MODULE SPECIFICATIONS REC Solar REC420AA PURE-R DESIGN LOCATION AND TEMPERATURES CONDUCTOR SIZE CALCULATIONS
<br /> RATED POWER(STC) 420 W TEMPERATURE DATA SOURCE ASHRAE 2%AVG.HIGH TEMP MYCROINVERTER TO MAX-SHORT CIRCUIT CURRRENT(ISC)= 13.1 A AC
<br /> MODULE VOC 59.4 V DC STATE Washington JUNCTION BOX(1) MAX.CURRENT(ISC X1.25)= 16.4 A AC
<br /> MODULE VMP 50 V DC CITY Everett CONDUCTOR(TC-ER,COPPER(90-C))= 12 AWG BLUE RAVEN
<br /> MODULE IMP 8.4 A DC WEATHER STATION SNOHOMISH CO CONDUCTOR RATING= 30 A
<br /> MODULE ISC 8.88 A DC ASHRAE EXTREME LOW TEMP('C) 5 AMB.TEMP.AMP.CORRECTION= 1
<br /> VOC CORRECTION -0.24%/°C ASHRAE 2%AVG.HIGH TEMP('C) 26 ADJUSTEDAMP,= 30 > 16.4 1403 N. Research Way
<br /> VMP CORRECTION -0.24 %/'C JUNCTION BOX TO MAX.SHORT CIRCUIT CURRRENT(ISC)= 13.1 A AC Orem, UT 84097
<br /> SERIES FUSE RATING 25 A DC 5'+5 TEM ELECTRICAL SPECIFICATIONS CIR 1 CIR 2 CIR 3 CIR 4 CIR 5 GR 6 JUNCTION BOX(2) MAX.CURRENT(ISC X1.25)= 16.4 A AC 800.377.4480
<br /> WWW.BLU E RAVENSOLAR.COM
<br /> ADJ.MODULE VOC @ ASHRAE LOW TEMP 63.7 V DC NUMBER OF MODULES PER MPPT 10 9 CONDUCTOR(UF B,COPPER(60-C))= 10 AWG CONFIDENTIAL-THE INFORMATION
<br /> ADJ.MODULE VMP @ ASHRAE 2%AVG.HIGH TEMP 46.0 V DC DC POWER RATING PER CIRCUIT(STC) 4200 3780 CONDUCTOR RATING= 30 A HEREIN CONTAINED SHALL NOT BE
<br /> TOTAL MODULE NUMBER 19 CONDUIT FILL DERATE= I USED FOR THE BENEFIT OF ANYONE
<br /> EXCEPT BLUE RAVEN SOLAR NOR
<br /> MICROINVERTER SPECIFICATIONS Enphase IQ7X Mtcrolnverters STC RATING OF ARRAY 7980 AMB. TEMP,AMP.CORRECTION= I SHALL IT BE DISCLOSED IN WHOLE OR
<br /> IN PART TO OTHERS OUTSIDE
<br /> POWER POINT TRACKING(MPPT)MIN/MAX 53 - 64 V DC AC CURRENT @ MAX POWER POINT(IMP 13.1 11.8 AD)USTEDAMP.= 30 > 16.4 RECIPIENTS ORGANIZATION,EXCEPT
<br /> MAXIMUM INPUT VOLTAGE 79.5 V DC MAX.CURRENT(IMP X 1.25) 16.375 14.7375 JUNCTION BOX TO MAX.SHORT CIRCUIT CURRRENT(ISC)= 13.1 A AC IN CONNECTION WITH THE SALE AND
<br /> USE OF THE RESPECTIVE EQUIPMENT,
<br /> MAXIMUM DC SHORT CIRCUIT CURRENT 10 A DC OCPD CURRENT RATING PER CIRCUIT 20 20 COMBINER BOX(3) MAX.CURRENT(ISC X1-25)= 16-4 A AC WITHOUT THE WRITTEN PERMISSION
<br /> MAXIMUM USABLE DC INPUT POWER 460 V' MAX COMB.ARRAY AC CURRENT(IMP) 24.9 CONDUCTOR(UF B,COPPER(60-C))= 10 AWG OF BLUE RAVEN SOLAR LLC.
