SECTION 26 Dw0- COMMON ELECTRICAL REQUIREMENTS <br />-I GENERAL <br />1.01SUMMARY <br />A. PROVIDE ALL LABOR MATERIALS, EQUIPMENTAND INCIDENTALS FOR COMPLETION OF ALL ELECTRICAL SYSTEMS DESCRIBED HEREIN. ALL <br />ELECTRICAL EQUIPMENT AND MATERIAL SHALL BE INSTALLED IN ACCORDANCE WITH REQUIREMENTS, GOVERNING AUTHORITIES, AND IN A <br />MENMENSKILLEDAMNCE WITH THE STANDARD PRACTICES OF THE <br />ELECTRICAL INDUSTRY KALL ELECTRICAL SYSTEMS SHALL BE COMPLETE AND OPERATIONAL TO THE BENEFIT OF THE OWNER, <br />1. GOOD WORKMANSHIP AND APPEARANCE ARE CONSIDERED EQUAL TO PROPER OPERATION. <br />2 THE CONTRACTOR SHALL PROVIDE ALL FORESEEABLE ELECTRICAL EQUIPMENT AND ACCESSORIES NECESSARY, WHETHER SPECIFICALLY <br />STATED OR NOT, TO MAKE THE REQUIRED ELECTRICAL SYSTEMS COMPLETE AND OPERATIONAL. <br />ELECTRICAL CONTRACTOR SHALL COMPLY WITH THE REQUIREMENTS OF THE GENERAL CONDITIONS, SUPPLEMENTAL GENERAL <br />CONDITIONS OF THE PROJECT SPECIFICATIONS, ANY BASE BUILDING SPECIFICATIONS AND BUILDING CRITERIA, AND ALL CONTRACT <br />SPECIFICATIONS AND DOCUMENTS, <br />C. COORDINATE AND ORDER THE PROGRESS OF ELECTRICAL WORK TO CONFORM TO THE OWNER'S SCHEDULE AND THE PROGRESS OF THE <br />WORK OF THE OTHER TRADES. <br />D. APPLY FOR AND PAY FOR ALL PERMITS. FEES, LICENSES AND INSPECTIONS FOR THIS DIVISION OF WORK. <br />E. PROVIDE TEMPORARY LIGHTING AND POWER AS REQUIRED. <br />F. VISITTHEPROJECT BEFORE SUBMITTING A BID AS NO EXTRAS WILL BE ALLOWED FOR LACK OF KNOWLEDGE OF OBVIOUS EXISTING <br />CONDITIONS. <br />DRAWINGS ARE DIAGRAMMATIC IN NATURE. TAKE ALL DIMENSIONS FROM ARCHITECTURAL DRAWINGS, CERTIFIED EQUIPMENT DRAWINGS <br />G AND FROM THE STRUCTURE ITSELF BEFORE FABRICATING ANY WORK. <br />102DEFINITIONS AND STANDARDS <br />A. 'PROVIDE' MEANS CONTRACTOR IS RESPONSIBLE FOR THE FURNISHING AND INSTALLATION OF. <br />B. 'EXPOSED' MEANS WHERE IT CAN BE SEEN AFTER THE BUILDING IS COMPLETED SUCH AS IN EQUIPMENT ROOMS, UNFINISHED AREAS, <br />ACCESSIBLE TUNNELS, ETC. WHERE CONDUIT/EQUIPMENT IS ACCESSIBLE. <br />C. 'CONCEALED' MEANS WHERE IT CANNOT BE SEEN AFTER THE BUILDING IS COMPLETED SUCH AS IN SPACES AS CHASES, TRENCHES, ABOVE <br />CEILINGS, IN WALLS AND BURIED WHERE CONDUITM'IRE IS INACCESSIBLE WHEN BUILDING IS COMPLETED. <br />D. STANDARDS FOR MATERIALS: ALL MATERIALS SHALL BE NEW EXCEPTAS OTHERWISE STATED, AND SHALL CONFORM WITH THE CURRENT <br />APPLICABLE INDUSTRY STANDARDS, NEMA STANDARDS AND UNDERWRITERS' LABORATORIES STANDARDS, <br />E. COMPLY WITH THE LATEST FEDERAL, STATE AND LOCAL CODES REQUIREMENTS, AND ORDINANCES, WITH THE NATIONAL ELECTRICAL CODE <br />IF THE NATIONAL FIRE N ASSOCIATION, AND WUTR REQUIREMENTS OF THE POWER AND TELEPHONE COMPANIES FURNISHING <br />SERVICES TO THE PROJECTT THE FOLLOWING IS A BRIEF LIST OF APPLICABLE CODES: <br />A NO. TO -NATIONAL ELECTRICAL CODE, LATEST EDITION <br />2. NFPA NO. 72_ FIRE ALARM, LATEST EDITION <br />3, NFPA N0.lot <br />- LIFE SAFETY CODE. LATEST EDITION <br />4. IBC S UBC, LATEST EDITION <br />5. LOCAL BUILDING CODES, LATEST EDITION <br />PROVIDE TESTING OF ALL ELECTRICAL SYSTEMS AND COMPONENTS AS REQUIRED BY ALL APPLICABLE BUILDING CODES AND ORDINANCES, <br />UL,ANSI, ICEA, NECA,ETC, AND AS RECOMMENDED BYTHE ELECTRICAL EQUIPMENT MANUFACTURER, <br />1.038UBMITTALS <br />A. SHOP DRAWINGS: SUBMIT SHOP DRAWINGS AS REQUIRED IN DiVSION 1 FORALL MATERIALS AND EQUIPMENT. IFTHE SHOP DRAWINGS <br />DEVIATE FROM THE CONTRACT DOCUMENTS ADVISE THE ENGINEER OF THE DEVIATIONS VIA WRITTEN FORMAT, ACCOMPANYING THE SHOP <br />DRAWINGS. INCLUDE THE REASON FOR THE DEVIATION(5). COORDINATE ALL REQUIRED CHANGES WITH THE OTHER TRADES AFFECTED. IF <br />THE CHANGES ARE OCCASIONED BY THE CONTRACTOR, THE CONTRACTOR SHALL PAY MY COSTS INVOLVED, SHOP DRAWINGS SHALL <br />INcLU BUTAREN OT'MITEO TO THE FOLLawlrvc: <br />1. PRODUCT DATA FIZI-ECTRICAL IDENTIFICATION. <br />1, PRIDUCT A FOR WIRING DEVICES. <br />3. PRODUCT DATA FOR LIGHTING CONTROL DEVICES. <br />4, PRODUCTDATAFOREQUIPMENTWIRINGSYETEMS, <br />DUCTDATAAND DRAWINGS FOR PANELBOAROS. <br />fi. PRODUCT DATA FOR LIGHTING. <br />1, PRODUCTDATA,CALCUATIONSANODRAWINGSFORFIREALARMSYSTEM, <br />8. TEST REPORTS AS REQUIRED. <br />9. CERTIFICATES OF OPERATION AS REQUIRED. <br />-WARRANTY A. FIR VIDEA WRITTEN WARRANTYTO THE OWNER COVERING THE ENTIRE ELECTRICAL WORK EXCLUDING INCANDESCENT, FLUORESCENT, <br />AND HID LAMPS, TO BE FREE FROM DEFECTIVE MATERIALS, EQUIPMENT AND WORKMANSHIP FORA PERIOD OF ONE YEAR AFTER DATE OF <br />ACIEITMIEAIIEFE-IVEEIUIPMENT OR MATERIALS WHICH APPEAR DURING THE WARRANTY PERIOD SHALL BE REPLACED OR <br />REPAIRED BY THE ELECTRICAL CONTRACTOR IN ATIMELY FASHION AT NO COST TO THE OWNER, <br />1 GECLOSE OUT SUBMITTALS <br />A. OPERATION AND MAINTENANCE MANUALS: SUBMIT NUMBER AS REQUIRED BY DIVISION 1, TYPED AND HARD BOUND TO ARCHITECT FOR <br />APPROVAL PRIOR TO SCHEDULING MY SYSTEM DEMONSTRATION FOR THE OWNER AND FIFTEEN (15) DAYS PRIOR TO FINAL OBSERVATION. <br />BOIII SHALL BE ARRANGED IN SEQUENCE TO MATCH THE SPECIFICATION SECTIONS. <br />PART PRODUCTS <br />2.01 GENERAL <br />A ALLIED UIPMENT AND MATERIALS SHALL BE NEW UNLESS NOTED OTHERWISE AND ACCEPTABLE FOR INSTALLATION ONLY IF LABELED OR <br />LISTED AS DEFINED IN NFPA70, ARTICLE 100, BY UL OR BY A RECOGNIZED TESTING LABORATORY WHERE STANDARDS HAVE BEEN <br />ESTABLISHED No ACCEPTABLE TO THE AUTHORITY HAVING JURISDICTION. LABELED OR LISTED EQUIPMENT SHALL BE INSTALLED IN <br />ACCORDANCE WITH ANY INSTRUCTIONS OR LABELING PROVIDED WITH THE EQUIPMENT. <br />B. MAKE PROVISIONS FOR SAFE DELIVERY AND SECURE STORAGE OF ALL MATERIALS. <br />C. SHOULD THE CONTRACTOR WISH TO HAVE PRODUCTS CONSIDERED OTHER THAN THOSE SPECIFIED, CONTRACTOR MUST SUBMIT THOSE <br />SAS REQUIRED IN DIVISION 1. CONTRACTOR WILL BE REQUIRED TO BUBMITTHE TOTAL SAVINGS (ANTICIPATED SAVINGS) TO THE <br />OWNER. <br />PARTS EXECUTION <br />30 <br />1 GENERAL <br />A PRO VIDE ALL CORE DRILLING.CHANNELING, CUTTING. PATCHING, SLEEVES,ETC. AS REQUIRED FOR INSTALLATION OF ELECTRICAL <br />EQUIPMENT. SEAL HOLES, FIREPROOFING WHERE NECESSARY, AND REFINISH ALL REPAIR WORK TO ORIGINAL CONDITION WHERE DAMAGED <br />BY ELECTRICAL WORK. <br />1. COORDINATE CORE DRILL LOCATIONS WITH STRUCTURAL PRIOR TO WORK, <br />2. COORol A EUGSITE IUTIESWITHAPPROPRIATEUTILITYCOMPANYPwORTOMRK. <br />S. PROVIDEBRANCHCIRCUTTSTOEQUIPMENT PROVIDED BY OTHERS AND TO MECHANICAL EQUIPMENT AND MAKE ALL CONNECTIONS. <br />TEMPERATURE CONTROL EQUIPMENT WIRING AND CONNECTIONS SHALL BE PROVIDED BY THE MECHANICAL CONTRACTOR. <br />C. PROVIDESAFETYSWITCHES AND/OR THERMAL OVERLOAD SWITCHES AS REQUIRED. <br />D. HEATER UNITS IN ALL MOTOR STARTERS SHALL BE SIZED FORAPPROXIMATELY ONE HUNDRED FIFTEEN PERCENT(115%)OF FULL LOAD <br />MOTOR CURRENT. CHECK AND COORDINATEALL THERMAL PROTECTIVE DEVICES WITH THE EQUIPMENT THEY PROTECT. <br />E. PROVIDEFOREACHMOTOR,ONE-HALF(1l2) HORSEPOWER AND BELOW. A HORSEPOWER RATED DISCONNECT SWITCH AND THERMAL <br />OVERLOAD PROTECTION UNLESS INTERNALLY PROVIDED WITH THE MOTOR. THERMAL OVERLOAD SWITCHES FOR SINGLE PHASE MOTORS <br />SHALL BE ALLEN-SRADLEY BULLETIN ISO OR ACCEPTABLE. <br />F. CAREFULLY COORDINATE ALL ELECTRICAL WORK WITH ALL OTHER APPLICABLE DIVISIONS. <br />END OF SECTION <br />SECTION 26 0510 - DEMOLITION FOR REMODELING <br />PART1 GENERAL <br />OtAUTHIS SECTION INCLUDES SELECTIVE DEMOLITION FOR EXISTING SPACES. <br />-2 EXECUTION <br />ON <br />201A. FIELDCHECK ALL EXISTING CONDITIONS PRIOR TO BIDDING AND INCLUDE AN ALLOWANCE FOR THE REMOVAL AND RELOCATIONOF EXISTING <br />CONDUITS. WIRES, DEVICES, FIXTURES, OR OTHER EQUIPMENT AS INDICATED OR AS REQUIRED TO COORDINATE AND ADAPT NEW AND <br />EXISTING ELECTRICAL SYSTEMS TO ALL OTHER WORK REQUIRED ON THIS PROJECT. NO EXTRAS WILL BE ALLOWED FOR ALTERATIONS OF A <br />FORESEEABLE NATURE REQUIRED TO ACHIEVE THE END RESULT AS INDICATED ON THE DRAWINGS. <br />B. WHERE THE REUSE OF EXISTING CONDUITS, OUTLETS, JUNCTION BOXES. ETC., IS PERMISSIBLE, MAKE CERTAIN THAT THE WIRING FOR THEM <br />IS CONTINUOUS FROM OUTLET TO OUR AND THAT ALL SPLICES AND INSULATIONS ARE IN