FARRINGTON <br /> m §,, D AIR QUALITY SERVICES <br /> Air Handling Unit <br /> PROJECT: Ballot Facility TI DATE: 6/17/2024 <br /> LOCATION: Everett,WA CONTACT: JT Parker <br /> PROJECT#: 23-1064 <br /> SYSTEM/UNIT: AHU-01/B-09 Tested By: Eric Liles <br /> Date: 6/17/2024 <br /> Unit Data Term Box Test Data <br /> Manufacturer Trane Design Max Airflow 450 CFM <br /> Model Number VDDF Actual Max Airflow 413 CFM <br /> Serial Number R23K01752 Max Diff.SP 0.63 in.wc <br /> Box Inlet Size 6"/6" Min Design CFM 135 CFM <br /> K Factor 2.21/2.06 Actual Min Airflow 135 CFM <br /> Min Diff.SP 0.06 in.wc <br /> Design Reheat Airflow 315 CFM <br /> Actual Reheat Airflow 305 CFM <br /> Reheat Diff.SP 0.34 in.wc <br /> AHU-01/B-09 Supply Outlet Summary <br /> System/Unit Outlet \Size LxW/ Instrument AK Design Prelim Final CFM %Final <br /> Type D Factor CFM CFM <br /> Outlet-01 CD 8 Flowhood 1.00 225 225 225 100 <br /> Outlet-02 CD 8 Flowhood 1.00 - 225 - 225 225 100 <br /> Totals: - - - - 450 450 450 100 <br /> SYSTEM/UNIT: AHU-01/B-10 Tested By: Eric Liles <br /> Date: 6/17/2024 <br /> Unit Data Term Box Test Data <br /> Manufacturer Trane Design Max Airflow 900 CFM <br /> Model Number VDDF Actual Max Airflow 890 CFM <br /> Serial Number R23K01741 Max Diff.SP 0.34 in.wc <br /> Box Inlet Size 1078" Min Design CFM 270 CFM <br /> K Factor 2.03/2.02 Actual Min Airflow 270 CFM <br /> Min Diff.SP 0.05 in.wc <br /> Design Reheat Airflow 630 CFM <br /> Actual Reheat Airflow 615 CFM <br /> Reheat Diff.SP 0.42 in.wc <br /> AHU-01/B-10 Supply Outlet Summary <br /> System/Unit Outlet Size LxW/ Instrument AK Design Prelim Final CFM %Final <br /> Type D Factor CFM CFM <br /> Outlet-01 CD 14 Flowhood 1.00 300 300 275 92 <br /> Outlet-02 CD 14 Flowhood 1.00 300 300 275 92 <br /> Outlet-03 CD 14 Flowhood 1.00 300 275 275 92 <br /> Totals: - - - - 900 875 825 92 <br /> Farrington Air Quality Services <br />