Laserfiche WebLink
FARRINGTON <br /> AIR QUALITY SERVICES <br /> Fan Unit <br /> PROJECT: Ballot Facility TI DATE: 6/17/2024 <br /> LOCATION: Everett,WA CONTACT: JT Parker <br /> PROJECT#: 23-1064 <br /> SYSTEM/UNIT: EF-01 Tested By: Eric Liles <br /> Date: 6/17/2024 <br /> Unit Data Motor Data <br /> Unit Manufacturer Greenheck Motor Type Direct Drive <br /> Unit Model Number CSP-A390-VG Nameplate Motor FL Amps 1.50 Amps <br /> Type of Service Dedicated Exhaust Nameplate Motor Hertz 60 Hz <br /> Nominal Efficiency(0.00) 0.90% <br /> Test Data Motor Power Factor(0.00) 0.80 <br /> Design Actual <br /> Airflow 300 CFM Motor Data <br /> Design Nameplate <br /> Motor Voltage 120 Volts <br /> Motor RPM 1750 RPM <br /> Motor Phase 1 <br /> Log: EF-01 6/10/2024 Chris Brittenham Fan is not making design CFM.Speed control set to <br /> 10,but only achieving 43%of design. <br /> EF-01 Exhaust Inlet Summary <br /> System/Unit Inlet Type Size LxW/ Instrument AK Design Prelim Final CFM %Final <br /> D _Factor CFM _ CFM <br /> Inlet-01 EG Flowhood 1.00 300 130 <br /> Totals: - - - 300 130 0 0 <br /> Farrington Air Quality Services <br />