GOOD CONDITION. PROVIDE MODIFICATIONS TO <br />ASSURE THAT CIRCUITS, OR SYSTEM SHALL NOT PASB THROUGH OUTLETS OR JUNCTION BOXES WHICH MAYBE RENDERED INACCESSIBLE <br />BY CHANGES TO BE MADE TO THE PROJECT, EXISTING CONDUITS, WIRE, DEVICES, ETC., WHICH SHALL BE REMOVED SHALL BECOME THE <br />PROPERTY OF THE OWNER UNLESS <br />-TH <br />NOTE <br />MANNER C. CONNECT NEW WORK TO EXISTING IN A THAT WILL ASSURE PROPER RACEWAY GROUNDING THROUGHOUT IN CONFORMANCE WITH <br />THE NATIONAL ELECTRICAL CODE. <br />D. REMODEL WORN, CURING AND PATCHING: THIS CONTRACTOR SHALL PERFORM ALL CUTTING, CHANNELING, CHASING, DRILLING, EFC., AS <br />REQUIRED TO INSTALL OR REMOVE ELECTRICAL EQUIPMENT IN AREAS OF REMODELING. THIS WORK SHALL BE PERFORMED SO AS TO <br />MINIMIZE DAMAGE TO PORTIONS OF WALL FINISHES, SURFACES, PLASTERING, OR THE STRUCTURES WHICH ARE TO BE REUSED, <br />RESURFADED, PLASTERED, OR PAINTED UNDER OTHER DIVISIONS OF THESE SPECIFICATIONS. <br />2.SZ COORDINATION <br />A. CAREFULLY COORDINATE WITH THE REQUIRED REMODELING WORK, CUTTING AND PATCHING ETC., PERFORMED BY OTHERTRADES. <br />REMOVE OR RELOCATE EXISTING ELECTRICAL CONDUITS, WIRES, DEVICES, FIXTURES AND OTHER EQUIPMENT AS NECESSARY. <br />2.03 OUTAGES <br />NS F EXISTING ELECTRICAL SYSTEMS SHALL BE MINIMIZED AND SHALL BE AT A TIME AND OF A DURATION AS <br />A ACCEPTED BY THE OWNER <br />O <br />ENDOFSECTION <br />SECTION 260519-LOW-V0LTAGE ELECTRICAL POWER CONDUCTORS AND CABLES <br />PART GENERAL <br />1.018UMMARY <br />A. THIS SECTION INCLUDES THE FOLLOWING: <br />1, BUILDMIWIRES ANDCABLESRATED600VANDLES1. <br />2. CONNECTORS,SPLICES, AND TERMINATIONS RATED 600 V AND LESS. <br />PART PRODUCTS <br />CONDUCTORS AND CABLES <br />A. MANUFACTURERS OFFERING PRODUCTS THAT MAY BE INCORPORATED INTO THE WORK INCLUDE, BUT ARE NOT LIMITED TO, THE FOLLOWING: <br />1, AMERIOIN INSULATED WIRE CORR: A LEVITON COMPANY <br />2. GENERAL CABLE CORPORATION <br />3. SE NATORWIREBCABLECOMPANY <br />. SOUTHWIRE COMPANY <br />S. COPPER CONDUCTORS: COMPLY WITH NEMA WC 70. <br />C. MULTI CONOUCTOR CABLE: COMPLY WITH NEMA WC 70 FOR METAL -GLAD CABLE, TYPE MC WITH GROUND WIRE. <br />2.02 CONNECTORS AND SPLICES <br />A. FACTORY -FABRICATED CONNECTORS AND SPLICES OF SIZE, AMPACITY RATING, MATERIAL. TYPE. AND CLASS FOR APPLICATION AND SERVICE <br />PARTS EXECUTION <br />3.01 CONDUCTOR MATERIAL APPLICATIONS <br />A OR SIGNAL CIRCUITS, WHICH NAN' BE NO. 14 AWG OR SMALLER INCREASE CONDUCTOR <br />SIZE AS NECESSARY TO LIMIT BRANCH CIRCUIT VOLTAGE DROP TO M AND SERVICEITEEDER VOLTAGE DROP TO 2%. <br />B. -CON UCTORS SHALL BE COPPER; SOLID CONDUCTOR FOR N0.12 AWG AND SMALLER, STRANDED FOR NO. 10 MG AND LARGER. <br />C. ALL WIRING SHALL BE AS FOLLOWS: <br />1. SERVICE ENTRANCE. EXPOSED FEEDERS. AND FEEDERS CONCEALED IN CEILINGS, WALLS AND PARTITIONS: TYPE THHN. THWN OR XHHW. <br />SINGLE CONDUCTORS IN RACEWAY. <br />2. FEEDERS CONCEALED IN CONCRETE AND BELOW SLABBLON-GRADE: TYPE THHN-THWN, SINGLE CONDUCTORSIN RACEWAY. <br />3. BRAN CH CIRCUITS CONCEALED IN CEILINGS.WALLS. AND PARTITIONS. AND CONCEALED IN CONCRETE OR BELOW SLABS -ON -GRADE: TYPE <br />LE GONDUGTORS IN RACEWAY. <br />4. CORD DROPSANo PORTABLE APPLIANCE CONNECTIONS: TYPE SO, HARD SERVICE CORD. <br />5. FIRE ALARM CIRCUITS: TYPE THHN-THWN, IN RACEWAY OR POWER -LIMITED. FIRE -PROTECTIVE. SIGNALING CIRCUIT CABLE, TYPE NPLFP <br />OR PLFP. <br />1. CLASSI CONTROL CIRCUITS: TYPE THHN-THWN, IN RACEWAY <br />7. CLASS 2 CONTROL CIRCUITS: TYPETHHN-THWN, IN RACEWAYOR POWER-LIMITEDCABLE, CONGEALED IN BUILDING FINISHES. <br />30 . 