GENERAL NOTES
<br />1. COORDINATE MECHANICAL WORK WITH THAT OF OTHER TRADES.
<br />REFER TO CONTRACT DOCUMENTS INCLUDING BUT NOT LIMITED
<br />TO ARCHITECTURAL, ELECTRICAL, STRUCTURAL, FIRE PROTECTION,
<br />FIRE ALARM, SECURITY, CIVIL AND LANDSCAPE DRAWINGS AND
<br />SPECIFICATIONS.
<br />2. MAINTAIN CODE REQUIRED AND MANUFACTURERS' MINIMUM
<br />MAINTENANCE CLEARANCES AND AS NOTED ON THE DRAWINGS.
<br />SYSTEMS INSTALLED FOUND TO BE IN CONFLICT WITH THIS
<br />REQUIREMENT WILL BE MOVED AT CONTRACTOR'S EXPENSE TO
<br />ENSURE COMPLIANCE.
<br />3. ACCESS CLEARANCES FOR MAINTENANCE AND REPLACEMENT:
<br />VERIFY PHYSICAL DIMENSIONS OF EQUIPMENT TO ENSURE THAT
<br />ACCESS CLEARANCES CAN BE MET. COORDINATE LOCATIONS OF
<br />MECHANICAL WORK AND WORK OF OTHER TRADES TO PROVIDE
<br />ACCESS CLEARANCES FOR SERVICE AND MAINTENANCE.
<br />COMMISSIONING NOTES
<br />1. THIS PROJECT SHALL BE COMMISSIONED PER THE AHJ,
<br />CONTRACTOR SHALL INCLUDE IN HIS BID THE COST FOR
<br />COMMISSIONING EACH SYSTEM DEMONSTRATING COMPLIANCE WITH
<br />THE CONTRACT DOCUMENTS.
<br />2. PREPARE A PRELIMINARY SCHEDULE AND COMMISSIONING PLAN
<br />INCLUDING FLUSH OUT, CLEANING, EQUIPMENT START-UP, TEST
<br />AND BALANCE FOR VERIFICATION BY ARCHITECT AND ENGINEER.
<br />3. THE BUILDING AND ITS ENERGY SYSTEMS HAVE BEEN DESIGN TO
<br />COMPLY WITH ENERGY CODE ENFORCED BY THE LOCAL AHJ.
<br />CONTRACTOR IS RESPONSIBLE FOR CORRECT INSTALLATION OF
<br />ENERGY CONSERVATION MEASURES.
<br />PLUMBING NOTES
<br />1. INVERT ELEVATIONS SHOWN ARE FOR REFERENCE ONLY.
<br />CONTRACTOR SHALL COORDINATE AND CONFIRM LOCATIONS
<br />PRIOR TO STARTING WORK.
<br />2. SEE TYPICAL PLUMBING DETAILS ON SHEET M5.0.
<br />3. SLOPE WASTE PIPING AT %"PER FOOT UNLESS OTHERWISE
<br />NOTED.
<br />4. SEE ARCHITECTURAL DRAWINGS INCLUDING INTERIOR
<br />ELEVATIONS FOR PLUMBING FIXTURE LOCATIONS AND
<br />REQUIRED MOUNTING HEIGHTS. THIS INCLUDES FLOOR
<br />DRAINS, ROOF DRAINS AND OWNER FURNISHED ITEMS.
<br />5. SEE STRUCTURAL DRAWINGS FOR ADDITIONAL INFORMATION
<br />REGARDING CONSTRUCTION INCLUDING FLOOR SYSTEMS AND
<br />SLAB CONDITIONS.
<br />6. FOR PIPE SIZES TO INDIVIDUAL FIXTURES SEE PLUMBING
<br />FIXTURE SCHEDULE.
<br />7. PROVIDE CLEANOUTS BELOW EACH SINK.
<br />8. PROVIDE ACCESS PANEL AT ISOLATION VALVES WHERE
<br />LOCATED ABOVE HARD LID CEILINGS OR IN WALLS. SHUT OFF
<br />VALVE LOCATIONS ARE SHOWN DIAGRAMMATICALLY AND NEED
<br />TO BE COORDINATED SO THEY ARE INSTALLED IN ACCESSIBLE
<br />LOCATIONS.