<br /> MAXIMUM OUTPUT CURRENT 1.31 A AC MAX.ARRAY AC POWER_ 5985W AC_ CONDUCTOR RATING= 30 A
<br /> AC OVERCURRENT PROTECTION 20 A CONDUIT FILL DERATE= 0.8 NABCEP
<br /> MAXIMUMOUIPUT POWER 315 W AC VOLTAGE RISE CALCULATIONS DIST FT COND. /RISE V VEND(V) %VRISE AMB. TEMP.AMP.CORRECTION= 1 CERTIFIED
<br /> CEC WEIGHTED EFFICIENCY 9750% VRISE SEC. 1(MICRO TO)BOX) 36 12 Cu. 1.45 241.45 0.61% ADJUSIEDAMP.= 24 > 16.4
<br /> VRISE SEC.2()BOX TO COMBINER BOX) 45 10 Cu. 1.50 241.50 0.62% COMBINER BOX TO INVERTER RATED AMPS= 24.9 A AC PV INSTALLATION
<br /> AC PHOTOVOLATIC MODULE MARKING(NEC 690.52) VRISE SEC.3(COMBINER BOX TO POI) 5 8 Cu 0.20 240.20 0.08% MAIN PV OCPD(15) MAX-CURRENT(RATED AMPS X1.25)= 31.11 A AC PROFESSIONAL
<br /> NOMINAL OPERATING AC VOLTAGE 240 V AC TOTAL VRISE 3.15 243.15 1.31% CONDUCTOR(THWN 2,COPPER(75-C TERM.))= 8 AWG Scott Gurney
<br /> #PV-011719-015866
<br /> NOMINAL OPERATING AC FREQUENCY 47-68 HZ AC CONDUCTOR RATING= 50 A
<br /> MAXIMUMAC POWER 240 VA AC PHOTOVOLTAIC AC DISCONNECT OUTPUT LABEL NEC 690.54) CONDUIT FILL DERATE= 1 CONTRACTOR:
<br /> MAXIMUMAC CURRENT 1.0 A AC AC OUTPUT CURRENT 24.9 A AC AMB. TEMP,AMP.CORRECTION= 1 BRS FIELD OPS
<br /> MAXIMUM OCPD RATING FOR AC MODULE 20 A AC NOMINAL AC VOLTAGE 240 V AC ADJUSTEDAMP. = 50 > 31.1 800-377-4480
<br /> Q 0
<br /> GROUNDING NOTES WIRING &CONDUIT NOTES
<br /> 1.A GROUNDING ELECTRODE SYSTEM IN ACCORDANCE WITH[NEC 690.47]AND[NEC 250.50-60]SHALL BE 1.ALL CONDUIT SIZES AND TYPES,SHALL BE LISTED FOR ITS PURPOSE AND APPROVED FOR THE SITo E
<br /> PROVIDED. PER[NEC 690.47],THE GROUNDING ELECTRODE SYSTEM OF AN EXISTING BUILDING MAY BE APPLICATIONS. O -lid
<br /> 00 co
<br /> USED AND BE BONDED AT THE SERVICE ENTRANCE. IF EXISTING SYSTEM IS INACCESSIBLE, OR 2. BOLTED CONNECTION REQUIRED IN DC DISCONNECTS ON THE WHITE GROUNDED CONDUCTOR USE C14 0.)
