Laserfiche WebLink
, <br /> FARRINGTON <br /> „.=t,,- AIR QUALITY SERVICES <br /> Air Handling Unit <br /> PROJECT: Ballot Facility TI DATE: 6/17/2024 <br /> LOCATION: Everett,WA CONTACT: JT Parker <br /> PROJECT#: 23-1064 <br /> SYSTEM/UNIT: AHU-01/B-11 Tested By: Eric Liles <br /> Date: 6/17/2024 <br /> Unit Data Term Box Test Data <br /> Manufacturer Trane Design Max Airflow 1000 CFM <br /> Model Number VDDF Actual Max Airflow 975 CFM <br /> Serial Number R23K01742 Max Diff.SP 0.42 in.wc <br /> Box Inlet Size 10"/8" Min Design CFM 300 CFM <br /> K Factor 2.08/2.01 Actual Min Airflow 300 CFM <br /> Min Diff.SP 0.04 in.wc <br /> Design Reheat Airflow 700 CFM <br /> Actual Reheat Airflow 700 CFM <br /> Reheat Diff.SP 0.55 in.wc <br /> AHU-01/B-11 Supply Outlet Summary <br /> System/Unit Outlet Size LxW/ Instrument AK Design Prelim Final CFM %Final <br /> Type D Factor CFM CFM <br /> Outlet-01 CD 12 Flowhood 1.00 250 250 250 100 <br /> Outlet-02 CD 12 Flowhood 1.00 250 250 250 100 <br /> Outlet-03 CD 16 Flowhood 1.00 250 - 250 250 100 <br /> Outlet-04 CD 16 Flowhood 1.00 250 250 250 100 <br /> Totals: - - - - 1000 1000 1000 100 <br /> SYSTEM/UNIT: AHU-01/B-12 Tested By: Eric Liles <br /> Date: 6/17/2024 <br /> Unit Data Term Box Test Data <br /> Manufacturer Trane Design Max Airflow 700 CFM <br /> Model Number VDDF Actual Max Airflow 700 CFM <br /> Serial Number R23K01748 Max Diff.SP 0.49 in.wc <br /> Box Inlet Size 08/06 Min Design CFM 180 CFM <br /> K Factor 2.11/2.13 Actual Min Airflow 180 CFM <br /> Min Diff.SP 0.04 in.wc <br /> Design Reheat Airflow 520 CFM <br /> Actual Reheat Airflow 510 CFM <br /> Reheat Diff.SP 0.97 in.wc <br /> AHU-01/B-12 Supply Outlet Summary <br /> System/Unit Outlet Size LxW/ Instrument AK Design Prelim Final CFM %Final <br /> Type D Factor CFM CFM <br /> Outlet-01 CD 24x24 Flowhood 1.00 700 700 700 100 <br /> Totals: - - - - 700 700 700 100 <br /> Farrington Air Quality Services <br />