Laserfiche WebLink
''' � FARRINGTON <br /> r/ AIR QUALITY SERVICES <br /> Air Handling Unit <br /> PROJECT: Ballot Facility TI DATE: 6/17/2024 <br /> LOCATION: Everett,WA CONTACT: JT Parker <br /> PROJECT#: 23-1064 <br /> SYSTEM/UNIT: AHU-01/B-15 Tested By: Eric Liles <br /> Date: 6/17/2024 <br /> Unit Data Term Box Test Data <br /> Manufacturer Trane Design Max Airflow 900 CFM <br /> Model Number VDDF Actual Max Airflow 900 CFM <br /> Serial Number R23K01744 Max Diff.SP 0.35 in.wc <br /> Box Inlet Size 10"/8" Min Design CFM 270 CFM <br /> K Factor 2.01/2.00 Actual Min Airflow 270 CFM <br /> Min Diff.SP 0.03 in.wc <br /> Design Reheat Airflow 630 CFM <br /> Actual Reheat Airflow 630 CFM <br /> Reheat Diff.SP 0.42 in.wc <br /> AHU-01/B-15 Supply Outlet Summary <br /> System/Unit Outlet Size LxW/ Instrument AK Design Prelim Final CFM %Final <br /> Type D Factor CFM CFM <br /> Outlet-01 CD 8 Flowhood 1.00 150 150 150 100 <br /> Outlet-02 CD 8 Flowhood 1.00 150 150 150 100 <br /> Outlet-03 CD 12 Flowhood 1.00 300 300 300 100 <br /> Outlet-04 CD 12 Flowhood 1.00 300 300 300 100 <br /> Totals: - - - - 900 900 900 100 <br /> SYSTEM/UNIT: AHU-01/B-16 Tested By: Eric Liles <br /> Date: 6/17/2024 <br /> Unit Data Term Box Test Data <br /> Manufacturer Trane Design Max Airflow 675 CFM <br /> Model Number VDDF Actual Max Airflow 670 CFM <br /> Serial Number R23K01753 Max Diff.SP 0.50 in.wc <br /> Box Inlet Size 08/06 Min Design CFM 205 CFM <br /> K Factor 2.07/2.20 Actual Min Airflow 205 CFM <br /> Min Diff.SP 0.05 in.wc <br /> Design Reheat Airflow 470 CFM <br /> Actual Reheat Airflow 460 CFM <br /> Reheat Diff.SP 0.79 in.wc <br /> AHU-01/B-16 Supply Outlet Summary <br /> System/Unit Outlet Size LxW/ Instrument AK Design Prelim Final CFM %Final <br /> Type D Factor CFM CFM <br /> Outlet-01 CD 10 Flowhood 1.00 225 225 225 100 <br /> Outlet-02 CD 10 Flowhood 1.00 225 225 225 100 <br /> Outlet-03 CD 10 Flowhood 1.00 225 220 220 - 98 <br /> Totals: - - - - 675 670 670 99 <br /> Farrington Air Quality Services <br />