<br /> INADEQUATE,OR IS ONLY METALLIC WATER PIPING,A SUPPLEMENTAL GROUNDING ELECTRODE WILL BE POLARIS BLOCK OR NEUTRAL BAR). CC OQ
<br /> USED AT THE INVERTER LOCATION CONSISTING OF A UL LISTED 8 FT GROUND ROD WITH ACORN CLAMP. 3.ANY CONNECTION ABOVE LIVE PARTS MUST BE WATERTIGHT.REDUCING WASHERS DISALLOWED ABOVE G M LO T`
<br /> 2.THE GROUNDING ELECTRODE CONDUCTOR SHALL BE PROTECTED FROM PHYSICAL DAMAGE BETWEEN LIVE PARTS,MEYERS HUBS RECOMMENDED
<br /> THE GROUNDING ELECTRODE AND THE PANEL(OR INVERTER)IF SMALLER THAN#6 AWG COPPER WIRE 4.UV RESISTANT CABLE TIES(NOT ZIP TIES)USED FOR PERMANENT WIRE MANAGEMENT OFF THE ROOF O 0 W W
<br /> PER [NEC 250.64(B)]. THE GROUNDING ELECTRODE CONDUCTOR WILL BE CONTINUOUS, EXCEPT FOR SURFACE IN ACCORDANCE WITH[NEC 110.2,110.3(A-B)]. LL 0 N N
<br /> SPLICES OR JOINTS AT BUSBARS WITHIN LISTED EQUIPMENT PER[NEC 250.64(C)]. 5. SOLADECK JUNCTION BOXES MOUNTED FLUSH WITH ROOF SURFACE TO BE USED FOR WIRE Zy
<br /> 3.GROUNDING ELECTRODE CONDUCTORS SHALL BE NO LESS THAN 8 AWG AND NO GREATER THAN 6 AWG MANAGEMENT AND AS FLASHED ROOF PENETRATIONS FOR INTERIOR CONDUIT RUNS.
<br /> COPPER AND BONDED TO THE EXISTING GROUNDING ELECTRODE TO PROVIDE FOR A COMPLETE SYSTEM. 6.ALL PV CABLES AND HOMERUN WIRES BE TYPE USE-2,AND SINGLE-CONDUCTOR CABLE LISTED AND Q U✓ C
<br /> 4.PV SYSTEM SHALL BE GROUNDED IN ACCORDANCE TO[NEC 250.21],[NEC TABLE 250.122],AND ALL METAL IDENTIFIED AS PV WIRE,TYPE TC-ER,OR EQUIVALENT;ROUTED TO SOURCE CIRCUIT COMBINER BOXES AS q 0 c
<br /> PARTS OR MODULE FRAMES ACCORDING TO[NEC 690.46]. REQUIRED. CWC (10) X LU LU
<br /> M LU LU
<br /> 5.MODULE SOURCE CIRCUITS SHALL BE GROUNDED IN ACCORDANCE TO[NEC 690.42]. 7.ALL CONDUCTORS AND OCPD SIZES AND TYPES SPECIFIED ACCORDING TO[NEC 690.81 FOR MULTIPLE G
<br /> 6.THE GROUNDING CONNECTION TO A MODULE SHALL BE ARRANGED SUCH THAT THE REMOVAL OF A CONDUCTORS.
<br /> MODULE
<br /> N 0
<br /> MODULE DOES NOT INTERRUPT A GROUNDED CONDUCTOR TO ANOTHER MODULE. 8.ALL PV DC CONDUCTORS IN CONDUIT EXPOSED TO SUNLIGHT SHALL BE INSTALLED AT LEAST 7/8"ABOVE 0 Z 6
<br /> 7. EACH MODULE WILL BE GROUNDED USING THE SUPPLIED CONNECTION POINTS IDENTIFIED IN THE THE ROOF SURFACE AND DERATED ACCORDING TO [NEC TABLE 310.15 (B)(2)(A)], [NEC TABLE
<br /> INSTALLATIONMANUFACTURER'S 04
<br /> 8.ENCLOSU ES SHALL BE PRO ER PROPERLY RED WITH REMOVAL OF PAINT/FINISH AS APPROPRIATE WHEN 9. EXPOSED AROOF PV DC CON(DU(CT]ORS SHALL BE USE-2,90*C RATED,WET AND UV RESISTANT,AND UL = (6 O > U V
<br /> GROUNDING EQUIPMENT WITH TERMINATION GROUNDING LUGS. LISTED RATED FOR 600V, UV RATED SPIRAL WRAP SHALL BE USED TO PROTECT WIRE FROM SHARP V J Cfl W Q D
<br /> 9.GROUNDING SYSTEM COMPONENTS SHALL BE LISTED FOR THEIR PURPOSE,AND GROUNDING DEVISES EDGES.