<br />9. PROVIDE ACCESS PANEL FOR WATER HAMMER ARRESTORS
<br />AND TRAP PRIMER PANELS.
<br />10. FLOOR DRAINS, FLOOR SINKS AND TRAPS SHALL BE SERVED
<br />FROM THE NEAREST ELECTRONIC TRAP PRIMER.
<br />11. ROUTE MAIN HOT WATER LINES SHOWN DOWN IN WALLS TO
<br />WITHIN 24"OF LAVATORIES OR HAND WASHING SINKS.
<br />12. PIPING INSTALLED ON EXTERIOR WALLS SHALL BE LOCATED
<br />ON THE INTERIOR, "WARM"SIDE OF THE INSULATION SYSTEM.
<br />AVENUE DENTAL
<br />ENERGY CODE NOTES
<br />1. MOTORS SHALL COMPLY WITH MINIMUM FULL LOAD EFFICIENCIES
<br />LISTED IN THE ENERGY CODE ENFORCED BY THE AHJ.
<br />2. INSULATION SHALL COMPLY WITH THICKNESS AND TYPES LISTED
<br />IN THE ENERGY CODE ENFORCED BY THE AHJ UNLESS MORE
<br />STRINGENT REQUIREMENTS ARE SPECIFIED.
<br />3. SUBMIT RECORD DRAWINGS TO THE BUILDING OWNER UPON
<br />PROJECT COMPLETION.
<br />4. SUBMIT OPERATION AND MAINTENANCE MANUALS TO BUILDING
<br />OWNER UPON PROJECT COMPLETION.
<br />5. THIS BUILDING AND ITS ENERGY SYSTEMS HAVE BEEN DESIGNED
<br />TO COMPLY WITH THE ENERGY CODE ENFORCED BY THE LOCAL
<br />AHJ.
<br />PIPING NOTES
<br />1. PROVIDE UNIONS OR FLANGES AT PIPING CONNECTIONS TO
<br />EQUIPMENT, COILS, TRAPS, CONTROL VALVES, AND OTHER
<br />COMPONENTS TO ALLOW DISASSEMBLY FOR MAINTENANCE.
<br />2. PROVIDE AN INSULATED COPPER TRACER WIRE OR OTHER
<br />APPROVED CONDUCTOR ADJACENT TO UNDERGROUND NONMETALLIC
<br />(PLASTIC) PIPING. ACCESS SHALL BE PROVIDED TO THE TRACER
<br />WIRE OR THE TRACER WIRE SHALL TERMINATE ABOVE GROUND AT
<br />EACH END OF THE PIPING. THE TRACER WIRE SHALL NOT BE
<br />LESS THAN NO. 18 AWG AND THE INSULATION TYPE SHALL BE
<br />SUITABLE FOR BURIAL.
<br />3. PROVIDE 12" LONG, 'h" WIDE FLUORESCENT ORANGE TAPE AT
<br />CONCEALED VALVE LOCATIONS.
<br />NON-STRUCTURAL MECHANICAL COMPONENT NOTES
<br />1. ARCHITECTURAL, MECHANICAL, ELECTRICAL, AND
<br />NON-STRUCTURAL COMPONENTS THAT ARE PERMANENTLY
<br />ATTACHED TO STRUCTURES AND THEIR SUPPORTS AND
<br />ATTACHMENTS SHALL BE DESIGNED AND CONSTRUCTED TO
<br />RESIST THE EFFECTS OF EARTHQUAKE MOTIONS.
<br />2. DESIGN AND SPECIFY HANGERS AND SEISMIC BRACING. SHALL
<br />COORDINATE THE SUPPORT SYSTEMS AND DESIGN LOADS FOR
<br />HUNG PIPING AND OTHER MECHANICAL SYSTEMS (INCLUDING
<br />COMBINED MULTIPLE PIPE RUNS) WITH THE GENERAL
<br />CONTRACTOR AND THE STEEL AND WOOD JOIST MANUFACTURERS
<br />IN ADDITION TO OTHER TRADES THAT MAY BE IMPACTED.
