T- ' FARRINGTON <br /> [1 7-- AIR QUALITY SERVICES <br /> Air Handling Unit <br /> PROJECT: Ballot Facility TI DATE: 6/17/2024 <br /> LOCATION: Everett,WA CONTACT: JT Parker <br /> PROJECT#: 23-1064 <br /> SYSTEM/UNIT: AHU-01/B-17 Tested By: Eric Liles <br /> Date: 6/17/2024 <br /> Unit Data Term Box Test Data <br /> Manufacturer Trane Design Max Airflow 600 CFM <br /> Model Number VDDF Actual Max Airflow 590 CFM <br /> Serial Number R23K01754 Max Diff.SP 0.39 in.wc <br /> Box Inlet Size 08/06 Min Design CFM 180 CFM <br /> K Factor 2.0/2.15 Actual Min Airflow 0 CFM <br /> Min Diff.SP 180.00 in.wc <br /> Design Reheat Airflow 420 CFM <br /> Actual Reheat Airflow 410 CFM <br /> Reheat Diff.SP 0.64 in.wc <br /> AHU-01/B-17 Supply Outlet Summary <br /> System/Unit Outlet Size LxW/ Instrument AK Design Prelim Final CFM %Final <br /> Type D Factor CFM CFM <br /> Outlet-01 CD 12 Flowhood 1.00 300 290 290 97 <br /> Outlet-02 CD 12 Flowhood 1.00 300 290 290 97 <br /> Totals: - - - 600 580 580 97 <br /> SYSTEM/UNIT: AHU-01/B-18 Tested By: Eric Liles <br /> Date: 6/17/2024 <br /> Unit Data Term Box Test Data <br /> Manufacturer Trane Design Max Airflow 550 CFM <br /> Model Number VDDF Actual Max Airflow 540 CFM <br /> Serial Number R23K01755 Max Diff.SP 0.33 in.wc <br /> Box Inlet Size 08/06 Min Design CFM 165 CFM <br /> K Factor 2.06/2.18 Actual Min Airflow 165 CFM <br /> Min Diff.SP 0.03 in.wc <br /> Design Reheat Airflow 385 CFM <br /> Actual Reheat Airflow 370 CFM <br /> Reheat Diff.SP 0.51 in.wc <br /> AHU-01/B-18 Supply Outlet Summary <br /> System/Unit Outlet Size LxW/ Instrument AK Design Prelim Final CFM %Final <br /> Type D _Factor CFM CFM <br /> Outlet-01 CD 12 Flowhood 1.00 275 270 270 98 <br /> Outlet-02 CD 12 Flowhood 1.00 275 270 270 98 <br /> Totals: - - - - 550 540 540 98 <br /> Farrington Air Quality Services <br />