<br /> EXPOSED TO THE ELEMENTS SHALL BE RATED FOR DIRECT BURIAL. 10. PHASE AND NEUTRAL CONDUCTORS SHALL BE DUAL RATED THHN/THWN-2 INSULATED, 90-C RATED,
<br /> 10.GROUNDING AND BONDING CONDUCTORS SHALL BE COPPER,SOLID OR STRANDED,AND BARE WHEN WET AND UV RESISTANT,RATED FOR 600V DRAWING BY:
<br /> EXPOSED. 11. 4-WIRE DELTA CONNECTED SYSTEMS HAVE THE PHASE WITH THE HIGHER VOLTAGE TO GROUND
<br /> 11. EQUIPMENT GROUNDING CONDUCTORS SHALL BE SIZED ACCORDING TO [NEC 690.45] AND BE A MARKED ORANGE OR IDENTIFIED BY OTHER EFFECTIVE MEANS. Michael Horley
<br /> MINIMUM OF 10 AWG WHEN NOT EXPOSED TO DAMAGE (6 AWG SHALL BE USED WHEN EXPOSED TO 12.ALL SOURCE CIRCUITS SHALL HAVE INDIVIDUAL SOURCE CIRCUIT PROTECTION
<br /> DAMAGE). 13.VOLTAGE DROP LIMITED TO 2%FOR DC CIRCUITS AND 3%FOR AC CIRCUITS PLOT DATE:
<br /> 12.GROUNDING AND BONDING CONDUCTORS,IF INSULATED,SHALL BE COLOR CODED GREEN(OR MARKED 14. NEGATIVE GROUNDED SYSTEMS DC CONDUCTORS SHALL BE COLOR CODED AS FOLLOWS: DC
<br /> GREEN
<br /> 3.ALL CONDUIT BETWEEN IF 4 AWG ORTHE UTILITY AC DISCONNECT AND THE POINT OF CONNECTION SHALL HAVE POSITIVE-PIOSITIVE GROUN ED SYSTEMS DC COND CTORS COLOR CODED GREY) January 3, 2024
<br /> GROUNDED BUSHINGS AT BOTH ENDS. DC POSITIVE-GREY(OR MARKED GREY),DC NEGATIVE-BLACK(OR MARKED BLACK)
<br /> 14. SYSTEM GEC SIZED ACCORDING TO [NEC 690.47], [NEC TABLE 250.66], DC SYSTEM GEC SIZED 16.AC CONDUCTORS>4AWG COLOR CODED OR MARKED: PHASE A OR L1-BLACK,PHASE B OR L2-RED, PROJECT NUMBER:
<br /> ACCORDING TO[NEC 250.1661,MINIMUM 8 AWG WHEN INSULATED,6 AWG WHEN EXPOSED TO DAMAGE. PHASE C OR L3-BLUE,NEUTRAL-WHITE/GRAY
<br /> 15. EXPOSED NON-CURRENT CARRYING METAL PARTS OF MODULE FRAMES, EQUIPMENTS, AND USE-2 IS NOT INDOOR RATED BUT PV CABLE IS RATED THWN/THWN-2 AND MAY BE USED INSIDE O 0 O 820030 CONDUCTOR ENCLOSURES SHALL BE GROUNDED IN ACCORDANCE WITH[NEC 250.1341 OR[NEC 250.136(A)] USE-2 IS AVAILABLE AS UV WHITE 8
<br /> REGARDLESS OF VOLTAGE. 17.RIGID CONDUIT,IF INSTALLED,(AND/OR NIPPLES)MUST HAVE A PULL BUSHING TO PROTECT WIRES.
<br /> 18. IF CONDUIT DETERMINED TO BE RAN THROUGH ATTIC IN FIELD THEN CONDUIT WILL BE EITHER EMT, SHEET NAME:
<br /> FMC, OR MC CABLE IF DC CURRENT COMPLYING WITH [NEC 690.31], [NEC 250.118(10)]. DISCONNECTING
<br /> MEANS SHALL COMPLY WITH[NEC 690.13]AND[NEC 690.15]. E L E C CALC S
<br /> 19.CONDUIT RAN THROUGH ATTIC WILL BE AT LEAST 18"BELOW ROOF SURFACE COMPLYING WITH[NEC
<br /> 230.6(4)]AND SECURED NO GREATER THAN 6'APART PER[NEC 330.30(B)]. REVISION: PAGE NUMBER:
<br /> B PV6