2 INSTALLATION OF CONDUCTORS AND CABLES <br />A WIRING FOR CONTROL SYSTEMS SHALL BE INSTALLED IN CONJUNCTION WITH MECHANICAL AND MISCELLANEOUS EQUIPMENT. <br />. INSTALL CONDUCTORAT EACH OUTLET, WITH AT LEAST S INCHES OF SLACK TO ALLOW FOR CONNECTION TO DEVICE. <br />3.03 CONNECTIONS <br />A. SPLICES FOR No.6 AWG AND SMALLER SHALL BE MADE WITH TWIST -ON WIRE CONNECTORS. <br />S. SPLICES FOR NO.4 AWG AND LARGER SHALL BE MADE WITH SOLDERLESS OR COMPRESSION TYPE CUTALR LUGS. <br />304 FIELDQUALITYCONTROL <br />A. TESTING: PERFORM THE FOLLOWINGLITV-CONT FIELD QUAROL TESTING: <br />1. TORQUE TEST CONDUCTOR CONNECTIONS AND TERMINATIONS TO MANUFACTURER'S RECOMMENDED VALUES. <br />ERFORMCONTINUITYTESTONALLPo RANDEQUIPMENTBRANCHCIRCUITCONDUCTORS.VERIFYPROPERPHASINGCONNEUIIONS. <br />3. INSULATION TEST: MEASURE THE INSULATION OF FEEDER CONDUCTORS. MEASUREMENTS SHALL BE TAKEN BETWEEN CONDUCTORS, <br />AND CONDUCTORS AND GROUND. RESISTANCE SHALL BE 1.0W.0000HMS OR MORE WHEN TESTED AT 500 VOLTS BY MEGGER WITHOUT <br />CIRGUITLOADS. <br />B. CABLES WILL BE CONSIDERED DEFECTIVE IF THEY DO NOT PASS TESTS AND INSPECTIONS. <br />END OF SECTION <br />SECTION Z60s28 GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS <br />PART GENERAL <br />1.OtAUCONDUIT SYSTEMS, SUPPORTS, CABINETS, EQUIPMENT, TRANSFORMERS, FIXTURES, THE GROUNDED CIRCUIT CONDUCTOR, ETC. SHALL BE <br />PROPERLY GROUNDED IN ACCORDANCE WITH THE CURRENT ISSUE OF THE NATIONAL ELECTRICAL CODE. PROVIDE ALL BONDING JUMPERS <br />AND WIRE, GROUNDIN BUSHINGS, CLUMPS, ETC. AS REQUIRED FOR COMPLETE GROUNDING. <br />e. CONNECTIONS SHALL BE EITHER BOLTED -PRESSURE -TYPE COMPRESSION TYPE OR EXOTHERMIC -WELDED TYPE, <br />PART2 PRODUCTS <br />2.01 CONDUCTORS <br />A. GROUNDING CONDUCTOR MATERIAL: COPPER <br />PART I EXECUTION <br />3.01 APPLICATIONS <br />A. CONDUCTORS: INSTALLSOLIDCENDUCTORFORNO.BAWGANDSMALLER,ANDSTRANDEDCONDUCTORSFORNO.6AWGANDLARGER <br />UNLESS OTHERWISE INDICATED. <br />B. GROUNDALLCOMMUNICATIONS EQUIPMENT. <br />C. UNDERGROUNDGROUNDING CONDUCTORS:INSTALL BARE TINNEDLOPPER CONDUCTOR NO. 2 AWG MINIMUM. BURY AT LEAST It' BELOW <br />GRADE OR BELOW FROST LINE, WHICHEVER IS GREATER <br />3.02 GROUNDING AT THE SERVICE <br />A. BOND THE ELECTRICAL <br />RAL SERVICE NEUTAT SERVICE ENTRANCE EQUIPMENT PER THE CURRENT ISSUE OF THE NATIONAL ELECTRICAL <br />CODE UTILIZING MAIN COLD WATER PIPE, BUILDING STEEL, DRIVEN GROUND ROD, CONCRETE ENCASED ELECTRODE AS APPLICABLE. ROUTE <br />GROUNDING ELECTRODE CONDUCTORS TO PROVIDE THE SHORTEST AND MOST DIRECT PATH TO THE GROUND ELECTRODE SYSTEM. <br />.3 EQUIPMENT GROUNDING <br />A. PROVIDE A SEPARATE EQUIPMENT GROUNDING CONDUCTOR IN ALL FEEDER AND BRANCH CIRCUITS AND ALL FLEXIBLE AND NONMETALLIC <br />RACEWAYS. <br />3.W INSTALLATION <br />A. GROUNDINGCONDUCTORS: ROUTE ALONG SHORTESTAND STRAIGHTEST PATHS POSSIBLE UNLESS OTHERWISE INDICATED OR REQUIRED <br />BYIIDE G ACCESS OR PLACING CONDUCTORS WHERE THEY MAYBE SUBJECTED TO STRAIN, IMPACT, OR DAMAGE. <br />CONDUCTORS SHALL NOT MAKE MORE THAN A w DEGREE BEND WITH A MINIMUM BENDING RADIUS OF 12INCHES. <br />ENDOFSECTION <br />SECTION M Os29- HANGERS AND SUPPORTS FOR ELECTRICAL SYSTEMS <br />PART1 GENERAL <br />1,015UMMARV <br />A. PROVIDE HANGERS AND SUPPORTS FOR EQUIPMENT, RACEWAYS AND CABLES, INCLUDING WEIGHT OF WIRE IN RACEWAYS. ALL SYSTEMS <br />CABLING SHALL BE SUPPORTED BY BRIDAL RINGS OR SIMILAR MEANS. <br />PART <br />AR 2 PRODUCTS <br />2.01 SUPPORT ANCHORAGE AND ATTACHMENT COMPONENTS <br />A. STEEL SLOTTED SUPPORT SYSTEMS: COMPLY WITH MFMA4,FACTORY-FABRICATED COMPONENTS FOR FIELD ASSEMBLY. <br />B. MATERIAL COLD -FORMED STEEL, WITH CORROSION -RESISTANT COATING ACCEPTABLE TO AUTHORITIES HAVING JURISDICTION AND OF <br />TYPE ADEQUATE TO CARRY THE LOADS OF EQUIPMENT, RACEWAYS AND CABLES, INCLUDING WEIGHT OF WIRE IN RACEWAY. <br />C. METAL ITEMS FOR USE OUTDOORS OR IN DAMP LOCATIONS: HOT -DIP GALVANIZED STEEL. <br />D. SLOTTED -STEEL CHANNEL SUPPORTS: FLANGE EDGES TURNED TOWARD WEB, AND 9I16 INCH DIAMETER SLOTTED HOLES AT A MAXIMUM OF <br />2 INCHES O.C.. IN WEBS, <br />E. CHANNEL THICKNESS: SELECTED TO SUITE STRUCTURAL LOADING, <br />F. FITTINGS AND ACCESSORIES: PRODUCTS OF THE SAME MANUFACTURER AS CHANNEL SUPPORTS. <br />G. RACEWAYANDCABLESUPPORTS,120VOLTSANDABOVE: MANUFACTUREDCLEVIS HANGERS, RISERCLAMPS, STRAPS, THREADED <br />C-CLAMPS WITH RETAINERS, CEILING TRAPEZE HANGERS, WALL BRACKETS, AND SPRING -STEEL CLAMPS OR CLICK -TYPE HANGERS. <br />H. CABLE SUPPORTS BELOW 120 VOLTS: BRIDLE RINGB