADC
<br />MODULE ISC
<br />8.88 ADC
<br />VOC CORRECTION
<br />-0.24 %/°C
<br />VMP CORRECTION
<br />-0.24 %/°C
<br />SERIES FUSE RATING
<br />25 A DC
<br />ADJ, MODULE VOC @ ASHRAE LOW TEMP
<br />63.7 V DC
<br />ADJ. MODULE VMP @ ASHRAE 2% AVG. HIGH TEMP
<br />46.0 V DC
<br />MI I.KUINVtK ILK ZIYLLI FILAI IUN.)
<br />Lnpnase nvA IYIIcroinverLers
<br />POWER POINT TRACKING (MPPT) MIN/MAX
<br />53 - 64 V DC
<br />MAXIMUM INPUT VOLTAGE
<br />79.5 V DC
<br />MAXIMUM DC SHORT CIRCUIT CURRENT
<br />10 A DC
<br />MAXIMUM USABLE DC INPUT POWER
<br />460 W
<br />MAXIMUM OUTPUT CURRENT
<br />1,31 A AC
<br />AC OVERCURRENT PROTECTION
<br />20 A
<br />MAXIMUM OUTPUT POWER
<br />315 W
<br />CEC WEIGHTED EFFICIENCY
<br />97.5 %
<br />AC PHOTOVOLATIC MODULE MARKING (NEC 690.52)
<br />NOMINAL OPERATING AC VOLTAGE 240 V AC
<br />NOMINAL OPERATING AC FREQUENCY 47 - 68 HZ AC
<br />MAXIMUM AC POWER 240 VA AC
<br />MAXIMUM AC CURRENT 1.0 A AC
<br />MAXJMUM OCPD RATING FOR AC MODULE 20 AAC
<br />GROUNDING NOTES
<br />TEMPERATURE DATA SOURCE ASHRAE 2%AVG. HIGH TEMP
<br />STATE Washington
<br />CITY Everett
<br />WEATHER STATION SNOHOMISH CO
<br />ASHRAE EXTREME LOW TEMP (°C) -5
<br />ASHRAE 2% AVG, HIGH TEMP ("C) 26
<br />SYSTEM ELECTRICAL SPECIFICATIONS CIR 1 CIR 2 CIR 3 CIR 4 CIR 5 CIR 6
<br />NUMBER OF MODULES PER MPPT
<br />DC POWER RATING PER CIRCUIT (STC)
<br />TOTAL MODULE NUMBER
<br />STC RATING OF ARRAY
<br />AC CURRENT @ MAX POWER POINT (IMP)
<br />MAX. CURRENT (IMP X 1.25)
<br />OCPD CURRENT RATING PER CIRCUIT
<br />MAX. COMB. ARRAY AC CURRENT (IMP)
<br />MAX. ARRAY AC POWER
<br />9
<br />3780
<br />8
<br />3360
<br />8
<br />3360
<br />25
<br />10500
<br />11.8
<br />14.7375
<br />20
<br />10.5
<br />13.1
<br />20
<br />10.5
<br />13.1
<br />20
<br />32.8
<br />7875W AC
<br />AC VOLTAGE RISE CALCULATIONS
<br />DIST (FT)
<br />COND.
<br />VRISE(V) VEND(V)
<br />%VRISE
<br />VRISE SEC. 1 (MICRO TO JBOX)
<br />32.4
<br />12 Cu.
<br />1.18
<br />241.18
<br />0.49%
<br />VRISE SEC. 2 (JBOX TO COMBINER BOX)
<br />65
<br />10 Cu.
<br />1.95
<br />241.95
<br />0.81%
<br />VRISE SEC. 3 (COMBINER BOX TO POI)
<br />5
<br />8 Cu.
<br />0.26
<br />240.26
<br />0.11%
<br />TOTAL VRISE
<br />3.38
<br />243.38
<br />1.41%
<br />PHOTOVOLTAIC AC DISCONNECT OUTPUT LABEL (NEC 690.S4)
<br />AC OUTPUT CURRENT 32.8 A AC
<br />NOMINAL AC VOLTAGE 240 V AC
<br />1. A GROUNDING ELECTRODE SYSTEM IN ACCORDANCE WITH [NEC 690.471 AND [NEC 250.50-601 SHALL BE
<br />PROVIDED. PER [NEC 690.47], THE GROUNDING ELECTRODE SYSTEM OF AN EXISTING BUILDING MAY BE
<br />USED AND BE BONDED AT THE SERVICE ENTRANCE. IF EXISTING SYSTEM IS INACCESSIBLE, OR
<br />INADEQUATE, OR IS ONLY METALLIC WATER PIPING, A SUPPLEMENTAL GROUNDING ELECTRODE WILL BE
<br />USED AT THE INVERTER LOCATION CONSISTING OF A UL LISTED 8 FT GROUND ROD WITH ACORN CLAMP.
