GENERAL NOTES <br />1. COORDINATE MECHANICAL WORK WITH THAT OF OTHER TRADES. <br />REFER TO CONTRACT DOCUMENTS INCLUDING BUT NOT LIMITED <br />TO ARCHITECTURAL, ELECTRICAL, STRUCTURAL, FIRE PROTECTION, <br />FIRE ALARM, SECURITY, CIVIL AND LANDSCAPE DRAWINGS AND <br />SPECIFICATIONS. <br />2. MAINTAIN CODE REQUIRED AND MANUFACTURERS' MINIMUM <br />MAINTENANCE CLEARANCES AND AS NOTED ON THE DRAWINGS. <br />SYSTEMS INSTALLED FOUND TO BE IN CONFLICT WITH THIS <br />REQUIREMENT WILL BE MOVED AT CONTRACTOR'S EXPENSE TO <br />ENSURE COMPLIANCE. <br />3. ACCESS CLEARANCES FOR MAINTENANCE AND REPLACEMENT: <br />VERIFY PHYSICAL DIMENSIONS OF EQUIPMENT TO ENSURE THAT <br />ACCESS CLEARANCES CAN BE MET. COORDINATE LOCATIONS OF <br />MECHANICAL WORK AND WORK OF OTHER TRADES TO PROVIDE <br />ACCESS CLEARANCES FOR SERVICE AND MAINTENANCE. <br />COMMISSIONING NOTES <br />1. THIS PROJECT SHALL BE COMMISSIONED PER THE AHJ, <br />CONTRACTOR SHALL INCLUDE IN HIS BID THE COST FOR <br />COMMISSIONING EACH SYSTEM DEMONSTRATING COMPLIANCE WITH <br />THE CONTRACT DOCUMENTS. <br />2. PREPARE A PRELIMINARY SCHEDULE AND COMMISSIONING PLAN <br />INCLUDING FLUSH OUT, CLEANING, EQUIPMENT START-UP, TEST <br />AND BALANCE FOR VERIFICATION BY ARCHITECT AND ENGINEER. <br />3. THE BUILDING AND ITS ENERGY SYSTEMS HAVE BEEN DESIGN TO <br />COMPLY WITH ENERGY CODE ENFORCED BY THE LOCAL AHJ. <br />CONTRACTOR IS RESPONSIBLE FOR CORRECT INSTALLATION OF <br />ENERGY CONSERVATION MEASURES. <br />PLUMBING NOTES <br />1. INVERT ELEVATIONS SHOWN ARE FOR REFERENCE ONLY. <br />CONTRACTOR SHALL COORDINATE AND CONFIRM LOCATIONS <br />PRIOR TO STARTING WORK. <br />2. SEE TYPICAL PLUMBING DETAILS ON SHEET M5.0. <br />3. SLOPE WASTE PIPING AT %"PER FOOT UNLESS OTHERWISE <br />NOTED. <br />4. SEE ARCHITECTURAL DRAWINGS INCLUDING INTERIOR <br />ELEVATIONS FOR PLUMBING FIXTURE LOCATIONS AND <br />REQUIRED MOUNTING HEIGHTS. THIS INCLUDES FLOOR <br />DRAINS, ROOF DRAINS AND OWNER FURNISHED ITEMS. <br />5. SEE STRUCTURAL DRAWINGS FOR ADDITIONAL INFORMATION <br />REGARDING CONSTRUCTION INCLUDING FLOOR SYSTEMS AND <br />SLAB CONDITIONS. <br />6. FOR PIPE SIZES TO INDIVIDUAL FIXTURES SEE PLUMBING <br />FIXTURE SCHEDULE. <br />7. PROVIDE CLEANOUTS BELOW EACH SINK. <br />8. PROVIDE ACCESS PANEL AT ISOLATION VALVES WHERE <br />LOCATED ABOVE HARD LID CEILINGS OR IN WALLS. SHUT OFF <br />VALVE LOCATIONS ARE SHOWN DIAGRAMMATICALLY AND NEED <br />TO BE COORDINATED SO THEY ARE INSTALLED IN ACCESSIBLE <br />LOCATIONS. <br />9. PROVIDE ACCESS PANEL FOR WATER HAMMER ARRESTORS <br />AND TRAP PRIMER PANELS. <br />10. FLOOR DRAINS, FLOOR SINKS AND TRAPS SHALL BE SERVED <br />FROM THE NEAREST ELECTRONIC TRAP PRIMER. <br />11. ROUTE MAIN HOT WATER LINES SHOWN DOWN IN WALLS TO <br />WITHIN 24"OF LAVATORIES OR HAND WASHING SINKS. <br />12. PIPING INSTALLED ON EXTERIOR WALLS SHALL BE LOCATED <br />ON THE INTERIOR, "WARM"SIDE OF THE INSULATION SYSTEM. <br />AVENUE DENTAL <br />ENERGY CODE NOTES <br />1. MOTORS SHALL COMPLY WITH MINIMUM FULL LOAD EFFICIENCIES <br />LISTED IN THE ENERGY CODE ENFORCED BY THE AHJ. <br />2. INSULATION SHALL COMPLY WITH THICKNESS AND TYPES LISTED <br />IN THE ENERGY CODE ENFORCED BY THE AHJ UNLESS MORE <br />STRINGENT REQUIREMENTS ARE SPECIFIED. <br />3. SUBMIT RECORD DRAWINGS TO THE BUILDING OWNER UPON <br />PROJECT COMPLETION. <br />4. SUBMIT OPERATION AND MAINTENANCE MANUALS TO BUILDING <br />OWNER UPON PROJECT COMPLETION. <br />5. THIS BUILDING AND ITS ENERGY SYSTEMS HAVE BEEN DESIGNED <br />TO COMPLY WITH THE ENERGY CODE ENFORCED BY THE LOCAL <br />AHJ. <br />PIPING NOTES <br />1. PROVIDE UNIONS OR FLANGES AT PIPING CONNECTIONS TO <br />EQUIPMENT, COILS, TRAPS, CONTROL VALVES, AND OTHER <br />COMPONENTS TO ALLOW DISASSEMBLY FOR MAINTENANCE. <br />2. PROVIDE AN INSULATED COPPER TRACER WIRE OR OTHER <br />APPROVED CONDUCTOR ADJACENT TO UNDERGROUND NONMETALLIC <br />(PLASTIC) PIPING. ACCESS SHALL BE PROVIDED TO THE TRACER <br />WIRE OR THE TRACER WIRE SHALL TERMINATE ABOVE GROUND AT <br />EACH END OF THE PIPING. THE TRACER WIRE SHALL NOT BE <br />LESS THAN NO. 18 AWG AND THE INSULATION TYPE SHALL BE <br />SUITABLE FOR BURIAL. <br />3. PROVIDE 12" LONG, 'h" WIDE FLUORESCENT ORANGE TAPE AT <br />CONCEALED VALVE LOCATIONS. <br />NON-STRUCTURAL MECHANICAL COMPONENT NOTES <br />1. ARCHITECTURAL, MECHANICAL, ELECTRICAL, AND <br />NON-STRUCTURAL COMPONENTS THAT ARE PERMANENTLY <br />ATTACHED TO STRUCTURES AND THEIR SUPPORTS AND <br />ATTACHMENTS SHALL BE DESIGNED AND CONSTRUCTED TO <br />RESIST THE EFFECTS OF EARTHQUAKE MOTIONS. <br />2. DESIGN AND SPECIFY HANGERS AND SEISMIC BRACING. SHALL <br />COORDINATE THE SUPPORT SYSTEMS AND DESIGN LOADS FOR <br />HUNG PIPING AND OTHER MECHANICAL SYSTEMS (INCLUDING <br />COMBINED MULTIPLE PIPE RUNS) WITH THE GENERAL <br />CONTRACTOR AND THE STEEL AND WOOD JOIST MANUFACTURERS <br />IN ADDITION TO OTHER TRADES THAT MAY BE IMPACTED. <br />STERILIZATION AND FLUSHING OF WATER PIPING <br />1. AFTER COMPLETION OF WATER PIPING INSTALLATION, BUT <br />PRIOR TO CONNECTION TO EXISTING MAINS, FLUSH SYSTEM <br />WITH CLEAN WATER. TAKE SAMPLE OF WATER FROM SYSTEM <br />TO DETERMINE COMPLIANCE WITH HEALTH DEPARTMENT <br />STANDARDS. OBTAIN NECESSARY TESTS FROM GOVERNING <br />HEALTH DEPARTMENT. IF SAMPLE IS NOT IN COMPLIANCE, <br />PERFORM STERILIZATION. <br />2. STERILIZE FOR 8 HOUR CONTACT TIME WITH 50 PARTS PER <br />MILLION CHLORINE CONCENTRATION. OPEN VALVES SEVERAL <br />TIMES. FOLLOW BY FLUSHING WITH CLEAN WATER UNTIL <br />RESIDUAL CHLORINE IS LESS THAN 0.2 PARTS PER MILLION. <br />3. AFTER FLUSHING AND STERILIZATION ARE COMPLETE, <br />CONDUCT TESTS TO DETERMINE COMPLIANCE WITH HEALTH <br />DEPARTMENT STANDARDS FOR STERILIZATION RESULTS. IF <br />PIPE