Laserfiche WebLink
Current Draw <br /> Strobes, Horn-Strobes Horns <br /> Multi-cd Wall Strobes(EG1-VM) Wall or Ceiling Mounted <br /> UL 15 cd* 30 cd* 15/75 cd** 75 cd* 110 cd* Temporal Horns(EG1-HD) <br /> Rating RMS RMS RMS RMS RMS UL High dB Low dB <br /> 16 Vdc 103 141 152 255 311 Rating (RMS) (RMS) <br /> 16 Vfwr 125 179 224 346 392 16 Vdc 26 19 <br /> *EG1-VM multi-cd;**EG1 F-V1575 fixed 15/75 cd 24 Vdc 36 27 <br /> 33 Vdc 41 33 <br /> Typical 15 cd 30 cd 15/75 75 cd 110 cd 16 Vfwr 51 37 <br /> Current RMS RMS RMS RMS RMS 24 Vfwr 69 52 <br /> 16 Vdc 85 127 150 245 285 33 Vfwr 76 70 <br /> 20 Vdc 71 98 123 188 240 <br /> 24 Vdc 59 82 104 152 191 Typical High dB Low dB <br /> 33 Vdc 46 64 84 112 137 Current RMS RMS <br /> 16 Vfwr 119 169 223 332 376 16 Vdc 22 17 <br /> 20 Vfwr 103 143 189 253 331 20 Vdc 24 19 <br /> 24 Vfwr 1 94 129 169 1 218 262 24 Vdc 27 22 <br /> 33 Vfwr 1 87 112 148 1 179 205 33 Vdc 32 26 <br /> 16 Vfwr 34 30 <br /> Wall Temporal Horn-strobes—High dB Setting 20 Vfwr 40 34 <br /> UL 15 30 15/75 75 110 *EG1-HDVM multi-cd 24 Vfwr 45 38 <br /> Rating cd* cd* cd** cd* cd* **EG1 F-HDV1575 fixed 15/75 cd 33 Vfwr 52 47 <br /> R MS RMS RMS RMS RMS <br /> 16 Vdc 129 167 172 281 337 Wall or Ceiling Mounted Horns(EG1-P) <br /> 16 Vfwr 176 230 269 397 443 UL Designation Voltage Range Max.Current, <br /> RMS <br /> Typical 15 cd 30 cd 15/75 75 cd 110 cd Regulated 24 16-33 Vdc 13 mA <br /> Current RMS RMS RMS RMS RMS Vdc <br /> 16 Vdc 102 135 160 246 309 24 fwr 16-33 Vfwr 11 mA <br /> 20 Vdc 88 109 137 193 248 <br /> 24 Vdc 81 94 122 161 203 Typical Current RMS <br /> 33 Vdc 74 72 106 124 154 24 Vdc 10 <br /> 16 Vfwr 144 182 247 352 393 24 Vdc 11 <br /> 20 Vfwr 141 162 220 274 362 31 Vdc 12 <br /> 24 Vfwr 136 152 203 235 282 20 Vfwr 9 <br /> 33 Vfwr 125 144 196 201 232 24 Vfwr 10 <br /> Wall Temporal Horn-strobes—Low dB Setting Current values are shown in mA. <br /> UL 15 30 15/75 75 110 <br /> Rating cd* cd* cd** cd* cd* <br /> RMS RMS RMS RMS RMS <br /> 16 Vdc 122 160 146 274 330 *EG1-HDVM multi-cd <br /> 16 Vfwr 162 216 231 383 429 **EG1 F-HDV1575 fixed 15/75 cd <br /> Typical 15 cd 30 cd 15/75 75 cd 110 cd <br /> Current RMS RMS RMS RMS RMS <br /> 16 Vdc 96 130 158 243 302 <br /> 20 Vdc 79 104 133 189 241 <br /> 24 Vdc 68 88 119 156 197 <br /> 33 Vdc 56 71 100 118 146 <br /> 16 Vfwr 128 180 241 344 389 <br /> 20 Vfwr 118 1 157 213 266 343 <br /> 24 Vfwr 113 1 144 195 230 279 <br /> 33 Vfwr 112 1 137 182 197 226 <br /> Page 3 of 6 DATA SHEET S85001-0573 <br /> Not to be used for installation purposes. Issue 11.1 <br />