MODULE SPECIFICATIONS QCeI[s Q.PEAK DUO BLK ML-G10*400 DESIGN LOCATION AND TEMPERATURES CONDUCTOR SIZE CALCULATIONS <br /> RATED POWER(STC) 400 W TEMPERATURE DATA SOURCE ASHRAE 2%AVG.HIGH TEMPI MICROINVERTER TO MAX.SHORT CIRCUIT CURRRENT(ISC) = 14.S A AC <br /> MODULE VOC 45.3 V DC STATE Washington JUNCTION BOX(1) MAX.CURRENT(ISC X1.25)= 18.2 A AC <br /> MODULE VMP 37.13 V DC CITY Everett CONDUCTOR(TC-ER,COPPER(90'C))= 12 AWG BLUE RAVE N <br /> MODULE IMP 10.77 A DC WEATHER STATION SNOHOMISH CO! CONDUCTOR RATING= 30 A <br /> MODULE ISC 11.14 A DC ASHRAE EXTREME LOW TEMP('C) -51 AMB.TEMP.AMP.CORRECTION = 1 <br /> VOC CORRECTION -0.27%/'C JASHRAE 2%AVG.HIGH TEMP('C) 30 ADJUSTED AMP.= 30 > 18.2 1403 N. Research Way <br /> VMP CORRECTION -0.34%/'C JUNCTION BOX TO MAX.SHORT CIRCUIT CURRRENT(ISC)= 14.5 A AC Orem, UT 84097 <br /> SERIES FUSE RATING 20 A DC SYSTEM ELECTRICAL SPECIFICATIONS CIR 1 CIR 2 CIR 3 CIR 4 CIR 5 CIR 6 JUNCTION BOX(2) MAX.CURRENT(ISC X1.25)= 18.2 A AC 8ERAV.4480 <br /> W W W.BLU RAVENSOLAR.COM <br /> ADJ. MODULE VOC @ ASHRAE LOW TEMP 49.0 V DC NUMBER OF MODULES PER MPPT 9 12 CONDUCTOR(THWN-2,COPPER(75-C TERM.))= 10 AWG <br /> CONFIDENTIAL-THE INFORMATION <br /> ADJ. MODULE VMP @ ASHRAE 2%AVG.HIGH TEMP 32.5 V DC DC POWER RATING PER CIRCUIT(STC) 360_0_ 4__8.0.0_ CONDUCTOR RATING= 35 A HEREIN CONTAINED SHALL NOT BE <br /> TOTAL MODULE NUMBER 21 CONDUIT FILL DERATE= 1 USED FOR THE A EOA NE <br /> NO <br /> RAR <br /> EXCEPT BLUE RVENN SOL <br /> AR NOR <br /> MICROINVERTER SPECIFICATIONS Enphase IQ8.Mkroinverters STC RATING OF ARRAY 8400 AMB.TEMP.AMP.CORRECTION= 1 SHALL IT BE DISCLOSED IN WHOLE OR <br /> IN PART TO OTHERS OUTSIDE <br /> POWER POINT TRACKING(MPPT)MIN/MAX 30 - 58 V DC AC CURRENT @ MAX POWER POINT(IMP 10.9 14.5 ADJUSTED AMP.= 35 > 18.2 RECIPIENTS ORGANIZATION,EXCEPT <br /> MAXIMUM INPUT VOLTAGE 60 V DC MAX CURRENT(IMP X1.25) 13.6125 18.15 JUNCTION BOX TO MAX.SHORT CIRCUIT CURRRENT(ISC)= 14.5 A AC IN CONNECTION WITH THE SALE AND <br /> USE OF THE RESPECTIVE EQUIPMENT, <br /> MAXIMUM DC SHORT CIRCUIT CURRENT 15 A DC OCPD CURRENT RATING PER CIRCUIT 20 20 COMBINER BOX(3) MAX.CURRENT(ISC X1.25)= 18.2 A AC WITHOUT THE WRITTEN PERMISSION <br /> MAXIMUM USABLE DC INPUT POWER 440 W MAX.COMB.ARRAY AC CURRENT(IMP) 25.4 CONDUCTOR(THWN-2,COPPER(75-C TERM.))