Laserfiche WebLink
MODULE SPECIFICATIONS QCelIs Q.PEAK DUO BLK ML-G10+/t 400 DESIGN LOCATION AND TEMPERATURES CONDUCTOR SIZE CALCULATIONS <br /> RATED POWER(STC) 400 W TEMPERATURE DATA SOURCE ASHRAE 2%AVG.HIGH TEMP MICROINVERTER TO MAX.SHORT CIRCUIT CURRRENT(ISC)= 13.3 A AC <br /> MODULE VOC 45.55 V DC STATE Washington JUNCTION BOX(1) MAX.CURRENT(ISC X1.25) = 16.6 A AC <br /> MODULE VMP 38.09 V DC CITY EVERETT CONDUCTOR(TC-ER,COPPER(90-C))= 12 AWG BLUE RAVEN <br /> MODULE IMP 10.5 A DC WEATHER STATION SNOHOMISH COi CONDUCTOR RATING= 30 A <br /> MODULE ISC 11.07 A DC ASHRAE EXTREME LOW TEMP('C) -51 AMB. TEMP.AMP.CORRECTION = 1 <br /> VOC CORRECTION -0.27%/'C ASHRAE 2%AVG.HIGH TEMP("C) 30 ADJUSTED AMP.= 30 > 16.6 1403 N. Research Way <br /> VMP CORRECTION -0.34%/'C JUNCTION BOX TO MAX.SHORT CIRCUIT CURRRENT(ISC)= 13.3 A AC Orem, UT 84097 <br /> SERIES FUSE RATING 20 A DC SYSTEM ELECTRICAL SPECIFICATIONS CIR 1 CIR 2 CIR 3 CIR 4 CIR 5 CIR 6 JUNCTION BOX(2) MAX.CURRENT(ISC X1.25)= 16.6 A AC 8ERAV.4480 <br /> W W W.BLU RAVENSOLAR.COM <br /> ADJ.MODULE VOC @ ASHRAE LOW TEMP 49.2 V DC NUMBER OF MODULES PER MPPT11 CONDUCTOR(THWN-2,COPPER(75'C TERM.))= 10 AWG CONFIDENTIAL-THE INFORMATION <br /> ADJ. MODULE VMP @ ASHRAE 2%AVG.HIGH TEMP 33.3 V DC DC POWER RATING PER CIRCUIT(STC) 4400 CONDUCTOR RATING= 35 A HEREIN CONTAINED SHALL NOT BE <br /> TOTAL MODULE NUMBER 11 CONDUIT FILL DERATE= 1 USED FOR THE EOA NE <br /> NO <br /> RA R <br /> EXCEPT BLUE RAVENN SOLLAR NOR <br /> MICROINVERTER SPECIFICATIONS Enphase IQ8+Microinverters STC RATING OF ARRAY 4400 AMB.TEMP.AMP.CORRECTION = 1 SHALL IT BE DISCLOSED IN WHOLE OR <br /> IN PART TO OTHERS OUTSIDE <br /> POWER POINT TRACKING(MPPT)MIN/MAX 30 - 58 V DC AC CURRENT @ MAX POWER POINT(IMP 13.3 ADJUSTED AMP.= 35 > 16.6 RECIPIENTS ORGANIZATION,EXCEPT <br /> MAXIMUM INPUT VOLTAGE 60 V DC MAX.CURRENT(IMP X 1.25) 16.6375 JUNCTION BOX TO MAX.SHORT CIRCUIT CURRRENT(ISC)= 13.3 A AC IN CONNECTION WITH THE D <br /> USE OF THE RESPECTIVE EQUIPMEUIPME NT, <br /> MAXIMUM DC SHORT CIRCUIT CURRENT 15 A DC OCPD CURRENT RATI NG PER CIRCUIT 20 COMBINER BOX(3) MAX.CURRENT(ISC X1.25)= 16.6 A AC WITHOUT THE WRITTEN PERMISSION <br /> MAXIMUM USABLE DC INPUT POWER 440 W MAX.COMB.ARRAY AC CURRENT(IMP) 13.3OF BLUE RAVEN SOLAR LLC. <br /> CONDUCTOR(TNWN-2,COPPER(75-C TERM.))