INSTALLED A MAXIMUM OF 4 FEET ON CENTER. <br />PART <br />3 EXECUTION <br />3.01 APPLICATION <br />A. MAXIMUM SUPPORT SPACING AND MINIMUM HANGER ROD SIZE FOR RACEWAY: SPACE SUPPORTS FOR CONDUIT AS REQUIRED BY NFPA 70. <br />MINIMUM ROD ER. SIZE SHALL BE 1I4INCH IN DIAMET <br />ENDOFSECTION <br />SECTION Ze VEG- RACEWAYS AND BOXES FOR ELECTRICAL SYSTEMS <br />PART1 GENERAL <br />1018UMMARY <br />A. SECTION INCLUDES METAL CONDUITS, TUBING, FITTINGS, SURFACE RACEWAY, AND BOXES, <br />PART2 PRODUCTS <br />L CONDUITS, TUBING, AND FITTINGS <br />01A. EMT <br />pCOMPLY <br />WIT H ANSI CSES AND UL 797. <br />B. FNI COMPLY <br />WITH UL 1; ZM-OATED STEEL. <br />C. LFMC: FLEXIBLE STEEL CONDUIT WITH PVC JACKET AND COMPLYING WITH UL 360. <br />D. FITTINGS FOR METAL CONDUIT: COMPLY WITH NEMA FB 1 AND UL 514B. <br />1. FITTINGSFOREMT: <br />a. MATERIAL: STEEL <br />b. TYPE: SETSCREW OR COMPRESSION. <br />2 .02 NONMETALLIC CONDUITS, TUBING, AND FIRINGS <br />A. LISTING AND LABELING: NONMETALLIC CONDUITS.TUBING, AND FITTINGS SHALL BE LISTED AND LABELED AS DEFINED IN NFPA 70.BYA <br />QUALIFIED TESTING AGENCY, AND MARKED FOR INTENDED LOCATION AND APPLICATION, <br />B. WC: TYPE EPC-0O-PVC, COMPLYING WITH NEMA TC 2 AND UL 651 UNLESS OTHERWISE INDICATED. <br />C. LFNC: COMPLY WITH UL 1660. <br />WITH NEMATC, MATCH TG CONDUI OR TUBING TYPE ANO MATERIAL. <br />E. FITTINGSFORLFNC: COMPLYWITHUL514B.3 <br />2.03 SURFACE <br />A. SURFACE METALLIC RACEWAYS SHALL BE LIMITED TO ONLY AREAS SPECIFICALLY NOTED AND OF SIZE AND TYPE SPECIFIED ON THE <br />DRAWINGS. <br />SI BOXES <br />2 A. GENERAL REQUIREMENTS FOR BOXES. ENCLOSURES, AND CABINETS: BOXES, ENCLOSURES. AND CABINETS INSTALLED IN WET LOCATIONS <br />SHALL BE LISTED FOR USE IN WET LOCATIONS. <br />e. SHE ET METAL OUTLET AND DEVICE BOXES: COMPLY WITH NEMA IS I AND UL 514A. FOUR INCH SQUARE OR OCTAGONAL, ZINC -COATED <br />SHEET STEEL TYPE, <br />C. FLOOR BOXES: AS SPECIFIED ON THE DRAWINGS, <br />PART EXECUTION <br />3.01 —APPLICATION <br />N ACCORDANCE WITH CHAPTER 9, TABLE 4 of THE NATIONAL ELECTRICAL CODE. <br />A MINIMUM SIZE 1I21NCH. ALL <br />CONDUITS SHALL BE CONCEALED IN FINISHED AREAS. <br />B. GALVANIZED RIGID METAL CONDUIT (RMC) AND INTERMEDIATE METAL CONDUIT (IMC) SHALL BE UTILIZED FOR ABOVE AND BELOW GRADE <br />I ==ARTICLES S44 AND S42 OF THE NATIONAL ELECTRICAL CODE ALL COUPLINGS SHALL BE THREADED. <br />C. ELECTRICAL MEFPLLIC TUBING IEMin HALL BE UTILIZED FOR ALL DRY, ABOVE GRADE ORABOVE FLOOR FEEDERSAND BRANCH CIRCUIT <br />HOMERUN APPLICATIONS IN ACCORDANCE WITH ARTICLE 358 OF THE NATIONAL ELECTRICAL CODE, COUPLINGS SHALL BE STEEL SET <br />D. METAL -CLAD CABLE (Ni WITH SEPARATE GROUND CONDUCTOR SHALL BE PERMITTED FOR ALL CONCEALED, ABOVE GRADE OR ABOVE <br />FLOOR BRANCH CIRCUIT APPLICATIONS EXCLUDING HOMERUNS IN ACCORDANCE WITH ARTICLE 330 OF THE NATIONAL ELECTRICAL CODE. <br />E. FLEXIBLE METALCONDUITSHALLBE UTILIZEDFOR ALL CONNECTIONSTOVIBRATING EQUIPMENT SUCH AS MOTORS MhNIMUM OF <br />MAXIMUM OF 6'-9'1, CONNECTIONS TO LAY -IN TYPE LIGHT FIXTURES OR IN REMODEL AREAS SPECIFICALLY NOTED FOR FEIGNING' IN EXISTING <br />WALLS OR NON -ACCESSIBLE CEILINGS. <br />F. RIGID NONMETALLIC CONDUIT (PVC) SHALL BE UTILIZED FOR ABOVE AND BELOW GRADE APPLICATIONS IN ACCORDANCE WITH ARTICLE 352 <br />OF THE NATIONAL ELECTRIC CODE. CONNECTIONSTO BE MADE BYTHE USE OFASUITABLE SOLVENT -TYPE CEMENT. <br />G. SURFACEMETALLIC RACEWAYS SHALL BE LIMITED TO ONLY AREAS SPECIFICALLY NOTED AND OF SIZE AND TYPE SPECIFIED ON THE <br />DRAWINGS. <br />LL CONDUITS EXPOSED OR CONGEALED SHALL BE ROUTED PARALLEL OR PERPENDICULAR WITH THE BUILDING WALLS. SUPPORT CONDUIT <br />AS REQUIRED BY THE LATEST EDITION OF THE NATIONAL ELECTRICAL CODE. <br />I. PROVIDE EXPANSION TYPE FITTINGS FOR ALL CONDUITS. WHICH CROSS EXPANSION JOINTS, <br />BOXES <br />302A. OUTLET BOXES SHALL BE LOCATED SO THAT TRANSMISSION OF SOUND THROUGH COMMON WALLS WILL NOT OCCUR. <br />B. ENCLOSURES EXPOSED TO WEATHER OR DAMP LEGATIONS SHALL BE WEATHERPROOF TYPE. <br />C. PROVIDE COVERS