<br />STERILIZATION AND FLUSHING OF WATER PIPING
<br />1. AFTER COMPLETION OF WATER PIPING INSTALLATION, BUT
<br />PRIOR TO CONNECTION TO EXISTING MAINS, FLUSH SYSTEM
<br />WITH CLEAN WATER. TAKE SAMPLE OF WATER FROM SYSTEM
<br />TO DETERMINE COMPLIANCE WITH HEALTH DEPARTMENT
<br />STANDARDS. OBTAIN NECESSARY TESTS FROM GOVERNING
<br />HEALTH DEPARTMENT. IF SAMPLE IS NOT IN COMPLIANCE,
<br />PERFORM STERILIZATION.
<br />2. STERILIZE FOR 8 HOUR CONTACT TIME WITH 50 PARTS PER
<br />MILLION CHLORINE CONCENTRATION. OPEN VALVES SEVERAL
<br />TIMES. FOLLOW BY FLUSHING WITH CLEAN WATER UNTIL
<br />RESIDUAL CHLORINE IS LESS THAN 0.2 PARTS PER MILLION.
<br />3. AFTER FLUSHING AND STERILIZATION ARE COMPLETE,
<br />CONDUCT TESTS TO DETERMINE COMPLIANCE WITH HEALTH
<br />DEPARTMENT STANDARDS FOR STERILIZATION RESULTS. IF
<br />PIPE SYSTEM IS FOUND TO BE CONTAMINATED, CORRECT
<br />DEFECTS AND PERFORM ADDITIONAL FLUSHING AND
<br />STERILIZATION UNTIL SATISFACTORY RESULTS ARE OBTAINED.
<br />4. SUBMIT WRITTEN CERTIFICATION OF FLUSHING AND
<br />STERILIZATION BY LOCAL AHJ.
<br />ABBREVIATIONS
<br />0 DIAMETER, PHASE
<br />A
<br />AIR, AMPS
<br />AAV
<br />AUTOMATIC AIR VENT
<br />ABV
<br />ABOVE
<br />AC
<br />AIR CONDITIONER
<br />ACU
<br />AIR CONDITIONING UNIT
<br />AD
<br />ACCESS DOOR
<br />ADA
<br />AMERICANS WITH DISABILITIES
<br />ACT
<br />AT
<br />AIRFOIL
<br />AFT
<br />ABOVE FINISHED FLOOR
<br />AFUE
<br />ANNUAL FUEL UTILIZATION
<br />EFFICIENCY
<br />AG
<br />ABOVE GROUND
<br />AHJ
<br />AUTHORITY HAVING
<br />JURISDICTION
<br />AHU
<br />AIR HANDLING UNIT
<br />AL
<br />ACOUSTIC LINED (DUCT)
<br />AP
<br />ACCESS PANEL
<br />ARCH
<br />ARCHITECT
<br />ASHRAE
<br />AMERICAN SOCIETY OF
<br />HEATING,
<br />REFRIGERATION AND
<br />AIR-CONDITIONING
<br />ENGINEERS, INC.
