MODULE SPECIFICATIONS QCelIs Q.PEAK DUO BLK ML-G10+/t 400 DESIGN LOCATION AND TEMPERATURES CONDUCTOR SIZE CALCULATIONS
<br /> RATED POWER(STC) 400 W TEMPERATURE DATA SOURCE ASHRAE 2%AVG.HIGH TEMP MICROINVERTER TO MAX.SHORT CIRCUIT CURRRENT(ISC)= 13.3 A AC
<br /> MODULE VOC 45.55 V DC STATE Washington JUNCTION BOX(1) MAX.CURRENT(ISC X1.25) = 16.6 A AC
<br /> MODULE VMP 38.09 V DC CITY EVERETT CONDUCTOR(TC-ER,COPPER(90-C))= 12 AWG BLUE RAVEN
<br /> MODULE IMP 10.5 A DC WEATHER STATION SNOHOMISH COi CONDUCTOR RATING= 30 A
<br /> MODULE ISC 11.07 A DC ASHRAE EXTREME LOW TEMP('C) -51 AMB. TEMP.AMP.CORRECTION = 1
<br /> VOC CORRECTION -0.27%/'C ASHRAE 2%AVG.HIGH TEMP("C) 30 ADJUSTED AMP.= 30 > 16.6 1403 N. Research Way
<br /> VMP CORRECTION -0.34%/'C JUNCTION BOX TO MAX.SHORT CIRCUIT CURRRENT(ISC)= 13.3 A AC Orem, UT 84097
<br /> SERIES FUSE RATING 20 A DC SYSTEM ELECTRICAL SPECIFICATIONS CIR 1 CIR 2 CIR 3 CIR 4 CIR 5 CIR 6 JUNCTION BOX(2) MAX.CURRENT(ISC X1.25)= 16.6 A AC 8ERAV.4480
<br /> W W W.BLU RAVENSOLAR.COM
<br /> ADJ.MODULE VOC @ ASHRAE LOW TEMP 49.2 V DC NUMBER OF MODULES PER MPPT11 CONDUCTOR(THWN-2,COPPER(75'C TERM.))= 10 AWG CONFIDENTIAL-THE INFORMATION
<br /> ADJ. MODULE VMP @ ASHRAE 2%AVG.HIGH TEMP 33.3 V DC DC POWER RATING PER CIRCUIT(STC) 4400 CONDUCTOR RATING= 35 A HEREIN CONTAINED SHALL NOT BE
<br /> TOTAL MODULE NUMBER 11 CONDUIT FILL DERATE= 1 USED FOR THE EOA NE
<br /> NO
<br /> RA R
<br /> EXCEPT BLUE RAVENN SOLLAR NOR
<br /> MICROINVERTER SPECIFICATIONS Enphase IQ8+Microinverters STC RATING OF ARRAY 4400 AMB.TEMP.AMP.CORRECTION = 1 SHALL IT BE DISCLOSED IN WHOLE OR
<br /> IN PART TO OTHERS OUTSIDE
<br /> POWER POINT TRACKING(MPPT)MIN/MAX 30 - 58 V DC AC CURRENT @ MAX POWER POINT(IMP 13.3 ADJUSTED AMP.= 35 > 16.6 RECIPIENTS ORGANIZATION,EXCEPT
<br /> MAXIMUM INPUT VOLTAGE 60 V DC MAX.CURRENT(IMP X 1.25) 16.6375 JUNCTION BOX TO MAX.SHORT CIRCUIT CURRRENT(ISC)= 13.3 A AC IN CONNECTION WITH THE D
<br /> USE OF THE RESPECTIVE EQUIPMEUIPME NT,
<br /> MAXIMUM DC SHORT CIRCUIT CURRENT 15 A DC OCPD CURRENT RATI NG PER CIRCUIT 20 COMBINER BOX(3) MAX.CURRENT(ISC X1.25)= 16.6 A AC WITHOUT THE WRITTEN PERMISSION
<br /> MAXIMUM USABLE DC INPUT POWER 440 W MAX.COMB.ARRAY AC CURRENT(IMP) 13.3OF BLUE RAVEN SOLAR LLC.
