gQ GROUp
<br /> MOUNTING: SURFACE (E)PANEL C2 MAIN BUS: 225A MOUNTING: SURFACE (E)PANEL M MAIN BUS: 250A h
<br /> LOCATION: ELECTRICAL ROOM MAIN CB: MLO LOCATION: ELECTRICAL ROOM MAIN CB: 250A `� Iy
<br /> FED FROM: PANEL M AIC RATING: EXISTING FED FROM: MSA AIC RATING: EXISTING Q; ��.`'1
<br /> VOLTAGE: 120/208V,3PH,4W VOLTAGE: 120/208V,3PH,4W
<br /> P B C C B P P B C C B P OPP
<br /> EQ#I VOLT-AMPERES O K I I K O VOLT-AMPERES EQ#/ EQ#/ VOLT-AMPERES O K I I K O VOLT-AMPERES EQ#/
<br /> DESCRIPTION DESCRIPTION DESCRIPTION DESCRIPTION r_
<br /> NOTE PHASEA PHASE13 PHASE[ E R R R R E PHASEA PHASEB PHASE[ NOTE NOTE PHASEA PHASES PHASEC E R R R R E PHASEA PHASES PHASE[ NOTE V
<br /> (E)LOAD 1 1 20 1 2 20 1 (E)LOAD (E)PANEL C1 * 3 200 1 2 SPACE E Ea��
<br /> (E)LOAD 1 20 3 4 20 1 (E)LOAD -- 3 4 SPACE ACE MEP GROUP,INC.
<br /> (E)LOAD 1 20 5 6 20 1 0 (E)LOAD -- 5 6 SPACE 9241 IRVINE BLVD.,SUITE 250
<br /> (E)LOAD 1 20 7 8 20 1 (E)LOAD SPACE 7 8 20 2 1710 (N)NERAC/CU IRVINE,CA 92618 pr, p
<br /> (E)LOAD �� 1 20 9 10 20 1 (E)LOAD SPACE 9 10 - - 1710 -- 951.808.1040 Is`�'
<br /> (E)LOAD �� 1 20 11 12 20 1 (E)EV SPACE 11 12 20 1 180 (N)SERVICE RECEPTACLE acemepgroup.com
<br /> (E)LOAD 3 20 13 14 20 1 (E)LOAD (E)PANEL C2 * 3 100 13 14 SPACE
<br /> -- 20 15 16 20 1 (E)LOAD — - 15 16 SPACE
<br /> -- - 20 17 18 20 1 (E)LOAD — 17 18 SPACE
<br /> (E)LOAD 3 20 19 20 SPACE VA PER PHASE 1710 1710 180 VA PER PHASE
<br /> --- - 20 21 22 15 1 (E)LOAD LARGEST MOTOR LOAD x1.25= 771D 1710 180
<br /> --- - 20 23 24 - 1 (E)LOAD LONG CONTINUOUS LOAD 3600 x1.25= 4500 TOTAL CONNECTED VA 3600 4�a1 WASy�TF
<br /> (E)NER CABINET 1 20 25 26 30 1 (E)LOAD +OTHER= 8910 MEASURED(E)VA 19.8*36U*1.25=8910
<br /> (E)NER QUAD 11 20 Z71 28 - 1 (E)LOAD TOTAL LOAD= 13410 37 AMPS @ 120/208V,3PH,4W
<br /> (E)LOAD 1 20 29 30 ZO 1 (E)LOAD 'ON ABOVE DENOTES CIRCUITRY THAT IS AN EXISTING TO REMAIN LOAD INCLUDED IN INSTANTANEOUS READING CALCULATED TO VA AT 125%OF MEASURED VALUE FOR PANEL FUNCTIONALITY n 22025035 q`r
<br /> VA PER PHASE VA PER PHASE PURPOSES.REFER TO GEAR LOAD CALCULATIONS FOR SERVICE LOAD JUSTIFICATION. 0'Lr'RFC/STEY-Y'�
<br /> LARGEST MOTOR LOAD x1.25= ZONAL LTV
<br /> LONG CONTINUOUS LOAD x1.25= TOTAL CONNECTED VA
<br /> +OTHER=
<br /> TOTAL LOAD= AMPS @
<br /> REVISION
<br /> PROJECT NO:24115
<br /> DATE:05/13/2024
<br /> DRAW BY:
<br /> CHECK BY:
<br /> SCALE:
<br /> PANEL SCHEDULES 1
<br /> �ECTORSEAL
<br /> ASPEN®PUMP KIT WIRING DIAGRAM WIRING MINI-SPLIT SYSTEM SCHEDULE W
<br /> MARK AC CU �y
<br /> Wiring instructions for Aspen Pumps INDOOR&OUTDOOR UNITS 1 1 IL.f`
<br /> Mini Orange Mini Lime Mini Aqua Silent- * Q
<br /> �DA/K/N Univolt MicroV Maxi Orange Maxi Lime Mini White IMPORTANT: The figures shown in the table are for information purpose only.They should be checked and selected � N
<br /> 230 VOLT RA,RA MULTI,QUATERNITY INDOOR UNITS to comply with the local/national codes of regulations. This is also subject to the type of installation and AREA SERVED NER w
<br /> MOdeIs:(FTX509,12,15,18,24,30,36 LVJU)(FTX(N)09,12,15,18,24 NMVJU)(FTK(N)09,12,18,24 NMVIU) 00
<br /> (FTX3036 NVJU)(FTX(I()B09,12,18,24 AXVJ U)(FrxG09,12,15 HVIU)(FVXS09,12,15,1 8 NVJU)(FTXR09,12,18 conductors used. TYPE WALL MOUNTED
<br /> TVJUWN(CTXG09,12,18 DVJUW/S)(CTXS07 LVJU) (FDXS09J2 LVIU)(CDXS15,18,24 LVJU) LU VJ
<br /> "The appropriate voltage range should be checked with label data on the unit.