SYSTEM IS FOUND TO BE CONTAMINATED, CORRECT <br />DEFECTS AND PERFORM ADDITIONAL FLUSHING AND <br />STERILIZATION UNTIL SATISFACTORY RESULTS ARE OBTAINED. <br />4. SUBMIT WRITTEN CERTIFICATION OF FLUSHING AND <br />STERILIZATION BY LOCAL AHJ. <br />ABBREVIATIONS <br />0 DIAMETER, PHASE <br />A <br />AIR, AMPS <br />AAV <br />AUTOMATIC AIR VENT <br />ABV <br />ABOVE <br />AC <br />AIR CONDITIONER <br />ACU <br />AIR CONDITIONING UNIT <br />AD <br />ACCESS DOOR <br />ADA <br />AMERICANS WITH DISABILITIES <br />ACT <br />AT <br />AIRFOIL <br />AFT <br />ABOVE FINISHED FLOOR <br />AFUE <br />ANNUAL FUEL UTILIZATION <br />EFFICIENCY <br />AG <br />ABOVE GROUND <br />AHJ <br />AUTHORITY HAVING <br />JURISDICTION <br />AHU <br />AIR HANDLING UNIT <br />AL <br />ACOUSTIC LINED (DUCT) <br />AP <br />ACCESS PANEL <br />ARCH <br />ARCHITECT <br />ASHRAE <br />AMERICAN SOCIETY OF <br />HEATING, <br />REFRIGERATION AND <br />AIR-CONDITIONING <br />ENGINEERS, INC. <br />ATM <br />ATMOSPHERE <br />B <br />BOILER <br />BDD <br />BACK DRAFT DAMPER <br />BE <br />BELOW FLOOR <br />BHP <br />BRAKE HORSE POWER <br />BOD <br />BOTTOM OF DUCT <br />BOP <br />BOTTOM OF PIPE <br />BOT <br />BOTTOM <br />BTUH <br />BRITISH THERMAL UNIT PER <br />HOUR <br />BV <br />BALL VALVE <br />C <br />CONDENSATE PIPING <br />CAP <br />CAPACITY <br />CC <br />COOLING COIL <br />CD <br />CEILING DIFFUSER, <br />CONDENSATE DRAIN <br />CFM <br />CUBIC FEET PER MINUTE <br />CG <br />CEILING GRILLE <br />CH <br />CABINET HEATER <br />CKV <br />CHECK VALVE <br />CLG <br />CEILING, COOLING <br />CO <br />CLEANOUT <br />CO2 <br />CO2 SENSOR <br />COND <br />CONDENSER, CONDENSATE <br />CONN <br />CONNECTOR <br />CONT <br />CONTINUE, CONTROL <br />COP <br />COEFFICIENT OF <br />PERFORMANCE <br />C.TK <br />COMPRESSION TANK <br />CU <br />CONDENSING UNIT, CUBIC <br />CV <br />CONSTANT VOLUME <br />CW <br />COLD WATER PIPING <br />D <br />DRAIN <br />DB <br />DRY BULB (TEMPERATURE) <br />dB <br />DECIBEL <br />DCVA <br />DOUBLE CHECK VALVE <br />ASSEMBLY <br />DEG <br />DEGREE <br />DEMO <br />DEMOLITION <br />DFU <br />DRAINAGE FIXTURE UNIT <br />DIA <br />DIAMETER <br />DIM <br />DIMENSION <br />DN <br />DOWN <br />DWGS <br />DRAWINGS <br />(E) <br />EXISTING <br />EA <br />EXHAUST AIR <br />EAT <br />ENTERING AIR TEMPERATURE <br />EER <br />ENERGY EFFICIENCY RATIO <br />EF <br />EXHAUST FAN <br />EFF <br />EFFICIENCY <br />EG <br />EXHAUST GRILLE <br />EL <br />ELEVATION <br />ELEC <br />ELECTRIC <br />EQUIV <br />EQUIVALENT <br />ESP <br />EXTERNAL STATIC PRESSURE <br />ET <br />EXPANSION TANK <br />EVAP <br />EVAPORATOR, EVAPORATIVE <br />EWC <br />ELECTRIC WATER COOLER <br />EWT <br />ENTERING WATER TEMP <br />EXH <br />EXHAUST <br />GAGE <br />EXT <br />EXTERIOR, EXTERNAL <br />QTY <br />QUANTITY <br />F <br />FAHRENHEIT, FIRE MAIN <br />PIPING <br />R <br />RELOCATED <br />FCO <br />FLOOR CLEANOUT <br />RA <br />RETURN AIR, RELIEF AIR <br />FCU <br />FAN COIL UNIT <br />RD <br />ROOF DRAIN <br />FD <br />FIRE DAMPER, FLOOR DRAIN, <br />REG <br />REGISTER <br />DRY SPRINKLER ROUTING <br />REF <br />REFERENCE, <br />FDC <br />FIRE DEPARTMENT <br />RETURN/EXHAUST FAN <br />CONNECTION <br />RG <br />RETURN GRILLE <br />FLA <br />FULL LOAD AMPS <br />RI&C <br />ROUGH IN AND CONNECT <br />FLEX <br />FLEXIBLE <br />RL <br />RAIN LEADER <br />FLR <br />FLOOR <br />RLA <br />RATED LOAD AMPS <br />FPM <br />FEET PER MINUTE <br />RPBP <br />REDUCED PRESSURE <br />FPS <br />FEET PER SECOND <br />BACKFLOW PREVENTER <br />FS <br />FLOOR SINK <br />RPM <br />REVOLUTIONS PER MINUTE <br />F/S <br />FIRE/SMOKE DAMPER <br />RTU <br />ROOFTOP UNIT <br />FT <br />FEET, FIN TUBE <br />TV <br />FACE VELOCITY <br />S <br />SENSOR <br />FW <br />FILTERED WATER PIPING <br />SA <br />SUPPLY AIR <br />SCFM <br />STANDARD CUBIC FEET PER <br />G <br />GAS <br />MINUTE <br />GA <br />GAGE <br />SCH <br />SCHEDULE <br />GAL <br />GALLONS <br />SENS <br />SENSIBLE <br />GALV <br />GALVANIZED <br />SF <br />SUPPLY FAN, SQUARE FOOT <br />GPF <br />GALLONS PER FLUSH <br />SG <br />SUPPLY GRILLE, SIGHT <br />GPH <br />GALLONS PER HOUR <br />GLASS WITH MOISTURE <br />GPM <br />GALLONS PER MINUTE <br />INDICATOR <br />GRID <br />GRILLES, REGISTERS, AND <br />SIM <br />SIMILAR <br />DIFFUSERS <br />SL <br />REFRIGERANT SUCTION LINE <br />GV <br />GATE VALVE, GLOBE VALVE <br />OR SOUND LINED (CLEAR <br />INSIDE <br />IAQ <br />INDOOR AIR QUALITY <br />DIMENSION) <br />IE <br />INVERT ELEVATION <br />SMACNA SHEET METAL AND AIR <br />C. <br />INCH <br />CONDITIONING CONTRACTORS' <br />IN.WG <br />INCHES WATER COLUMN <br />NATIONAL ASSOCIATION, INC. <br />SOV <br />SHUTOFF VALVE <br />kW <br />KILOWATT <br />SP <br />STATIC PRESSURE <br />SS <br />STAINLESS STEEL, SANITARY <br />L <br />LENGTH <br />SEWER <br />LAT <br />LEAVING AIR TEMPERATURE <br />LBS <br />POUND <br />T <br />THERMOSTAT <br />LD <br />LINEAR DIFFUSER <br />TCV <br />TEMPERATURE CONTROL <br />LR <br />LINEAR RETURN <br />VALVE <br />LVR <br />LOUVER <br />TO <br />TRENCH DRAIN, <br />LWR <br />LOW WALL RETURN <br />TEMPERATURE <br />DIFFERENCE <br />MAT <br />MIXED AIR TEMPERATURE <br />TEMP <br />TEMPERATURE <br />MAV <br />MANUAL AIR VENT <br />TG <br />TRANSFER GRILLE <br />MAX <br />MAXIMUM <br />TOP <br />TOP OF DUCT <br />MBH <br />THOUSAND BTU PER HOUR <br />TOP <br />TOP OF PIPE <br />MC <br />MECHANICAL CONTRACTOR <br />TOE <br />TOP OF STEEL <br />MCA <br />MINIMUM CIRCUIT AMPACITY <br />T <br />TOP OF FOOTING <br />MECH <br />MECHANICAL <br />TRAP <br />P <br />STEAM TRAP <br />MERV <br />MINIMUM EFFICIENCY <br />TSP <br />TOTAL STATIC PRESSURE <br />REPORTING VALUE <br />TU <br />TERMINAL UNIT <br />MIN <br />MINIMUM <br />TW <br />TEMPERED WATER <br />MOCP <br />MAXIMUM OVERCURRENT <br />P <br />TYPICAL <br />PROTECTION <br />MOD <br />MOTOR OPERATED DAMPER <br />UG <br />UNDERGROUND <br />UH <br />UNIT HEATER <br />N <br />NEW <br />UNO <br />UNLESS NOTED OTHERWISE <br />NA <br />NOT APPLICABLE <br />INC <br />NORMALLY CLOSED, NOISE <br />V <br />VENT PIPING, VOLT <br />CRITERIA <br />VA <br />VALVE <br />NIC <br />NOT IN CONTRACT <br />VAV <br />VARIABLE AIR VOLUME <br />NO <br />NORMALLY OPEN, NITROUS <br />VCD <br />VOLUME CONTROL DEVICE <br />OXIDE <br />VD <br />VOLUME DAMPER <br />IN. <br />NUMBER <br />VEL <br />VELOCITY <br />NTS <br />NOT TO SCALE <br />VENT <br />VENTILATION, VENTILATOR <br />VFD <br />VARIABLE FREQUENCY DRIVE <br />CA <br />OUTDOOR AIR <br />VOLT <br />VOLTAGE <br />OC <br />ON CENTER <br />VTR <br />VENT THRU ROOF <br />OD <br />OUTSIDE DIMENSION OR <br />DIAMETER <br />W <br />WASTE, WATT, WIDE, WATER <br />ORD <br />OVERFLOW ROOF DRAIN <br />W/ <br />WITH <br />ORL <br />OVERFLOW RAIN LEADER <br />WB <br />WET BULB (TEMPERATURE) <br />OSA <br />OUTDOOR SUPPLY AIR <br />WC <br />WATER CLOSET, WATER <br />P <br />PUMP, PRESSURE, PLUMBING <br />COLUMN <br />FIXTURE <br />WCO <br />WALL CLEANOUT <br />PD <br />PRESSURE DROP, PUMPED <br />WG <br />WATER GAGE <br />DRAIN <br />WH <br />WATER HEATER, WALL <br />PH <br />PHASE <br />HYDRANT <br />PIV <br />POST INDICATOR VALVE <br />WHA <br />WATER HAMMER ARRESTOR <br />POC <br />POINT OF CONNECTION <br />WM <br />WATER METER <br />PRV <br />PRESSURE REDUCING VALVE <br />WSEC <br />WASHINGTON STATE ENERGY <br />PSIG <br />POUNDS PER SQUARE INCH <br />CODE <br />WSFU <br />WATER SUPPLY FIXTURE UNIT <br />WT <br />WEIGHT <br />VICINITY MAP <br />-19 <br />® <br />m <br />Qc.,exe.pw <br />0 <br />e <br />w <br />CODES <br />2018 UNIFORM PLUMBING CODE WITH LOCAL AMENDMENTS <br />2018 INTERNATIONAL MECHANICAL CODE WITH LOCAL AMENDMENTS <br />2018 WASHINGTON STATE ENERGY CODE <br />2018 INTERNATIONAL FUEL GAS CODE <br />2018 INTERNATIONAL BUILDING CODE <br />Sheet List Table <br />Sheet Number <br />Sheet Title <br />P0.1 <br />ABBREVIATION & NOTES <br />P0.2 <br />LEGEND <br />P0.3 <br />SCHEDULES <br />P1.0 <br />FLOOR PLAN PLUMBING <br />P2.0 <br />FLOOR MEDICAL GASES <br />P3.0 <br />WATER & WASTE RISER <br />P4.0 <br />PLUMBING DETAILS <br />P4.1 <br />PLUMBING DETAILS <br />Z <br />Q <br />Ul <br />w <br />0 <br />• <br />Q2 <br />D <br />w <br />31620 23rd Ave S <br />Federal Way, WA 98003 <br />Linda@Burman.Design <br />00 <br />CD <br />N <br />00 <br />M <br />>Q <br />__J <br />L <br />w <br />z LU <br />W > <br />c) LU <br />W 00 <br />z > <br />W Q <br />< <br />t` <br />N <br />0 <br />JOB NO: ---- <br />ISSUE DATE <br />�9P S BUR,F, <br />Of WAS I <br />0 <br />z <br />p 42025 4 <br />SSrONAL bx <br />ZS1 <br />ABBREVIATION & <br />NOTES <br />P0.1 <br />