<br /> CONDUCTOR(TNWN-2,COPPER(75-C TERM.))= 10 AWG
<br /> MAXIMUM OUTPUT CURRENT 1.21 A AC MAX.ARRAY AC POWER 319OW AC CONDUCTOR RATING= 35 A
<br /> AC OVERCURRENT PROTECTION 20 A CONDUIT FILL DERATE= 1NABCEP
<br /> MAXIMUM OUTPUT POWER 290 W AC VOLTAGE RISE CALCULATIONS DIST(FT) COND. IRISE(V) VEND(V) %VRISE AMB.TEMP.AMP.CORRECTION= 1 CERTIFIED
<br /> CEC WEIGHTED EFFICIENCY 97% VRISE SEC. 1(MICRO TO JBOX) 39.6 12 Cu. 1.76 241.76 0.73% ADJUSTED AMP.= 35 > 16.6
<br /> VRISE SEC.2(JBOX TO COMBINER BOX) 40 10 Cu. 1.3S 241.35 0.56% COMBINER BOX TO INVERTER RATED AMPS= 13.3 A AC PV INSTALLATION
<br /> AC PHOTOVOLATIC MODULE MARKING(NEC 690.52) VRISE SEC.3(COMBINER BOX TO PD1) 30 10 Cu. 1.01 241.01 0.42% MAIN PV OCPD(15) MAX.CURRENT(RATED AMPS X1.25)= 16.64 A AC PROFESSIONAL
<br /> NOMINAL OPERATING AC VOLTAGE 240 V AC TOTAL VRISE 4.13 244.13 1.72% CONDUCTOR(THWN-2,COPPER(75-C TERM.))= 10 AWG Scott Gurney
<br /> #PV-011719-015866
<br /> NOMINAL OPERATING AC FREQUENCY 47-68 HZ AC CONDUCTOR RATING= 3S A
<br /> MAXIMUM AC POWER 240 VA AC PHOTOVOLTAIC AC DISCONNECT OUTPUT LABEL(NEC 690.54) CONDUIT FILL DERATE= 1 CONTRACTOR:
<br /> MAXIMUM AC CURRENT 1.0 A AC AC OUTPUT CURRENT 13.3 A AC AMB.TEMP.AMP,CORRECTION= 1 BRS FIELD OPS
<br /> MAXIMUM OCPD RATING FOR AC MODULE 20 A AC NOMINAL AC VOLTAGE 240 V AC ADJUSTED AMP.= 35 > 16.6 800-377-4480
<br /> GROUNDING NOTES WIRING &CONDUIT NOTES Z Q 0
<br /> 1.A GROUNDING ELECTRODE SYSTEM IN ACCORDANCE WITH[NEC 690.47]AND[NEC 250.50-60]SHALL BE 1.ALL CONDUIT SIZES AND TYPES, SHALL BE LISTED FOR ITS PURPOSE AND APPROVED FOR THE SITE 0 N
<br /> PROVIDED. PER[NEC 690.47],THE GROUNDING ELECTRODE SYSTEM OF AN EXISTING BUILDING MAY BE APPLICATIONS. ~ 00
<br /> USED AND BE BONDED AT THE SERVICE ENTRANCE. IF EXISTING SYSTEM IS INACCESSIBLE, OR 2. BOLTED CONNECTION REQUIRED IN DC DISCONNECTS ON THE WHITE GROUNDED CONDUCTOR(USE c
<br /> INADEQUATE,OR IS ONLY METALLIC WATER PIPING,A SUPPLEMENTAL GROUNDING ELECTRODE WILL BE POLARIS BLOCK OR NEUTRAL BAR). Q �O O
<br /> USED AT THE INVERTER LOCATION CONSISTING OF A UL LISTED 8 FT GROUND ROD WITH ACORN CLAMP. 3.ANY CONNECTION ABOVE LIVE PARTS MUST BE WATERTIGHT.REDUCING WASHERS DISALLOWED ABOVE c
<br /> 2.THE GROUNDING ELECTRODE CONDUCTOR SHALL BE PROTECTED FROM PHYSICAL DAMAGE BETWEEN LIVE PARTS,MEYERS HUBS RECOMMENDED 0) a