SET TO COME FLUSH WITH FINISHED WALLS. <br />D. PULL BOXES AND JUNCTION BOXES: JUNCTION BOXES AND PULL BOXES WILL BE PROVIDED AS REQUIRED, SIZEOFBOXESSHALLSEM <br />REQUIREMENTS. <br />1. ENCLOSURESSHALLBENEMATYPE SUITABLE FOR THESURROUNDING AREA AND CONDITIONS. <br />E. FLOOR BOXES: PROVIDE CEVERS SET TO COME FLUSH WITH FINISHED SURFACE. <br />END OF SECTION <br />SECTION 26 0553- IDENTIFICATION FOR ELECTRICAL SYSTEMS <br />1.018Um=y <br />A. SECTION INCLUDES IDENTIFICATION FOR CONDUCTORS, RACEWAYS, EQUIPMENT, AND UNDERGROUND WARNING TAPE. <br />PART2 PRODUCTS <br />201 POWER RACEWAY IDENTIFICATION MATERIALS <br />A SELEADHESIVE VINYL UBELS FOR <br />YS CARRYING CIRCUITS AT S00 V OR LESS: PREPRINTED, FLEXIBLE LABEL LAMINATED WITH A <br />CL EAR. WEATHER AND CHEMICAL -RESISTANT COATING. <br />2.02 CONDUCTOR IDENTIFICATION AND MATERIALS <br />A. CONDUCTORS 8 AWG AND SMALLER SHALL BE FACTORY COLOR CODED. CONDUCTORS 6 AWG AND LARGER MAY BE COLOR CODED BY FIELD <br />PAINTING OR COLOR TAPING A S-INCH LENGTH OF EXPOSED END. <br />RING FOR CONTROL SYSTEMS SHALL BE COLOR -CODED IN ACCORDANCE WITH THE WIRING DIAGRAMS FURNISHED WITH THE EQUIPMENT, <br />C. CONDUCTOR IDENTIFICATION SHALL BE AS FOLLOWS120- SYSTEM <br />BLACKPHASE A PHASE B RED <br />PHAIEI BLUE <br />NEUTRAL WHITE <br />GROUND GREEN <br />ISOLATED <br />GROUND GREEN W/YELLOW STRIPE <br />SWITC <br />LEG <br />PINK <br />1. COLD GOING CONDUCTOR TAPE: COLORED. SELF-ADHESIVE VINYL TAPE NOT LESS THAN 3 MILS THICK BY 1 INCH WIDE. <br />RO 2.03 UNDERGROUND-LINEWARNINGTAPE <br />A. PROVIDE DETECTABLE UNDERGROUND LINE WARNING TAPE FOR ALL UNDERGROUND ELECTRICAL SERVICE (POWER, COMMUNICATIONS, <br />ETC) SYSTEM RACEWAYS. <br />B. PRINTING ON TAPE SHALL BE PERMANENT AND SHALL NOT BE DAMAGED BY BURIAL OPERATIONS. TAPE MATERIAL AND INK SHALL BE <br />CHEMICALLY INERT. AND NOT SUBJECT TO DEGRADING WHEN EXPOSED TO ACIDS, ALKALIS, AND OTHER DESTRUCTIVE SUBSTANCES <br />COMMONLY FOUND IN SOILS, <br />2.06 EQUIPMENT IDENTIFICATION LABELS <br />A. PRO VIDEENGRAVEDNAMEPLATESFORALLELECTR-CABINETS,ENCLOSURES, PANELBOARDS, DISTRIBUTION EQUIPMENT ELECTRICAL <br />EQUIPMENT, BOXES, ETC. NAMEPLATES SHALL BE ENGRAVING STOCK MELAMINE PLASTIC LAMINATE, MINIMUM let INCH THICK FOR SIGNS UP <br />TO 20 SQUARE INCHES AND 1I4INCH THICK FOR LARGER SIZES WITH BLACK LETTERS ON A WHITE FACE OR AS REQUIRED BY CODE OR <br />OWNER, <br />PART <br />EXECUTION <br />3.IF GENERAL INSTALLATION <br />A. LOCATION: INSTALL IDENTIFICATION MATERIALS AND DEVICES AT LEGATIONS FOR MOST CONVENIENT VIEWING WITHOUT INTERFERENCE <br />WITH OPERATION AND MAINTENANCE OF EQUIPMENT. <br />B. SELF-ADHESIVE IDENTIFICATION PRODUCTS: CLEAN SURFACES BEFORE APPLICATION, USING MATERIALS AND METHODS RECOMMENDED BY <br />MANUFACTURER OF IDENTIFICATION DEVICE, <br />C. ATTACH SIGNS AND PLASTIC LABELS THAT ARE NOT SELF-ADHESIVE TYPE WITH MECHANICAL FASTENERS APPROPRIATE TO THE LOCATION <br />AND SUBSTRATE, <br />IN <br />IN <br />D, NDERGR' <br />DIRECTLY AS VEILINEAT6T08 INCHES BELOW FINISHED GRADER USE MULTIPLETAPESWHEREWIDTH OF MULTIPLE LEINWEAS INSTALLED INA <br />COMMON <br />TRENCH EXCEEDS 16 INCHES OVERALL, <br />END OFSEC <br />SECTION 26 2726- WIRING DEVICES <br />PART1 GENERAL <br />i D1A UT9S SECTION INCLUDES RECEPTACLES, GFCI RECEPTACLES, SNAP SWITCHES, DIMMERS, AND OCCUPANCY SENSORS. <br />PAU2 PRODUCTS <br />201 RECEPTACLES <br />A. RECEPTACLES SHALL BE 20 AMP PASS& SEYMOUR PS5362 SERIES SPECIFICATION GRADE, OR EQUAL, GFCI AND EXTERIOR RECEPTACLES <br />SHALL BE PASS 8 SEYMOUR 2095TRWR SERIES, OR EQUAL AND IF REQUIRED, PROVIDE WP IN USE METALTYPE COVER. PROVIDE DEVICE <br />COLOR AS DIRECTED BY THE ARCHITECT, ORTO MATCH BASE BUILDING STANDARDS, WHICHEVER IS APPLICABLE. <br />B. PROVIDE SPECIAL PURPOSE OUTLETS AS REQUIRED FOR EQUIPMENT PROVIDED BY OTHERS, <br />2.02 SNAP SWITCHES <br />A. AC QUIET OPERATING TYPE SWITCHES SHALL BE 120I2iTV, 20 AMP, PASS S SEYMOUR C820AC1 SERIES, OR EQUAL. PROVIDE DEVICE COLOR <br />AS DIRECTED BY THE ARCHITECT, OR TO MATCH BASE BUILDING