= 10 AWG <br /> MAXIMUM OUTPUT CURRENT 1.21 A AC MAX.ARRAY AC POWER 319OW AC CONDUCTOR RATING= 35 A <br /> AC OVERCURRENT PROTECTION 20 A CONDUIT FILL DERATE= 1NABCEP <br /> MAXIMUM OUTPUT POWER 290 W AC VOLTAGE RISE CALCULATIONS DIST(FT) COND. IRISE(V) VEND(V) %VRISE AMB.TEMP.AMP.CORRECTION= 1 CERTIFIED <br /> CEC WEIGHTED EFFICIENCY 97% VRISE SEC. 1(MICRO TO JBOX) 39.6 12 Cu. 1.76 241.76 0.73% ADJUSTED AMP.= 35 > 16.6 <br /> VRISE SEC.2(JBOX TO COMBINER BOX) 40 10 Cu. 1.3S 241.35 0.56% COMBINER BOX TO INVERTER RATED AMPS= 13.3 A AC PV INSTALLATION <br /> AC PHOTOVOLATIC MODULE MARKING(NEC 690.52) VRISE SEC.3(COMBINER BOX TO PD1) 30 10 Cu. 1.01 241.01 0.42% MAIN PV OCPD(15) MAX.CURRENT(RATED AMPS X1.25)= 16.64 A AC PROFESSIONAL <br /> NOMINAL OPERATING AC VOLTAGE 240 V AC TOTAL VRISE 4.13 244.13 1.72% CONDUCTOR(THWN-2,COPPER(75-C TERM.))= 10 AWG Scott Gurney <br /> #PV-011719-015866 <br /> NOMINAL OPERATING AC FREQUENCY 47-68 HZ AC CONDUCTOR RATING= 3S A <br /> MAXIMUM AC POWER 240 VA AC PHOTOVOLTAIC AC DISCONNECT OUTPUT LABEL(NEC 690.54) CONDUIT FILL DERATE= 1 CONTRACTOR: <br /> MAXIMUM AC CURRENT 1.0 A AC AC OUTPUT CURRENT 13.3 A AC AMB.TEMP.AMP,CORRECTION= 1 BRS FIELD OPS <br /> MAXIMUM OCPD RATING FOR AC MODULE 20 A AC NOMINAL AC VOLTAGE 240 V AC ADJUSTED AMP.= 35 > 16.6 800-377-4480 <br /> GROUNDING NOTES WIRING &CONDUIT NOTES Z Q 0 <br /> 1.A GROUNDING ELECTRODE SYSTEM IN ACCORDANCE WITH[NEC 690.47]AND[NEC 250.50-60]SHALL BE 1.ALL CONDUIT SIZES AND TYPES, SHALL BE LISTED FOR ITS PURPOSE AND APPROVED FOR THE SITE 0 N <br /> PROVIDED. PER[NEC 690.47],THE GROUNDING ELECTRODE SYSTEM OF AN EXISTING BUILDING MAY BE APPLICATIONS. ~ 00 <br /> USED AND BE BONDED AT THE SERVICE ENTRANCE. IF EXISTING SYSTEM IS INACCESSIBLE, OR 2. BOLTED CONNECTION REQUIRED IN DC DISCONNECTS ON THE WHITE GROUNDED CONDUCTOR(USE c <br /> INADEQUATE,OR IS ONLY METALLIC WATER PIPING,A SUPPLEMENTAL GROUNDING ELECTRODE WILL BE POLARIS BLOCK OR NEUTRAL BAR). Q �O O <br /> USED AT THE INVERTER LOCATION CONSISTING OF A UL LISTED 8 FT GROUND ROD WITH ACORN CLAMP. 3.ANY CONNECTION ABOVE LIVE PARTS MUST BE WATERTIGHT.REDUCING WASHERS DISALLOWED ABOVE c <br /> 2.THE GROUNDING ELECTRODE CONDUCTOR SHALL BE PROTECTED FROM PHYSICAL DAMAGE BETWEEN LIVE PARTS,MEYERS HUBS RECOMMENDED 0) a <br /> THE GROUNDING ELECTRODE AND THE PANEL(OR INVERTER) IF SMALLER THAN#6 AWG COPPER WIRE 4.UV RESISTANT CABLE TIES(NOT ZIP TIES)USED FOR PERMANENT WIRE MANAGEMENT OFF THE ROOF 0 C 0) W W <br /> PER [NEC 250.64(B)]. THE GROUNDING ELECTRODE CONDUCTOR WILL BE CONTINUOUS, EXCEPT FOR SURFACE IN ACCORDANCE WITH[NEC 110.2,110.3(A-B)]. LL M N N <br /> SPLICES OR JOINTS AT BUSBARS WITHIN LISTED EQUIPMENT PER[NEC 250.64(C)]. 