<br /> THE GROUNDING ELECTRODE AND THE PANEL(OR INVERTER) IF SMALLER THAN#6 AWG COPPER WIRE 4.UV RESISTANT CABLE TIES(NOT ZIP TIES)USED FOR PERMANENT WIRE MANAGEMENT OFF THE ROOF 0 C 0) W W
<br /> PER [NEC 250.64(B)]. THE GROUNDING ELECTRODE CONDUCTOR WILL BE CONTINUOUS, EXCEPT FOR SURFACE IN ACCORDANCE WITH[NEC 110.2,110.3(A-B)]. LL M N N
<br /> SPLICES OR JOINTS AT BUSBARS WITHIN LISTED EQUIPMENT PER[NEC 250.64(C)]. 5. SOLADECK JUNCTION BOXES MOUNTED FLUSH WITH ROOF SURFACE TO BE USED FOR WIRE 0 V)
<br /> Z
<br /> 3.GROUNDING ELECTRODE CONDUCTORS SHALL BE NO LESS THAN 8 AWG AND NO GREATER THAN 6 AWG MANAGEMENT AND AS FLASHED ROOF PENETRATIONS FOR INTERIOR CONDUIT RUNS. M N
<br /> COPPER AND BONDED TO THE EXISTING GROUNDING ELECTRODE TO PROVIDE FOR A COMPLETE SYSTEM. 6. ALL PV CABLES AND HOMERUN WIRES BE TYPE USE-2,AND SINGLE-CONDUCTOR CABLE LISTED AND E > C
<br /> 4.PV SYSTEM SHALL BE GROUNDED IN ACCORDANCE TO[NEC 250.21],[NEC TABLE 250.122],AND ALL METAL IDENTIFIED AS PV WIRE,TYPE TC-ER,OR EQUIVALENT;ROUTED TO SOURCE CIRCUIT COMBINER BOXES AS M > c
<br /> PARTS OR MODULE FRAMES ACCORDING TO[NEC 690.461. REQUIRED. CLCI ('0 LU Lu
<br /> 5.MODULE SOURCE CIRCUITS SHALL BE GROUNDED IN ACCORDANCE TO[NEC 690.42]. 7.ALL CONDUCTORS AND OCPD SIZES AND TYPES SPECIFIED ACCORDING TO[NEC 690.8]FOR MULTIPLE G
<br /> cu
<br /> 6. THE GROUNDING CONNECTION TO A MODULE SHALL BE ARRANGED SUCH THAT THE REMOVAL OF A CONDUCTORS. O X +�+ 1 J W w
<br /> MODULE DOES NOT INTERRUPT A GROUNDED CONDUCTOR TO ANOTHER MODULE. 8.ALL PV DC CONDUCTORS IN CONDUIT EXPOSED TO SUNLIGHT SHALL BE INSTALLED AT LEAST 7/8"ABOVE 0 M't 0f7. EACH MODULE WILL BE GROUNDED USING THE SUPPLIED CONNECTION POINTS IDENTIFIED IN THE THE ROOF SURFACE AND DERATED ACCORDING TO [NEC TABLE 310.15 (B)(2)(A)], [NEC TABLE C LO U) (/)
<br /> MANUFACTURER'S INSTALLATION INSTRUCTIONS. 310.15(B)(3)(A)],&[NEC 310.15(13)(3)(C)]. O N w
<br /> 8.ENCLOSURES SHALL BE PROPERLY PREPARED WITH REMOVAL OF PAINT/FINISH AS APPROPRIATE WHEN 9.EXPOSED ROOF PV DC CONDUCTORS SHALL BE USE-2,90-C RATED,WET AND UV RESISTANT,AND UL = 00 > V V
<br /> GROUNDING EQUIPMENT WITH TERMINATION GROUNDING LUGS. LISTED RATED FOR 600V, UV RATED SPIRAL WRAP SHALL BE USED TO PROTECT WIRE FROM SHARP U M W Q D
<br /> 9.GROUNDING SYSTEM COMPONENTS SHALL BE LISTED FOR THEIR PURPOSE,AND GROUNDING DEVISES EDGES.