<br />ATM
<br />ATMOSPHERE
<br />B
<br />BOILER
<br />BDD
<br />BACK DRAFT DAMPER
<br />BE
<br />BELOW FLOOR
<br />BHP
<br />BRAKE HORSE POWER
<br />BOD
<br />BOTTOM OF DUCT
<br />BOP
<br />BOTTOM OF PIPE
<br />BOT
<br />BOTTOM
<br />BTUH
<br />BRITISH THERMAL UNIT PER
<br />HOUR
<br />BV
<br />BALL VALVE
<br />C
<br />CONDENSATE PIPING
<br />CAP
<br />CAPACITY
<br />CC
<br />COOLING COIL
<br />CD
<br />CEILING DIFFUSER,
<br />CONDENSATE DRAIN
<br />CFM
<br />CUBIC FEET PER MINUTE
<br />CG
<br />CEILING GRILLE
<br />CH
<br />CABINET HEATER
<br />CKV
<br />CHECK VALVE
<br />CLG
<br />CEILING, COOLING
<br />CO
<br />CLEANOUT
<br />CO2
<br />CO2 SENSOR
<br />COND
<br />CONDENSER, CONDENSATE
<br />CONN
<br />CONNECTOR
<br />CONT
<br />CONTINUE, CONTROL
<br />COP
<br />COEFFICIENT OF
<br />PERFORMANCE
<br />C.TK
<br />COMPRESSION TANK
<br />CU
<br />CONDENSING UNIT, CUBIC
<br />CV
<br />CONSTANT VOLUME
<br />CW
<br />COLD WATER PIPING
<br />D
<br />DRAIN
<br />DB
<br />DRY BULB (TEMPERATURE)
<br />dB
<br />DECIBEL
<br />DCVA
<br />DOUBLE CHECK VALVE
<br />ASSEMBLY
<br />DEG
<br />DEGREE
<br />DEMO
<br />DEMOLITION
<br />DFU
<br />DRAINAGE FIXTURE UNIT
<br />DIA
<br />DIAMETER
<br />DIM
<br />DIMENSION
<br />DN
<br />DOWN
<br />DWGS
<br />DRAWINGS
<br />(E)
<br />EXISTING
<br />EA
<br />EXHAUST AIR
<br />EAT
<br />ENTERING AIR TEMPERATURE
<br />EER
<br />ENERGY EFFICIENCY RATIO
<br />EF
<br />EXHAUST FAN
<br />EFF
<br />EFFICIENCY
<br />EG
<br />EXHAUST GRILLE
<br />EL
<br />ELEVATION
<br />ELEC
<br />ELECTRIC
<br />EQUIV
<br />EQUIVALENT
<br />ESP
<br />EXTERNAL STATIC PRESSURE
<br />ET
<br />EXPANSION TANK
<br />EVAP
<br />EVAPORATOR, EVAPORATIVE
<br />EWC
<br />ELECTRIC WATER COOLER
<br />EWT
<br />ENTERING WATER TEMP
<br />EXH
<br />EXHAUST
<br />GAGE
<br />EXT
<br />EXTERIOR, EXTERNAL
<br />QTY
<br />QUANTITY
<br />F
<br />FAHRENHEIT, FIRE MAIN
<br />PIPING
<br />R
<br />RELOCATED
<br />FCO
<br />FLOOR CLEANOUT
<br />RA
<br />RETURN AIR, RELIEF AIR
<br />FCU
<br />FAN COIL UNIT
<br />RD
<br />ROOF DRAIN
<br />FD
<br />FIRE DAMPER, FLOOR DRAIN,
<br />REG
<br />REGISTER
<br />DRY SPRINKLER ROUTING
<br />REF
<br />REFERENCE,
<br />FDC
<br />FIRE DEPARTMENT
<br />RETURN/EXHAUST FAN
<br />CONNECTION
<br />RG
<br />RETURN GRILLE
<br />FLA
<br />FULL LOAD AMPS
<br />RI&C
<br />ROUGH IN AND CONNECT
<br />FLEX
<br />FLEXIBLE
<br />RL
<br />RAIN LEADER
<br />FLR
<br />FLOOR
<br />RLA
<br />RATED LOAD AMPS
<br />FPM
<br />FEET PER MINUTE
<br />RPBP
<br />REDUCED PRESSURE
<br />FPS
<br />FEET PER SECOND
<br />BACKFLOW PREVENTER
<br />FS
<br />FLOOR SINK
<br />RPM
<br />REVOLUTIONS PER MINUTE
<br />F/S
<br />FIRE/SMOKE DAMPER
<br />RTU