<br />2. THE GROUNDING ELECTRODE CONDUCTOR SHALL BE PROTECTED FROM PHYSICAL DAMAGE BETWEEN
<br />THE GROUNDING ELECTRODE AND THE PANEL (OR INVERTER) IF SMALLER THAN #6 AWG COPPER WIRE
<br />PER [NEC 250.64(B)]. THE GROUNDING ELECTRODE CONDUCTOR WILL BE CONTINUOUS, EXCEPT FOR
<br />SPLICES OR JOINTS AT BUSBARS WITHIN LISTED EQUIPMENT PER [NEC 250.64(C)].
<br />3. GROUNDING ELECTRODE CONDUCTORS SHALL BE NO LESS THAN 8 AWG AND NO GREATER THAN 6 AWG
<br />COPPER AND BONDED TO THE EXISTING GROUNDING ELECTRODE TO PROVIDE FOR A COMPLETE SYSTEM.
<br />4. PV SYSTEM SHALL BE GROUNDED IN ACCORDANCE TO [NEC 250.211, [NEC TABLE 250.1221, AND ALL METAL
<br />PARTS OR MODULE FRAMES ACCORDING TO [NEC 690.461.
<br />5. MODULE SOURCE CIRCUITS SHALL BE GROUNDED IN ACCORDANCE TO [NEC 690.42].
<br />6. THE GROUNDING CONNECTION TO A MODULE SHALL BE ARRANGED SUCH THAT THE REMOVAL OF A
<br />MODULE DOES NOT INTERRUPT A GROUNDED CONDUCTOR TO ANOTHER MODULE.
<br />7. EACH MODULE WILL BE GROUNDED USING THE SUPPLIED CONNECTION POINTS IDENTIFIED IN THE
<br />MANUFACTURER'S INSTALLATION INSTRUCTIONS.
<br />8. ENCLOSURES SHALL BE PROPERLY PREPARED WITH REMOVAL OF PAINT/FINISH AS APPROPRIATE WHEN
<br />GROUNDING EQUIPMENT WITH TERMINATION GROUNDING LUGS.
<br />9. GROUNDING SYSTEM COMPONENTS SHALL BE LISTED FOR THEIR PURPOSE, AND GROUNDING DEVISES
<br />EXPOSED TO THE ELEMENTS SHALL BE RATED FOR DIRECT BURIAL.
<br />10. GROUNDING AND BONDING CONDUCTORS SHALL BE COPPER, SOLID OR STRANDED, AND BARE WHEN
<br />EXPOSED.
<br />11. EQUIPMENT GROUNDING CONDUCTORS SHALL BE SIZED ACCORDING TO [NEC 690.45] AND BE A
<br />MINIMUM OF 10 AWG WHEN NOT EXPOSED TO DAMAGE (6 AWG SHALL BE USED WHEN EXPOSED TO
<br />DAMAGE).
<br />12. GROUNDING AND BONDING CONDUCTORS, IF INSULATED, SHALL BE COLOR CODED GREEN (OR MARKED
<br />GREEN IF 4 AWG OR LARGER).
<br />13. ALL CONDUIT BETWEEN THE UTILITY AC DISCONNECT AND THE POINT OF CONNECTION SHALL HAVE
<br />GROUNDED BUSHINGS AT BOTH ENDS.
<br />14. SYSTEM GEC SIZED ACCORDING TO [NEC 690.471, [NEC TABLE 250.661, DC SYSTEM GEC SIZED
<br />ACCORDING TO [NEC 250.166], MINIMUM 8 AWG WHEN INSULATED, 6 AWG WHEN EXPOSED TO DAMAGE.
<br />15. EXPOSED NON -CURRENT CARRYING METAL PARTS OF MODULE FRAMES, EQUIPMENTS, AND
<br />CONDUCTOR ENCLOSURES SHALL BE GROUNDED IN ACCORDANCE WITH [NEC 250.1341 OR [NEC 250.136(A)]
<br />REGARDLESS OF VOLTAGE.