<br /> EXPOSED TO THE ELEMENTS SHALL BE RATED FOR DIRECT BURIAL. 10. PHASE AND NEUTRAL CONDUCTORS SHALL BE DUAL RATED THHN/THWN-2 INSULATED, 90°C RATED,
<br /> 10.GROUNDING AND BONDING CONDUCTORS SHALL BE COPPER,SOLID OR STRANDED,AND BARE WHEN WET AND UV RESISTANT,RATED FOR 600V DRAWING BY:
<br /> EXPOSED. 11. 4-WIRE DELTA CONNECTED SYSTEMS HAVE THE PHASE WITH THE HIGHER VOLTAGE TO GROUND
<br /> 11. EQUIPMENT GROUNDING CONDUCTORS SHALL BE SIZED ACCORDING TO [NEC 690.45] AND BE A MARKED ORANGE OR IDENTIFIED BY OTHER EFFECTIVE MEANS. Brendan Fillmore
<br /> MINIMUM OF 10 AWG WHEN NOT EXPOSED TO DAMAGE (6 AWG SHALL BE USED WHEN EXPOSED TO 12.ALL SOURCE CIRCUITS SHALL HAVE INDIVIDUAL SOURCE CIRCUIT PROTECTION
<br /> DAMAGE). 13.VOLTAGE DROP LIMITED TO 2%FOR DC CIRCUITS AND 3%FOR AC CIRCUITS PLOT DATE:
<br /> 12.GROUNDING AND BONDING CONDUCTORS,IF INSULATED,SHALL BE COLOR CODED GREEN(OR MARKED 14. NEGATIVE GROUNDED SYSTEMS DC CONDUCTORS SHALL BE COLOR CODED AS FOLLOWS: DC
<br /> GREEN IF 4 AWG OR LARGER). POSITIVE-RED(OR MARKED RED),DC NEGATIVE-GREY(OR MARKED GREY) May 17 2023
<br /> 13.ALL CONDUIT BETWEEN THE UTILITY AC DISCONNECT AND THE POINT OF CONNECTION SHALL HAVE 15.POSITIVE GROUNDED SYSTEMS DC CONDUCTORS COLOR CODED:
<br /> GROUNDED BUSHINGS AT BOTH ENDS. DC POSITIVE-GREY(OR MARKED GREY),DC NEGATIVE-BLACK(OR MARKED BLACK) w W e 9�
<br /> 14. SYSTEM GEC SIZED ACCORDING TO [NEC 690.47], [NEC TABLE 250.661, DC SYSTEM GEC
<br /> SIZED 16.AC CONDUCTORS>4AWG COLOR CODED
<br /> ACCORDING O[NEC 250.166],MINIMUM 8 AWG WHEN INSULATED, AWG WHEN EXPOSED TO DAMAGE. PHASE C OR L3-BLUE,NEUTRAL-WHITE/GRAYOR MARKED: PHASE A OR L1-BLACK,PHASE B OR L2-RED, P ��WAS/� E� 20232 PROJECT NUMBER:
<br /> 15. EXPOSED NON-CURRENT CARRYING METAL PARTS OF MODULE FRAMES, EQUIPMENTS, AND 'USE-2 IS NOT INDOOR RATED BUT PV CABLE IS RATED THWN/THWN-2 AND MAY BE USED INSIDE �7 764 787
<br /> CONDUCTOR ENCLOSURES SHALL BE GROUNDED IN ACCORDANCE WITH[NEC 250.134]OR[NEC 250.136(A)] "USE-2 IS AVAILABLE AS UV WHITE Z
<br /> REGARDLESS OF VOLTAGE. 17. IGID CONDUIT,IF INSTALLED,CONDUIT DETERMINED TO BERANTHROUGH ATTICD/OR NIPPLES)MUST INTHEN CONDUIT WILE A PULL BUSHING TO LBE EITHER ECT 18. FHER EMT, 3 08:05 :5 SHEET NAME:
<br /> FMC, OR MC CABLE IF DC CURRENT COMPLYING WITH [NEC 690.31], [NEC 250.118(10)]. DISCONNECTING
<br /> MEANS SHALL COMPLY WITH[NEC 690.13]AND[NEC 690.151.19.CONDUIT E L EC CALCS
<br /> 230 6(4)]AND SECUREDTHROUGH
<br /> NO GREATER THAN 6AAPARTLEAST
<br /> PER[NEC BELOW O R006 j SURFACE COMPLYING WITH[NEC �r .Q�Ojs � ' '
<br /> S :�1- Cj�� _0600
<br /> REVISION: PAGE NUMBER:
<br /> SZo1' F�
<br /> 0 PV6