5. SOLADECK JUNCTION BOXES MOUNTED FLUSH WITH ROOF SURFACE TO BE USED FOR WIRE 0 V) <br /> Z <br /> 3.GROUNDING ELECTRODE CONDUCTORS SHALL BE NO LESS THAN 8 AWG AND NO GREATER THAN 6 AWG MANAGEMENT AND AS FLASHED ROOF PENETRATIONS FOR INTERIOR CONDUIT RUNS. M N <br /> COPPER AND BONDED TO THE EXISTING GROUNDING ELECTRODE TO PROVIDE FOR A COMPLETE SYSTEM. 6. ALL PV CABLES AND HOMERUN WIRES BE TYPE USE-2,AND SINGLE-CONDUCTOR CABLE LISTED AND E > C <br /> 4.PV SYSTEM SHALL BE GROUNDED IN ACCORDANCE TO[NEC 250.21],[NEC TABLE 250.122],AND ALL METAL IDENTIFIED AS PV WIRE,TYPE TC-ER,OR EQUIVALENT;ROUTED TO SOURCE CIRCUIT COMBINER BOXES AS M > c <br /> PARTS OR MODULE FRAMES ACCORDING TO[NEC 690.461. REQUIRED. CLCI ('0 LU Lu <br /> 5.MODULE SOURCE CIRCUITS SHALL BE GROUNDED IN ACCORDANCE TO[NEC 690.42]. 7.ALL CONDUCTORS AND OCPD SIZES AND TYPES SPECIFIED ACCORDING TO[NEC 690.8]FOR MULTIPLE G <br /> cu <br /> 6. THE GROUNDING CONNECTION TO A MODULE SHALL BE ARRANGED SUCH THAT THE REMOVAL OF A CONDUCTORS. O X +�+ 1 J W w <br /> MODULE DOES NOT INTERRUPT A GROUNDED CONDUCTOR TO ANOTHER MODULE. 8.ALL PV DC CONDUCTORS IN CONDUIT EXPOSED TO SUNLIGHT SHALL BE INSTALLED AT LEAST 7/8"ABOVE 0 M't 0f7. EACH MODULE WILL BE GROUNDED USING THE SUPPLIED CONNECTION POINTS IDENTIFIED IN THE THE ROOF SURFACE AND DERATED ACCORDING TO [NEC TABLE 310.15 (B)(2)(A)], [NEC TABLE C LO U) (/) <br /> MANUFACTURER'S INSTALLATION INSTRUCTIONS. 310.15(B)(3)(A)],&[NEC 310.15(13)(3)(C)]. O N w <br /> 8.ENCLOSURES SHALL BE PROPERLY PREPARED WITH REMOVAL OF PAINT/FINISH AS APPROPRIATE WHEN 9.EXPOSED ROOF PV DC CONDUCTORS SHALL BE USE-2,90-C RATED,WET AND UV RESISTANT,AND UL = 00 > V V <br /> GROUNDING EQUIPMENT WITH TERMINATION GROUNDING LUGS. LISTED RATED FOR 600V, UV RATED SPIRAL WRAP SHALL BE USED TO PROTECT WIRE FROM SHARP U M W Q D <br /> 9.GROUNDING SYSTEM COMPONENTS SHALL BE LISTED FOR THEIR PURPOSE,AND GROUNDING DEVISES EDGES. <br /> EXPOSED TO THE ELEMENTS SHALL BE RATED FOR DIRECT BURIAL. 10. PHASE AND NEUTRAL CONDUCTORS SHALL BE DUAL RATED THHN/THWN-2 INSULATED, 90°C RATED, <br /> 10.GROUNDING AND BONDING CONDUCTORS SHALL BE COPPER,SOLID OR STRANDED,AND BARE WHEN WET AND UV RESISTANT,RATED FOR 600V DRAWING BY: <br /> EXPOSED. 