STANDARDS, WHICHEVER IS APPLICABLE. <br />DIMMERS A. LUTRONCLSERIES. SLIDE TYPE RATED FOR LOAD SERVED. <br />TRONNOVAT SERIES, SLIDE TYPE FOR 0-10V DIMMING. <br />2U4 OCCUPANCY SENSORS <br />A. PIR WALL SWITCH SENSORS SHALL BE WATT STOPPER PW-100, OR EQUAL. <br />B. DUAL TECHNOLOGY WALL SWITCH SENSORS SHALL BE WATT STOPPER DW-100, OR EQUAL. <br />C. DUAL TECHNOLOGY CEILING SENSORS SHALL BE WATT STOPPER DT-355. OR EQUAL, <br />­ 'E"CEPLATES <br />2 A. DEVICE PLATES SHALL BE HIGH ABUSIVE NYLON, COLOR TO MATCH DEVICE, OR TO MATCH BASE BUILDING STANDARDS, WHICHEVER IS <br />APPLICABLE. <br />PART3 EXECUTION <br />301 INSTALLATION <br />A MOUNT DEVICES IN ACCORDANCE WITH THE FOLLOWING SCHEDULE EXCEPT WHERE OTHERWISEDRAWINGS NOTED ON THE OR IN AREAS <br />WITH COUNTERS, BASEBOARD HEATERS OR IN AREAS OF BLOCK OR BRICK CONSTRUCTION: <br />1. CONVENIENCE RECEPTACLES: LONG AXIS VERTICAL AT I'6 TO CENTER. <br />LIGHT <br />3, TELEPH UETSLEfSCLONGAXIS-OTRIZI AT 1-7AFFTO CENTER. <br />'EXCEPT IN AREAS WITH COUNTERS, BASEBOARD HEATERS, OR IN AREAS OF BLOCK OR BRICK CONSTRUCTION. <br />B. INSTALL GROUND PIN OF VERTICALLY MOUNTED RECEPTACLES UP, AND ON HORIZONTALLY MOUNTED RECEPTACLES TO THE LEFT. <br />C. ADA MOUNTING HEIGHTS TAKE PRECEDENCE OVER SCHEDULED MOUNTING HEIGHTS, <br />END OF SECTION SECTION as 5100- INTERIOR LIGHTING <br />PART 1 GENERAL <br />1.01SUMMARY <br />A. THIS SECTION INCLUDES THE FOLLOWING: <br />1. INTERIOR & EXTERIOR LUMINAIRES, LAMPS, AND DRIERS. <br />2. EMERGENCY EGRESS LIGHTING UNITS. <br />3, EXITSIGNS. <br />-SUBMITTALS <br />A. PROVIDE A SUBMITTAL FOR EACH TYPE OF LUMINAIRE, ARRANGED IN ORDER OF TYPE DESIGNATION. INCLUDE DATA ON FEATURES, <br />1, REMOTE <br />VERI, FINISHES, AND THE FOLLOWING <br />1 CPHYSICAL DESCRIPTION IOF LIGHTING FIXTURE INCLUDING DIMENSIONS, <br />2, EMERGENCYLIGHTINGUNITSINCLUDINGBATTERYANDCHARGER, <br />3. REMOTE DRIVERS AS DESIGNED. <br />4. INPUT WATTAGE, <br />LIFE (IN HOURS AND ENERGY -EFFICIENCY DATA OF SOURCE. <br />6. PHOTOMETRIC DATA, IN IESNA FORMAT, BASED ON LABORATORYTESTS OF EACH LIGHTING FIXTURE TYPE, OUTFITTED WITH LAMPS, <br />DRIERS, AND ACCESSORIES IDEMICAL TO THOSE INDICATED FOR THE LUMINAIRE AS APPLIED IN THIS PROJECT. <br />`MIN <br />TYPE <br />103CLOSEOUTISUBMITTALS <br />A. OPERATION AND MAINTENANCE DATA INCLUDE LIGHTING EQUIPMENT AND LUMINAIRES IN EMERGENCY OPERATION, NORMAL OPERATION, <br />AND MAINTENANCE MANUALS. <br />PAU2 PRODUCTS <br />NANURNITURENS <br />2 01A. SUBJECTTO COMPLIANCE WITH REQUIREMENTS IN DIVISION 1, PROVIDE PRODUCTS BYTHE MANUFACTURERS SPECIFIED ON THE DRAWINGS <br />OR PROVIDE PRODUCTS FROM MANUFACTURERS WITH SIMILAR CONSTRUCTION, INSTALIATION, WATTAGE USAGE, DIMMING TYPE, <br />DIMENSIONS, CERTIFICATIONS, FINIIHEI, IRI, CET, AND PHOTOMETRIC CHARACTERISTICS. CONTRACTOR WILL BE REQUIRED To SUBMIT THE <br />AL TOTSAVINGS (ANTICIPATED SAVINGS) TO THE OWNER. <br />B. ILLUMINATED EXIT SIGNS SHALL CONFORM TO LOCAL CODE REQUIREMENTS. <br />C. INTERIOR EMERGENCY POWER SUPPLY UNITS SHALL BE SELF-IONTAINED,MODULAR, BATTERY -INVERTER UNIT FACTDR UMEG WITHIN <br />LUMINAIRE BODY. AND SHALL COMPLY WITH UL 924. <br />D. LAMPS SHALL BE AS MANUFACTURED BY OSRAMSYLVANIA, PHILLIPS, G.E., GREE, TIP, OR VENTURE. DO NOT USE LAMPS BY ECOSAMRT. <br />E. COLOR TEMPERATURE FOR LEDs SHALL BE AS SPECIFIED IN THE DRAWINGS. <br />PART EXECUTION <br />301INSTALLATION <br />A SET LUMINAIRES LEVEL,PLUMB. AND SQUARE WITH CEILING AND WALLS. AND SECURE ACCORDING TO MANUFACTURER'S WRITTEN <br />INSTRUCTIONS AND APPROVED SUBMITTAL MATERIALS. INSTALL (AMPS IN EACH LUMINAIRE WITHOUT INTEGRAL TAMPING. DO NOT <br />SUPPORT LUMINARIES TO THE WORK OF OTIHERTRACES UNLESS OTHERWISE SPECIFIED OR NOTED. ALL LUMINAIRES SHALL BE <br />INDEPENDENTLY SUPPORTED FROM STRUCTURE. PROVIDE ALL NECESSARY SUPPORTS AND HANGERS TO SECURELY FASTEN AND SUPPORT <br />ALLLUMINAIRES TOSTRUCTURE. <br />.2 FIELD QUALITY CONTROL <br />30A INSPECT EACH INSTALLED LUMINAIRE FOR DAMAGE. REPLACE DAMAGED LUMINAIRES AND COMPONENTS. VERIFY NORMAL OPERATION