<br />ROOFTOP UNIT
<br />FT
<br />FEET, FIN TUBE
<br />TV
<br />FACE VELOCITY
<br />S
<br />SENSOR
<br />FW
<br />FILTERED WATER PIPING
<br />SA
<br />SUPPLY AIR
<br />SCFM
<br />STANDARD CUBIC FEET PER
<br />G
<br />GAS
<br />MINUTE
<br />GA
<br />GAGE
<br />SCH
<br />SCHEDULE
<br />GAL
<br />GALLONS
<br />SENS
<br />SENSIBLE
<br />GALV
<br />GALVANIZED
<br />SF
<br />SUPPLY FAN, SQUARE FOOT
<br />GPF
<br />GALLONS PER FLUSH
<br />SG
<br />SUPPLY GRILLE, SIGHT
<br />GPH
<br />GALLONS PER HOUR
<br />GLASS WITH MOISTURE
<br />GPM
<br />GALLONS PER MINUTE
<br />INDICATOR
<br />GRID
<br />GRILLES, REGISTERS, AND
<br />SIM
<br />SIMILAR
<br />DIFFUSERS
<br />SL
<br />REFRIGERANT SUCTION LINE
<br />GV
<br />GATE VALVE, GLOBE VALVE
<br />OR SOUND LINED (CLEAR
<br />INSIDE
<br />IAQ
<br />INDOOR AIR QUALITY
<br />DIMENSION)
<br />IE
<br />INVERT ELEVATION
<br />SMACNA SHEET METAL AND AIR
<br />C.
<br />INCH
<br />CONDITIONING CONTRACTORS'
<br />IN.WG
<br />INCHES WATER COLUMN
<br />NATIONAL ASSOCIATION, INC.
<br />SOV
<br />SHUTOFF VALVE
<br />kW
<br />KILOWATT
<br />SP
<br />STATIC PRESSURE
<br />SS
<br />STAINLESS STEEL, SANITARY
<br />L
<br />LENGTH
<br />SEWER
<br />LAT
<br />LEAVING AIR TEMPERATURE
<br />LBS
<br />POUND
<br />T
<br />THERMOSTAT
<br />LD
<br />LINEAR DIFFUSER
<br />TCV
<br />TEMPERATURE CONTROL
<br />LR
<br />LINEAR RETURN
<br />VALVE
<br />LVR
<br />LOUVER
<br />TO
<br />TRENCH DRAIN,
<br />LWR
<br />LOW WALL RETURN
<br />TEMPERATURE
<br />DIFFERENCE
<br />MAT
<br />MIXED AIR TEMPERATURE
<br />TEMP
<br />TEMPERATURE
<br />MAV
<br />MANUAL AIR VENT
<br />TG
<br />TRANSFER GRILLE
<br />MAX
<br />MAXIMUM
<br />TOP
<br />TOP OF DUCT
<br />MBH
<br />THOUSAND BTU PER HOUR
<br />TOP
<br />TOP OF PIPE
<br />MC
<br />MECHANICAL CONTRACTOR
<br />TOE
<br />TOP OF STEEL
<br />MCA
<br />MINIMUM CIRCUIT AMPACITY
<br />T
<br />TOP OF FOOTING
<br />MECH
<br />MECHANICAL
<br />TRAP
<br />P
<br />STEAM TRAP
<br />MERV
<br />MINIMUM EFFICIENCY
<br />TSP
<br />TOTAL STATIC PRESSURE
<br />REPORTING VALUE
<br />TU
<br />TERMINAL UNIT
<br />MIN
<br />MINIMUM
<br />TW
<br />TEMPERED WATER
<br />MOCP
<br />MAXIMUM OVERCURRENT
<br />P
<br />TYPICAL
<br />PROTECTION
<br />MOD
<br />MOTOR OPERATED DAMPER
<br />UG
<br />UNDERGROUND
<br />UH
<br />UNIT HEATER
<br />N
<br />NEW
<br />UNO
<br />UNLESS NOTED OTHERWISE
<br />NA
<br />NOT APPLICABLE
<br />INC
<br />NORMALLY CLOSED, NOISE
<br />V
<br />VENT PIPING, VOLT
<br />CRITERIA
<br />VA
<br />VALVE
<br />NIC
<br />NOT IN CONTRACT
<br />VAV
<br />VARIABLE AIR VOLUME
<br />NO
<br />NORMALLY OPEN, NITROUS
<br />VCD
<br />VOLUME CONTROL DEVICE
<br />OXIDE
<br />VD
<br />VOLUME DAMPER
<br />IN.