11. 4-WIRE DELTA CONNECTED SYSTEMS HAVE THE PHASE WITH THE HIGHER VOLTAGE TO GROUND <br /> 11. EQUIPMENT GROUNDING CONDUCTORS SHALL BE SIZED ACCORDING TO [NEC 690.45] AND BE A MARKED ORANGE OR IDENTIFIED BY OTHER EFFECTIVE MEANS. Brendan Fillmore <br /> MINIMUM OF 10 AWG WHEN NOT EXPOSED TO DAMAGE (6 AWG SHALL BE USED WHEN EXPOSED TO 12.ALL SOURCE CIRCUITS SHALL HAVE INDIVIDUAL SOURCE CIRCUIT PROTECTION <br /> DAMAGE). 13.VOLTAGE DROP LIMITED TO 2%FOR DC CIRCUITS AND 3%FOR AC CIRCUITS PLOT DATE: <br /> 12.GROUNDING AND BONDING CONDUCTORS,IF INSULATED,SHALL BE COLOR CODED GREEN(OR MARKED 14. NEGATIVE GROUNDED SYSTEMS DC CONDUCTORS SHALL BE COLOR CODED AS FOLLOWS: DC <br /> GREEN IF 4 AWG OR LARGER). POSITIVE-RED(OR MARKED RED),DC NEGATIVE-GREY(OR MARKED GREY) May 17 2023 <br /> 13.ALL CONDUIT BETWEEN THE UTILITY AC DISCONNECT AND THE POINT OF CONNECTION SHALL HAVE 15.POSITIVE GROUNDED SYSTEMS DC CONDUCTORS COLOR CODED: <br /> GROUNDED BUSHINGS AT BOTH ENDS. DC POSITIVE-GREY(OR MARKED GREY),DC NEGATIVE-BLACK(OR MARKED BLACK) w W e 9� <br /> 14. SYSTEM GEC SIZED ACCORDING TO [NEC 690.47], [NEC TABLE 250.661, DC SYSTEM GEC <br /> SIZED 16.AC CONDUCTORS>4AWG COLOR CODED <br /> ACCORDING O[NEC 250.166],MINIMUM 8 AWG WHEN INSULATED, AWG WHEN EXPOSED TO DAMAGE. PHASE C OR L3-BLUE,NEUTRAL-WHITE/GRAYOR MARKED: PHASE A OR L1-BLACK,PHASE B OR L2-RED, P ��WAS/� E� 20232 PROJECT NUMBER: <br /> 15. EXPOSED NON-CURRENT CARRYING METAL PARTS OF MODULE FRAMES, EQUIPMENTS, AND 'USE-2 IS NOT INDOOR RATED BUT PV CABLE IS RATED THWN/THWN-2 AND MAY BE USED INSIDE �7 764 787 <br /> CONDUCTOR ENCLOSURES SHALL BE GROUNDED IN ACCORDANCE WITH[NEC 250.134]OR[NEC 250.136(A)] "USE-2 IS AVAILABLE AS UV WHITE Z <br /> REGARDLESS OF VOLTAGE. 17. IGID CONDUIT,IF INSTALLED,CONDUIT DETERMINED TO BERANTHROUGH ATTICD/OR NIPPLES)MUST INTHEN CONDUIT WILE A PULL BUSHING TO LBE EITHER ECT 18. FHER EMT, 3 08:05 :5 SHEET NAME: <br /> FMC, OR MC CABLE IF DC CURRENT COMPLYING WITH [NEC 690.31], [NEC 250.118(10)]. DISCONNECTING <br /> MEANS SHALL COMPLY WITH[NEC 690.13]AND[NEC 690.151.19.CONDUIT E L EC CALCS <br /> 230 6(4)]AND SECUREDTHROUGH <br /> NO GREATER THAN 6AAPARTLEAST <br /> PER[NEC BELOW O R006 j SURFACE COMPLYING WITH[NEC �r .Q�Ojs � ' ' <br /> S :�1- Cj�� _0600 <br /> REVISION: PAGE NUMBER: <br /> SZo1' F� <br /> 0 PV6 <br />