OF <br />EACH LUMINAIRE AFTER INSTALLATION, INTERRUPT THE ELECTRICAL SUPPLY TO VERIFY PROPER OPERATION OF THE EMERGENCY <br />LIGHTING. IF LUMINAIRES ARE MALFUNCTIONING, THEN REPAIR OR REPLACE COMPONENTS AND RETEST UNTIL LUMINAIRE OPERATES <br />PROPERLY. <br />B PROPERLY PROTECT LUMINAIRES FROM CONSTRUCTION DUST AND DEBRIS UNTIL ALL OTHER TRADES HAVE COMPLETED THEIR WORK. <br />CLEAN LUMINAIRES INTERNALLYAND EXTERNALLY AFTER INSTALLATION PER MANUFACTURER'S RECOMMENDATIONS. <br />C. ENSURE ALL WIRING, COORDS. AND ACCESSORIES HAVE BEEN PROPERLY TRIMMED OR TUCKED AWAY SO AS NOT TO BE SEEN THROUGH <br />LENSES, <br />D. REPLACE ANY FAILED TAMPS IN EXISTING LUMINAIRES WITH MATCHING LAMP TYPE AND COLOR. <br />END OF SECTION <br />SECTION Z70528- PATHWAYS FOR COMMUNICATIONS SYSTEM <br />PART PRODUCTS <br />1. METALCENDUITSANDFITTINGS <br />A. PROVIDEPRODUCTSASLISTEDINSECTIONS60533. <br />B. PROVIDE EMPTY CONDUIT SYSTEMS WITH PULL STRING AND BACK BOXES. BACK BOXES SHALL BE 4INCH SQUARE, DEEP, GALVANIZED <br />PRESSED STEEL WITH PLASTER RING. PROVIDE 1 INCH CONDUIT WITH PULL STRING FROM EACH BACK BOX TO a INCHES ABOVE NEAREST <br />ACCESSIBLE CEILING. <br />C. ALL EQUIPMENT, WIRINOCABLE, DEVICES AND COVER PLATES SHALL BE PROVIDED AND INSTALLED BY THE OWNER. <br />PART2 EXECUTION <br />201 INSTALLATION <br />REQUIREMENTS EXCEPT WHERE REQUIREMENTS ON DRAWINGS OR IN <br />A I THISARTICLE ARESTRICTER.COMPLY WITH NFPA70 LIMITATIONS FOR TYPES OF PATHWAYS ALLOWED IN SPECIFIC OCCUPANCIES AND <br />NUMBER OF FLOORS. <br />KEEP PATHWAYS AT LEAST I LLEL RUNS OF FLUES AND STEAM OR HOT-WATER PIPES. INSTALL HOR¢ONTAL <br />B PATHWAY RUNS ABOVE WATER AND STEAM PIPING.A� <br />C. COMPLY WITH REQUIREMENTS IN SECTION 260529'HANGERS AND SUPPORTS FOR ELECTRICAL SYSTEMS' FOR HANGERS AND SUPPORTS. <br />D. INSTALL NO MORE THAN THE EQUIVALENT OF THREE eLLGEGREE BENDS IN MY PATHWAY RUN. SUPPORT WITHIN 12INCHES OF CHANGES IN <br />DIRECTION. UTILIZE LONG RADIUS ELLS FOR ALL OPTICAL -FIBER CABLES. <br />E. CONCEAL CONDUIT No EMT WITHIN FINISHED WALLS, CEILINGS, AND FLOORS UNLESS OTHERWISE INDICATED. INSTALL CONDUITS <br />PARALLEL OR PERPENDICULAR TO BUILDING LINES. <br />F. SUPPORT CONDUIT WITHIN 12 INCHES OF ENCLOSURES TO WHICH ATTACHED, <br />G. IN NT PLASTIC LINE WITH NOT LESS THAN ZM LB TENSILE <br />STRENGTH <br />.LLFAVE ATILEAST 121NCHE8OF SLACK AT EACH END OF PULL STRING. E <br />END OF SECTION <br />�I,blc LAWRENCE <br />GROUP <br />St. Lout <br />319 North 4th Street <br />Suite 1000 <br />St. Louis, Missouri 63102 <br />(314)231-5700 <br />PROJECTTEAM: <br />GENERAL CONTRACTOR: <br />TBD <br />PROFESSIONAL ENGINEER: <br />.IMEG <br />IMEG <br />7600 E Orchard Road, Suite 250-S <br />Greenwood Village, CO 80111 <br />Phone: 303.796.6000 <br />MEG Project No.: 23000048.10 <br />PROFESSIONAL SEAL: <br />IL Do <br />OEM <br />O� <br />'4 51988 <br />AL>� <br />05/24/2023 <br />PROJECTTITLE: <br />U <br />O <br />L.L <br />Z O <br />W <br />m <br />O <br />Z <br />Q <br />Z <br />W <br />J 06 <br />Q <br />U <br />U <br />W <br />0 <br />O <br />U <br />LLI <br />DO <br />O <br />U <br />M <br />M <br />06 <br />m <br />N <br />The Professional Architect's seal affixed W this sheet <br />applies Dory to the materiel end hems snows on this <br />sheet. All tlawings, insir oh, or other documents nt <br />eXnibiMN this seal shell not be considered prepared by <br />this architect, and this amhiWt expressly disclaims any <br />antl all responsibility for such plena, MIa <br />cl w sons not ied ibiting this seal. <br />This dra W antl d-ile on it Be the wle property of Me <br />architect end may be Used for this specific project nnly. <br />It shall not be band, espied or reproduced, in whole or <br />pert, or for any other purpow or prgect wiBlout the <br />written nonwnt of the ..hit-. <br />No Description Date <br />SHEET TITLE: <br />ELECTRICAL <br />SPECIFICATIONS <br />PROJECT NUMBER: <br />SHEET NUMBER: <br />2021932.001 <br />Drown Ry <br />ARD <br />Issue Dale: <br />May 23, 2023 <br />