= 10 AWG OF BLUE RAVEN SOLAR LLC. <br /> MAXIMUM OUTPUT CURRENT 1.21 A AC MAX.ARRAY AC POWER 6090W AC CONDUCTOR RATING= 35 A <br /> ACOVERCURRENT PROTECTION 20 A CONDUIT FILL DERATE= 0.8 NABCEP <br /> MAXIMUM OUTPUT POWER 290 W AC VOLTAGE RISE CALCULATIONS DIST(FT) COND. /RISE(V) VEND(V) %VRISE AMB.TEMP.AMP.CORRECTION = 1 CERTIFIED <br /> CEC WEIGHTED EFFICIENCY 97% VRISE SEC. 1(MICRO TO JBOX) 39.6 12 Cu. 1.76 241.76 0.73% ADJUSTED AMP.= 28 > 18.2 <br /> VRISE SEC 2(JBOX TO COMBINER BOX) 35 10 Cu, 1.29 24129 0.54% COMBINER BOX TO INVERTER RATED AMPS= 25.4 A AC PV INSTALLATION <br /> AC PHOTOVOLATIC MODULE MARKING(NEC 690.52) VRISE SEC.3(COMBINER BOX TO POI) 5 8 Cu 0-20 240.20 0.08% MAIN PV OCPD(15) MAX.CURRENT(RATED AMPS X1.25)= 31.76 A AC PROFESSIONAL <br /> NOMINAL OPERATING AC VOLTAGE 240 V AC TOTAL VRISE 3.25 243.25 1.35% CONDUCTOR(THWN-2,COPPER(75-C TERM.))= 8 AWG Scott Gurney <br /> #PV-011719-015866 <br /> NOMINAL OPERATING AC FREQUENCY 47-68 HZ AC CONDUCTOR RATING= 50 A <br /> MAXIMUMAC POWER 240 VA AC PHOTOVOLTAIC AC DISCONNECT OUTPUT LABEL(NEC 690.54) CONDUIT FILL DERATE= 1 CONTRACTOR: <br /> MAXIMUM AC CURRENT 1.0 A AC AC OUTPUT CURRENT 25.4 A AC AMB.TEMP.AMP.CORRECTION= 1 BRS FIELD OPS <br /> MAXIMUM OCPD RATING FOR AC MODULE 20 A AC NOMINAL AC VOLTAGE 240 V AC l ADJUSTED AMP.= 50 > 3L8 800-377-4480 <br /> GROUNDING NOTES WIRING &CONDUIT NOTES Z Q u <br /> 1.A GROUNDING ELECTRODE SYSTEM IN ACCORDANCE WITH[NEC 690.47]AND[NEC 250.50-60]SHALL BE 1.ALL CONDUIT SIZES AND TYPES, SHALL BE LISTED FOR ITS PURPOSE AND APPROVED FOR THE SITE 0 <br /> PROVIDED. PER[NEC 690.47],THE GROUNDING ELECTRODE SYSTEM OF AN EXISTING BUILDING MAY BE APPLICATIONS. MO <br /> USED AND BE BONDED AT THE SERVICE ENTRANCE. IF EXISTING SYSTEM IS INACCESSIBLE, OR 2. BOLTED CONNECTION REQUIRED IN DC DISCONNECTS ON THE WHITE GROUNDED CONDUCTOR(USE (V <br /> INADEQUATE,OR IS ONLY METALLIC WATER PIPING,A SUPPLEMENTAL GROUNDING ELECTRODE WILL BE POLARIS BLOCK OR NEUTRAL BAR). CC 00 <br /> USED AT THE INVERTER LOCATION CONSISTING OF A UL LISTED 8 FT GROUND ROD WITH ACORN CLAMP. 3.ANY CONNECTION ABOVE LIVE PARTS MUST BE WATERTIGHT.REDUCING WASHERS DISALLOWED ABOVE G O7 (.0 0Q <br /> 2.THE GROUNDING ELECTRODE CONDUCTOR SHALL BE PROTECTED FROM PHYSICAL DAMAGE BETWEEN LIVE PARTS,MEYERS HUBS RECOMMENDED > <br /> THE GROUNDING ELECTRODE AND THE PANEL(OR INVERTER) IF SMALLER THAN#6 AWG COPPER WIRE 4.UV RESISTANT CABLE TIES(NOT ZIP TIES)USED FOR PERMANENT WIRE MANAGEMENT OFF THE ROOF O Cu W LLQ <br /> PER [NEC 250.64(B)]. THE GROUNDING ELECTRODE CONDUCTOR WILL BE CONTINUOUS, EXCEPT FOR SURFACE IN ACCORDANCE WITH[NEC 110.2,110.3(A-B)]. LL L N N <br /> SPLICES OR JOINTS AT BUSBARS WITHIN LISTED EQUIPMENT PER[NEC 250.64(C)]. 