<br /> MANUFACTURER DAIKIN
<br /> NOTE:DO NOT USE SEPARATE 230 VOLT OUTLET TO POWER PUMP AS THIS IS NOT FAIL SAFE AND MAY CAUSE AN MODEL NUMBER
<br /> Firmly fix the wires with the FTKF18AXVJU r n
<br /> UJ
<br /> OVERFLOW! - INDOOR UNIT lNJ
<br /> 1.Check voltage at evaporator and ensure that pump voltage is correct. %� terminal screws. 0
<br /> MODEL NUMBER
<br /> 2.Make sure all power Is off prior to installing the pump.Connect Red power wire to terminal 2 in RKF18AXVJU
<br /> evaporator.This ensures the pump is powered only when evaporator has power but continues to OUTDOOR UNIT
<br /> he powered in case ofan evaporator fault. �O Outdoor LLl
<br /> 3.Installs amp inline fuse between evaporator and pump as shown to protect pump and unit. - Unit ELECTRICAL DATA 7
<br /> 4.DO NOT BREAK#3 COMMUNICATION WIRE OR GROUND WIRE FROM CONDENSER,THEY Recommend using AWG 14,stranded and L
<br /> MUST RUN TERMINAL TO TERMINAL. T Insulated wire for connections between Indoor 1 2 3— L'L2 uR V/PH/HZ 208-230/60/1 LLl LL I
<br /> 5.Do not connect Line 1(black)from condenser to terminals in evaporator,connect to black power `
<br /> wire of pump and common(gray)wire from overflow switch with a wirenut as shown. and outdoor units. >
<br /> 6.Connect purple(NIC)wire from overflowswitch toterminall in evaporator. l AlCA(A) 14.23 N
<br /> 7.Attach warning label provided to front face of terminal cover in indoor unit. \,-l�1 Local code always supersedes recommendation. M LU
<br /> 1.NOTE:OVERFLOW ALARM WIRE MUST BE CONNECTED TO ENSURETHAT IN CASE OF PUMP FAILURE OR BLOCKAGE IN DISCHARGE
<br /> HOSE,EVAPORATOR WILL SHUTDOWN.CONNECTION OFTHE OVERFLOWALARM CIRCUIT 15 MANDATORYAND FAILURETO DOSO 1, I MOP(A) 20.0 t1J
<br /> WILLINVALIDATE PUMP WARRANTY! 1 Safety devices CONDUIT(EMT) 3/4"
<br /> Indoor 2 in accordance power
<br /> Unit 3 with local and FEEDER(COPPER) 2#12
<br /> Mini Orange supply 60Hz J
<br /> 9 o national codes, pp y
<br /> Maxi Orange Mini Lime Back - i.e.acircuit 208-230V GROUND(COPPER) 1#12
<br /> Maxi Lime Mini Aqua Conduit mounting breaker
<br /> Silent+ 230V AC p DISCONNECT MEANS 20A/2P
<br /> Mini White late
<br /> uniY0lt Firmly fix the wires
<br /> MicroV with the terminal
<br /> REMARKS DETAILS
<br /> screws. Ground —
<br /> LIVE 1 BLACK 1 —
<br /> LIVE RED 3 Conduit
<br /> 2 '�- Lock nut FAN COIL POWER FROM HEAT PUMP YES SHEET TITLE:
<br /> COMMUNICATION WIRE
<br /> 3 s Note:Take care to ensure that all wiring REMARKS 2,3,4,5
<br /> GROUND GREEN
<br /> G between indoor unit and outdoor unit has a NOTES:
<br /> TERMINAL 8 consistent connection.Any splices can cause
<br /> BLOCKIN 1 2 3 G 1.PROVIDE LIQUID TIGHT METALLIC FLEXIBLE CONDUIT AT FINAL TERMINATION.
<br /> EVAPORATOR communication errors. MECHANICAL
<br /> PERMANENTLYLIVE 2.PROVIDE CONTROL WIRING,CONDUIT,ETC.FORA COMPLETE AND FUNCTIONAL
<br /> x NWIREUT m SYSTEM.SYSTEM REQUIRED COMMUNICATION WIRE BETWEEN DEVICES vv
<br /> �' 9 ' Circuit Breaker Rating 3.PROVIDE PERMANENT LABEL FOR THE INDOOR FAN COIL UNIT AND OUTDOOR UNIT. INFORMATION &
<br /> 0 9 9 ' 4.CONTRACTOR SHALL VERIFY MODEL NUMBERS AND MATCH WITH INDOOR UNIT PRIOR
<br /> 1AMP m CAUTION Class 09/12 15A TO INSTALLATION PANELS
<br /> FUSE 5.DISCONNECT SWITCHES/MEANS PROVIDED SHALL NOT CONTAIN FUSES AS LONG AS
<br /> GRAY(COM) Entire PCB replacement required If fuse failure Occurs. THE UPSTREAM BREAKER MATCHES THE MOP.IF NOT MATCHED,CONTRACTOR SHALL
<br /> PUMP 3AMY(COM Class 18/24 20A PROVIDE A FUSED DISCONNECT MATCHING MOP.
<br /> SHEET NUMBER:
<br /> -g—ASP-DAIK-00084 R5 0 0 41-101 9
<br /> E003