Application Installation and Mounting <br /> Genesis strobes are UL 1971-listed for use indoors as ceiling-or All models are intended for indoor wall or ceiling applications <br /> wall-mounted public-mode notification appliances for the hearing only. Horn-strobes mount to any flush North-American 4"square <br /> impaired. Prevailing codes require strobes to be used where ambi- electrical box. <br /> ent noise conditions exceed 105 dBA(87dBA in Canada),where o <br /> occupants use hearing protection, and in areas of public accom- o <br /> modation as defined in the Americans with Disabilities Act(see <br /> application notes—USA). O° o <br /> Combination horn-strobe signals must be installed in accordance O <br /> with guidelines established for strobe devices. <br /> Strobes <br /> Genesis strobes are UL 1971-listed for use indoors as ceiling-or <br /> wall-mounted public-mode notification appliances for the hearing <br /> impaired. Prevailing codes require strobes to be used where ambi- <br /> ent noise conditions exceed specified levels,where occupants <br /> use hearing protection,and in areas of public accommodation. Genesis ceiling horn-strobes simply unlatch and twist to open. <br /> Consult with your Authority Having Jurisdiction for details. This gains access to mounting screws and the selectable candela <br /> switch.The shallow depth of Genesis devices leaves ample room <br /> All Genesis strobes exceed UL synchronization requirements behind the signal for extra wiring. Once installed with the cover in <br /> (within 10 milliseconds other over a two-hour period)when used place, no mounting screws are visible. <br /> with a synchronization source. Synchronization is important in <br /> order to avoid epileptic sensitivity. Edwards recommends that these fire alarm horn-strobes always <br /> be installed in accordance with the latest recognized edition of <br /> NOTE:The flash intensity of some visible signals may not be adequate national and local fire alarm codes. <br /> to alert or waken occupants in the protected area. Research indicates <br /> that the intensity of strobe needed to awaken 90%of sleeping persons Field Configuration <br /> is approximately 100 cd.Edwards recommends that strobes in sleeping Depending on the model, Genesis horn-strobes may be set for 15 <br /> rooms be rated at at least 110 cd. to 95, or 95 to 177 candela output(see ordering information).The <br /> WARNING:These devices will not operate without electrical power.As output setting is changed by simply opening the device and sliding <br /> fires frequently cause power interruptions, further safeguards such as the switch to the desired setting.The horn-strobe does not have <br /> backup power supplies may be required. to be removed to change the output setting.The setting remains <br /> visible through a small window on the front of the device after the <br /> cover is closed. <br /> Horns The horn-strobe comes factory set for high dB output. Low dB <br /> Genesis horn output reaches as high as 99 dB(peak)and output may be selected by cutting a jumper on the circuit board. <br /> features a unique multiple frequency tone that results in excel- This reduces the output by about 5 dB. <br /> lent wall penetration and an unmistakable warning of danger.All <br /> models may be configured for either coded or non-coded signal <br /> circuits.They can also be set for low dB output with a jumper cut <br /> that reduces horn output by about 5 dB. Wiring <br /> The suggested sound pressure level for each signaling zone used Field wiring terminals accommodate#18 to#12 AWG(0.75 mm2 <br /> with alert or alarm signals is at least 15 dB above the average ambient to 2.5 mm2)wiring. Horn/strobes are interconnected with a single <br /> sound level,or 5 dB above the maximum sound level having a duration pair of wires as shown below. <br /> of at least 60 seconds,whichever is greater,measured 5 feet(1.5 m) <br /> above the floor.The average ambient sound level is,A-weighted sound Q <br /> pressure measured over a 24-hour period. <br /> + + To next <br /> Doubling the distance from the signal to the ear will theoretically appliance, <br /> result in a 6 dB reduction of the received sound pressure level. Polarity Shown in or returline <br /> alarm condition H I..I or return to <br /> The actual effect depends on the acoustic properties of materials control <br /> in the space. A 3 dBA difference represents a barely noticeable _ equipment <br /> change in volume. <br /> (D Note:Strobes must have continuous voltage. <br /> Dimensions <br /> 6.8"dia. <br /> (173 mm) <br /> 1.0" <br /> (25 mm) <br /> 0.60"(15 mm) <br /> Page 2 of 4 DATA SHEET S85001-0559 <br /> Not to be used for installation purposes. Issue 9.2 <br />