5. SOLADECK JUNCTION BOXES MOUNTED FLUSH WITH ROOF SURFACE TO BE USED FOR WIRE Z <br /> 3.GROUNDING ELECTRODE CONDUCTORS SHALL BE NO LESS THAN 8 AWG AND NO GREATER THAN 6 AWG MANAGEMENT AND AS FLASHED ROOF PENETRATIONS FOR INTERIOR CONDUIT RUNS. y <br /> COPPER AND BONDED TO THE EXISTING GROUNDING ELECTRODE TO PROVIDE FOR A COMPLETE SYSTEM. 6. ALL PV CABLES AND HOMERUN WIRES BE TYPE USE-2,AND SINGLE-CONDUCTOR CABLE LISTED AND L C <br /> 4.PV SYSTEM SHALL BE GROUNDED IN ACCORDANCE TO[NEC 250.21],[NEC TABLE 250.122],AND ALL METAL IDENTIFIED AS PV WIRE,TYPE TC-ER,OR EQUIVALENT;ROUTED TO SOURCE CIRCUIT COMBINER BOXES AS W ��' W W <br /> PARTS OR MODULE FRAMES ACCORDING TO[NEC 690.461. REQUIRED. C <br /> 5.MODULE SOURCE CIRCUITS SHALL BE GROUNDED IN ACCORDANCE TO[NEC 690.42]. 7.ALL CONDUCTORS AND OCPD SIZES AND TYPES SPECIFIED ACCORDING TO[NEC 690.8]FOR MULTIPLE c V Il-- <br /> 6. THE GROUNDING CONNECTION TO A MODULE SHALL BE ARRANGED SUCH THAT THE REMOVAL OF A CONDUCTORS. O = 0 <br /> MODULE DOES NOT INTERRUPT A GROUNDED CONDUCTOR TO ANOTHER MODULE. 8.ALL PV DC CONDUCTORS IN CONDUIT EXPOSED TO SUNLIGHT SHALL BE INSTALLED AT LEAST 7/8"ABOVE <br /> 7. EACH MODULE WILL BE GROUNDED USING THE SUPPLIED CONNECTION POINTS IDENTIFIED IN THE THE ROOF SURFACE AND DERATED ACCORDING TO [NEC TABLE 310.15 (B)(2)(A)], [NEC TABLE (fl L V) <br /> MANUFACTURER'S INSTALLATION INSTRUCTIONS. 310.15(B)(3)(A)],&[NEC 510.15(13)(3)(C)]. _E � (U <br /> 8.ENCLOSURES SHALL BE PROPERLY PREPARED WITH REMOVAL OF PAINT/FINISH AS APPROPRIATE WHEN 9.EXPOSED ROOF PV DC CONDUCTORS SHALL BE USE-2,90-C RATED,WET AND UV RESISTANT,AND UL = M > U V <br /> GROUNDING EQUIPMENT WITH TERMINATION GROUNDING LUGS. LISTED RATED FOR 600V, UV RATED SPIRAL WRAP SHALL BE USED TO PROTECT WIRE FROM SHARP U 0 Lo W Q <br /> 9.GROUNDING SYSTEM COMPONENTS SHALL BE LISTED FOR THEIR PURPOSE,AND GROUNDING DEVISES EDGES. <br /> EXPOSED TO THE ELEMENTS SHALL BE RATED FOR DIRECT BURIAL. 10. PHASE AND NEUTRAL CONDUCTORS SHALL BE DUAL RATED THHNrrHWN-2 INSULATED, 90°C RATED, <br /> 10.GROUNDING AND BONDING CONDUCTORS SHALL BE COPPER,SOLID OR STRANDED,AND BARE WHEN WET AND UV RESISTANT,RATED FOR 600V DRAWING BY: <br /> EXPOSED. 11. 