<br />WIRING & CONDUIT NOTES
<br />MICROINVERTER TO
<br />MAX. SHORT CIRCUIT CURRRENT (ISC) =
<br />11.8 AAC
<br />JUNCTION BOX (1)
<br />MAX. CURRENT (ISC X1.25) =
<br />14.7 A AC
<br />CONDUCTOR (TC-ER, COPPER (90°C)) =
<br />12 AWG
<br />CONDUCTOR RATING =
<br />30 A
<br />AMB. TEMP_ AMP. CORRECTION =
<br />1
<br />ADJUSTED AMP. =
<br />30 >
<br />14.7
<br />JUNCTION BOX TO
<br />MAX. SHORT CIRCUIT CURRRENT (ISC) =
<br />11.8 A AC
<br />JUNCTION BOX (2)
<br />MAX. CURRENT (ISC X1_25) =
<br />14.7 AAC
<br />CONDUCTOR (UF-B, COPPER (60°C)) =
<br />10 AWG
<br />CONDUCTOR RATING =
<br />30 A
<br />CONDUIT FILL DERATE =
<br />1
<br />AMB. TEMP. AMP. CORRECTION =
<br />1
<br />ADJUSTED AMP. =
<br />30 >
<br />14.7
<br />JUNCTION BOX TO
<br />MAX. SHORT CIRCUIT CURRRENT (ISC) =
<br />11.8 A AC
<br />COMBINER BOX (3)
<br />MAX. CURRENT (ISC X1.25) =
<br />14.7 A AC
<br />CONDUCTOR (UF-B, COPPER (60°C)) =
<br />10 AWG
<br />CONDUCTOR RATING =
<br />30 A
<br />CONDUIT FILL DERATE =
<br />0.8
<br />AMB. TEMP. AMP. CORRECTION =
<br />1
<br />ADJUSTED AMP. =
<br />24 >
<br />14.7
<br />COMBINER BOX TO
<br />INVERTER RATED AMPS=
<br />32.8AAC
<br />MAIN PV OCPD (15)
<br />MAX. CURRENT (RATED AMPS X1.25) =
<br />40.94 AAC
<br />CONDUCTOR (THWN-2, COPPER (75-C TERM.)) =
<br />8 AWG
<br />CONDUCTOR RATING=
<br />50A
<br />CONDUIT FILL DERATE =
<br />1
<br />AMB. TEMP_ AMP. CORRECTION =
<br />1
<br />ADJUSTED AMP. =
<br />50 >
<br />40.9
<br />1. ALL CONDUIT SIZES AND TYPES, SHALL BE LISTED FOR ITS PURPOSE AND APPROVED FOR THE SITE
<br />APPLICATIONS.
<br />2. BOLTED CONNECTION REQUIRED IN DC DISCONNECTS ON THE WHITE GROUNDED CONDUCTOR (USE
<br />POLARIS BLOCK OR NEUTRAL BAR).
<br />3. ANY CONNECTION ABOVE LIVE PARTS MUST BE WATERTIGHT. REDUCING WASHERS DISALLOWED ABOVE
<br />LIVE PARTS, MEYERS HUBS RECOMMENDED
<br />4. UV RESISTANT CABLE TIES (NOT ZIP TIES) USED FOR PERMANENT WIRE MANAGEMENT OFF THE ROOF
<br />SURFACE IN ACCORDANCE WITH [NEC 110.2,110.3(A-B)].
<br />5. SOLADECK JUNCTION BOXES MOUNTED FLUSH WITH ROOF SURFACE TO BE USED FOR WIRE
<br />MANAGEMENT AND AS FLASHED ROOF PENETRATIONS FOR INTERIOR CONDUIT RUNS.
<br />6. ALL PV CABLES AND HOMERUN WIRES BE TYPE USE-2, AND SINGLE -CONDUCTOR CABLE LISTED AND
<br />IDENTIFIED AS PV WIRE, TYPE TC-ER, OR EQUIVALENT; ROUTED TO SOURCE CIRCUIT COMBINER BOXES AS
<br />REQUIRED.
<br />7. ALL CONDUCTORS AND OCPD SIZES AND TYPES SPECIFIED ACCORDING TO [NEC 690.8] FOR MULTIPLE
<br />CONDUCTORS.
<br />8. ALL PV DC CONDUCTORS IN CONDUIT EXPOSED TO SUNLIGHT SHALL BE INSTALLED AT LEAST 7/8" ABOVE
<br />THE ROOF SURFACE AND DERATED ACCORDING TO [NEC TABLE 310.15 (B)(2)(A)], [NEC TABLE
<br />310.15(B)(3)(A)],& [NEC 310.15(13)(3)(C)].
<br />9. EXPOSED ROOF PV DC CONDUCTORS SHALL BE USE-2, 900C RATED, WET AND UV RESISTANT, AND UL
<br />LISTED RATED FOR 600V, UV RATED SPIRAL WRAP SHALL BE USED TO PROTECT WIRE FROM SHARP
<br />EDGES.