<br />NUMBER
<br />VEL
<br />VELOCITY
<br />NTS
<br />NOT TO SCALE
<br />VENT
<br />VENTILATION, VENTILATOR
<br />VFD
<br />VARIABLE FREQUENCY DRIVE
<br />CA
<br />OUTDOOR AIR
<br />VOLT
<br />VOLTAGE
<br />OC
<br />ON CENTER
<br />VTR
<br />VENT THRU ROOF
<br />OD
<br />OUTSIDE DIMENSION OR
<br />DIAMETER
<br />W
<br />WASTE, WATT, WIDE, WATER
<br />ORD
<br />OVERFLOW ROOF DRAIN
<br />W/
<br />WITH
<br />ORL
<br />OVERFLOW RAIN LEADER
<br />WB
<br />WET BULB (TEMPERATURE)
<br />OSA
<br />OUTDOOR SUPPLY AIR
<br />WC
<br />WATER CLOSET, WATER
<br />P
<br />PUMP, PRESSURE, PLUMBING
<br />COLUMN
<br />FIXTURE
<br />WCO
<br />WALL CLEANOUT
<br />PD
<br />PRESSURE DROP, PUMPED
<br />WG
<br />WATER GAGE
<br />DRAIN
<br />WH
<br />WATER HEATER, WALL
<br />PH
<br />PHASE
<br />HYDRANT
<br />PIV
<br />POST INDICATOR VALVE
<br />WHA
<br />WATER HAMMER ARRESTOR
<br />POC
<br />POINT OF CONNECTION
<br />WM
<br />WATER METER
<br />PRV
<br />PRESSURE REDUCING VALVE
<br />WSEC
<br />WASHINGTON STATE ENERGY
<br />PSIG
<br />POUNDS PER SQUARE INCH
<br />CODE
<br />WSFU
<br />WATER SUPPLY FIXTURE UNIT
<br />WT
<br />WEIGHT
<br />VICINITY MAP
<br />-19
<br />®
<br />m
<br />Qc.,exe.pw
<br />0
<br />e
<br />w
<br />CODES
<br />2018 UNIFORM PLUMBING CODE WITH LOCAL AMENDMENTS
<br />2018 INTERNATIONAL MECHANICAL CODE WITH LOCAL AMENDMENTS
<br />2018 WASHINGTON STATE ENERGY CODE
<br />2018 INTERNATIONAL FUEL GAS CODE
<br />2018 INTERNATIONAL BUILDING CODE
<br />Sheet List Table
<br />Sheet Number
<br />Sheet Title
<br />P0.1
<br />ABBREVIATION & NOTES
<br />P0.2
<br />LEGEND
<br />P0.3
<br />SCHEDULES
<br />P1.0
<br />FLOOR PLAN PLUMBING
<br />P2.0
<br />FLOOR MEDICAL GASES
<br />P3.0
<br />WATER & WASTE RISER
<br />P4.0
<br />PLUMBING DETAILS
<br />P4.1
<br />PLUMBING DETAILS
<br />Z
<br />Q
<br />Ul
<br />w
<br />0
<br />•
<br />Q2
<br />D
<br />w
<br />31620 23rd Ave S
<br />Federal Way, WA 98003
<br />Linda@Burman.Design
<br />00
<br />CD
<br />N
<br />00
<br />M
<br />>Q
<br />__J
<br />L
<br />w
<br />z LU
<br />W >
<br />c) LU
<br />W 00
<br />z >
<br />W Q
<br /><
<br />t`
<br />N
<br />0
<br />JOB NO: ----
<br />ISSUE DATE
<br />�9P S BUR,F,
<br />Of WAS I
<br />0
<br />z
<br />p 42025 4
<br />SSrONAL bx
<br />ZS1
<br />ABBREVIATION &
<br />NOTES
<br />P0.1