4-WIRE DELTA CONNECTED SYSTEMS HAVE THE PHASE WITH THE HIGHER VOLTAGE TO GROUND <br /> 11. EQUIPMENT GROUNDING CONDUCTORS SHALL BE SIZED ACCORDING TO [NEC 690.45] AND BE A MARKED ORANGE OR IDENTIFIED BY OTHER EFFECTIVE MEANS. Brendan Fillmore <br /> MINIMUM OF 10 AWG WHEN NOT EXPOSED TO DAMAGE (6 AWG SHALL BE USED WHEN EXPOSED TO 12.ALL SOURCE CIRCUITS SHALL HAVE INDIVIDUAL SOURCE CIRCUIT PROTECTION w <br /> 2023 ,05 , 1 <br /> DAMAGE). 13.VOLTAGE DROP LIMITED TO 2%FOR DC CIRCUITS AND 3%FOR AC CIRCUITS >♦E Q12.GROUNDING AND BONDING CONDUCTORS,IF INSULATED,SHALL BE COLOR CODED GREEN(OR MARKED 14. NEGATIVE GROUNDED SYSTEMS DC CONDUCTORS SHALL BE COLOR CODED AS FOLLOWS: DC , PLOT DATE: <br /> GREEN IF 4 AWG OR LARGER). POSITIVE-RED(OR MARKED RED),DC NEGATIVE-GREY(OR MARKED GREY) PO� /�/ FMay 16, 2023 <br /> 13.ALL CONDUIT BETWEEN THE UTILITY AC DISCONNECT AND THE POINT OF CONNECTION SHALL HAVE 15.POSITIVE GROUNDED SYSTEMS DC CONDUCTORS COLOR CODED: �� NC ` Y <br /> GROUNDED BUSHINGS AT BOTH ENDS. DC POSITIVE-GREY(OR MARKED GREY),DC NEGATIVE-BLACK(OR MARKED BLACK) <br /> 14. SYSTEM GEC SIZED ACCORDING TO [NEC 690.47], [NEC TABLE 250.661, DC SYSTEM GEC SIZED 16.AC CONDUCTORS>4AWG COLOR CODED OR MARKED: PHASE A OR L1-BLACK,PHASE B OR L2-RED, t� Z PROJECT NUMBER: <br /> ACCORDING TO[NEC 2 ],MINIMUM 8 AWG WHEN INSULATED,6 AWG WHEN EXPOSED DAMAGE. PHASE C OR L3-BLUE,NEUTRAL-WHITE/GRAY 7 10954.:59 <br /> 15. EXPOSED NON-CURRENT CARRYING METAL PARTS OF MODULE FRAMES, EQUIPMENTS, AND 'USE-2 IS NOT INDOOR RATED BUT PV CABLE IS RATED THWN/THWN-2 AND MAY BE USED INSIDE <br /> CONDUCTOR ENCLOSURES SHALL BE GROUNDED IN ACCORDANCE WITH[NEC 250.134]OR[NEC 250.136(A)] "USE-2 IS AVAILABLE AS UV WHITE > <br /> 767549 <br /> REGARDLESS OF VOLTAGE. 17.RIGID CONDUIT,IF INSTALLED,(AND/OR NIPPLES)MUST HAVE A PULL BUSHING TO PROTECT WIRES. .� //�� <br /> 18. IF CONDUIT DETERMINED TO BE RAN THROUGH ATTIC IN FIELD THEN CONDUIT WILL BE EITHER EMT, �0 kF 54072 �G� ' !�'�� ' SHEET NAME: <br /> E L EC CALCS <br /> FMC, OR MC CABLE IF DC CURRENT COMPLYING WITH [NEC 690.31], [NEC 250.118(10)]. DISCONNECTING k C1STY, -06'00 <br /> 0 0 <br /> MEANS SHALL COMPLY WITH[NEC 690.13]AND[NEC 690.151. <br /> 19.CONDUIT RAN THROUGH ATTIC WILL BE AT LEAST 18"BELOW ROOF SURFACE COMPLYING WITH[NEC /OIYALF� <br /> 230.6(4)]AND SECURED NO GREATER THAN 6'APART PER[NEC 330.30(B)]. <br /> REVISION: PAGE NUMBER: <br /> 0 PV6 <br />