<br />10. PHASE AND NEUTRAL CONDUCTORS SHALL BE DUAL RATED THHN/THWN-2 INSULATED, 90°C RATED,
<br />WET AND UV RESISTANT, RATED FOR 600V
<br />11.4-WIRE DELTA CONNECTED SYSTEMS HAVE THE PHASE WITH THE HIGHER VOLTAGE TO GROUND
<br />MARKED ORANGE OR IDENTIFIED BY OTHER EFFECTIVE MEANS.
<br />12. ALL SOURCE CIRCUITS SHALL HAVE INDIVIDUAL SOURCE CIRCUIT PROTECTION
<br />13. VOLTAGE DROP LIMITED TO 2% FOR DC CIRCUITS AND 3% FOR AC CIRCUITS
<br />14. NEGATIVE GROUNDED SYSTEMS DC CONDUCTORS SHALL BE COLOR CODED AS FOLLOWS: DC
<br />POSITIVE- RED (OR MARKED RED), DC NEGATIVE- GREY (OR MARKED GREY)
<br />15. POSITIVE GROUNDED SYSTEMS DC CONDUCTORS COLOR CODED:
<br />DC POSITIVE- GREY (OR MARKED GREY), DC NEGATIVE- BLACK (OR MARKED BLACK)
<br />16. AC CONDUCTORS >4AWG COLOR CODED OR MARKED: PHASE A OR L1- BLACK, PHASE B OR L2- RED,
<br />PHASE C OR L3- BLUE, NEUTRAL- WHITE/GRAY
<br />USE-2 IS NOT INDOOR RATED BUT PV CABLE IS RATED THWN/THWN-2 AND MAY BE USED INSIDE
<br />** USE-2 IS AVAILABLE AS UV WHITE
<br />17. RIGID CONDUIT, IF INSTALLED, (AND/OR NIPPLES) MUST HAVE A PULL BUSHING TO PROTECT WIRES.
<br />18. IF CONDUIT DETERMINED TO BE RAN THROUGH ATTIC IN FIELD THEN CONDUIT WILL BE EITHER EMT,
<br />FMC, OR MC CABLE IF DC CURRENT COMPLYING WITH [NEC 690.311, [NEC 250.118(10)1. DISCONNECTING
<br />MEANS SHALL COMPLY WITH [NEC 690.131 AND [NEC 690.151.
<br />19. CONDUIT RAN THROUGH ATTIC WILL BE AT LEAST 18" BELOW ROOF SURFACE COMPLYING WITH [NEC
<br />230.6(4)] AND SECURED NO GREATER THAN 6' APART PER [NEC 330.30(B)].
<br />rt t W
<br />�Q+ of W'ASfl,f�C�f�
<br />4
<br />54072 0
<br />�F cI�R� `
<br />SS7UNAL
<br />2023,11,0
<br />BLUE RAVEN
<br />1403 N. Research Way
<br />Orem, UT 84097
<br />800.377.4480
<br />W W W.BLUERAVENSOLAR.COM
<br />CONFIDENTIAL- THE INFORMATION
<br />HEREIN CONTAINED SHALL NOT BE
<br />USED FOR THE BENEFIT OF ANYONE
<br />EXCEPT BLUE RAVEN SOLAR NOR
<br />SHALL IT BE DISCLOSED IN WHOLE OR
<br />IN PART TO OTHERS OUTSIDE
<br />RECIPIENTS ORGANIZATION, EXCEPT
<br />IN CONNECTION WITH THE SALE AND
<br />USE OF THE RESPECTIVE EQUIPMENT,
<br />WITHOUT THE WRITTEN PERMISSION
<br />OF BLUE RAVEN SOLAR LLC.
<br />NABCEP
<br />CERTIFIED
<br />PV INSTALLATION
<br />PROFESSIONAL
<br />Scott Gumey
<br />#PV-011719-015866
<br />CONTRACTOR:
<br />BRS FIELD OPS
<br />800-377-4480
<br />Z
<br />O o
<br />CQ N
<br />G 00
<br />>
<br />LL O Q .-
<br />Z 0
<br />LU (�
<br />IY] Ci)
<br />U � w
<br />Q Q
<br />Lo Y
<br />I` Lt7
<br />(D
<br />N N
<br />0) U)
<br />G G
<br />U) y
<br />y
<br />Q
<br />DRAWING BY:
<br />Brendan Fillmore
<br />PLOT DATE:
<br />November 3, 2023
<br />PROJECT NUMBER
<br />870808
<br />6 09:30:30 SHEET NAME
<br />7 ELEC CALCS
<br />0 / ' 0 0' REVISIONTPV6