Laserfiche WebLink
GENERAL NOTES <br /> 1. CONDUIT: 1/2" MINIMUM, 3/4" MINIMUM FOR ALL <br /> HOMERUNS UNLESS NOTED OTHERWISE. 3/4" FLEX <br /> WITH GROUND WIRE. <br /> 2. CONDUCTORS SHOWN: #12 AWG, STRANDED COPPER, <br /> INSULATION TYPE THHN/THWN, UNLESS OTHERWISE <br /> NOTED. <br /> 3. COLOR CODE CONDUCTORS: IDENTIFY CONDUCTOR <br /> WHICH DO NOT HAVE APPROPRIATELY COLORED <br /> INSULATION WITH COLOR TAPE WHEREVER CONDUCTORS <br /> ARE ACCESSIBLE. IDENTIFY INSULATED GROUND <br /> CONDUCTORS IN ACCORDANCE WITH THE LATEST NEC <br /> (USING TAPE). COLOR CODE AS FOLLOWS: <br /> 208Y 120V 480Y 277V <br /> AO (LEFT BUS IN PNL) BLACK BROWN <br /> BO (CENTER BUS IN PNL) RED ORANGE <br /> CO (RIGHT BUS IN PNL) BLUE YELLOW <br /> NETURAL WHITE GRAY <br /> EQUIPMENT GROUND GREEN GREEN <br /> ISOLATED GROUND GRN/YEL* GRN/YEL* <br /> *GREEN WITH YELLOW TRACER <br /> 4. DYMO LABEL EACH RECEPTACLE, JUNCTION/OUTLET BOX <br /> AND SWITCH WITH CIRCUIT IDENTIFICATION. <br /> 5. POST NEW OR REVISED PANEL SCHEDULES UPON <br /> COMPLETION OF JOB. <br /> 6. UPON COMPLETION OF JOB RETURN REDLINES TO <br /> 0 0 0 0 0U=] ENGINEERING. <br /> 7. THE AREA CLASSIFICATION FOR THIS AREA IS CLASS I, <br /> 1 ° DIVSION 2 UP TO 18" ABOVE FINISHED GRADE WITHIN <br /> 50'-0" OF AIRCRAFT. FOR THE PURPOSE OF THIS <br /> PROJECT, ALL WORK AREAS SHALL BE CONSIDERED <br /> CLASS I, DIVISION 2 UP TO 18" ABOVE FINISHED <br /> GRADE. ALL ELECTRICAL EQUIPMENT AND WIRING <br /> SHALL BE INSTALLED IN ACCORDANCE WITH NEC <br /> 45-218 SMK S 45-218 SMK N ARTICLE 501. <br /> ZONE #: 12, 12:12 ZONE #: 11, 12:11 <br /> s S CONSTRUCTION NOTES <br /> 1 1 ADD NEW SMOKE DETECTORS (QTY. 2) WITH <br /> ADDRESSABLE SMOKE DETECTORS COMPATIBLE WITH <br /> 45-214 BUILDING FACP. INSTALL CONDUIT AND WIRE <br /> AS REQUIRED. <br /> B <br /> B <br /> 0 0 0 0 0 0 <br /> PLAN VIEW �I <br /> SCALE: 1/4 <br /> Timothy C.Eastman-253�- 4� <br /> NICETC��anl�i 4' 2' 0 2' 4' <br /> �� eerr��y5 Level IV <br /> rtTcation Ex Tres:March 01,2025 <br /> aBwlgou w SCALE: 1/4"=1'—O" <br /> PERMIT SUBMITTAL <br /> 03.03.24 PO BOX 1138 <br /> AUBURN,WA 98071 <br /> SEATRONICS 253-939-6060 <br /> FIRE PROTECTION SERMCES JOB NO. BwG x0. <br /> of 9132326 9132326-1E60 <br /> SYM REVISION BY APPROVED DATE SYM REVISION BY APPROVED DATE ACCEPTABILITY DRAWN DATE SUBTITLE CURRENT REVISION SYMBOL DATE <br /> — RECORD DRAWING J#577613-02 HNTB/HAE HNTB/RHM 06,16.08 THIS DESIGN AND/OR CHECKED TOOL SHED POWER PLAN 9132326 0 <br /> OV <br /> A TOOL SHELTER UPGRADE 8334030 BDH TT/WRL 09.29.09 SPECIFICATION IS APPR ED BOE//VG® APPROVED BY DEPT. DATE N IN TITLE SHEET 1 E 60 [A�T <br /> B FIRE ALARM PANEL REPLACEMENT SEA 03.03.24 CHECKED <br /> APPROVED BUILDING 45-218 JOB N0. COMP4NO <br /> 5-218-1E60 <br /> APPROVED ELECTRICAL MASTER EVERETT, WA,DWG No. 45-218-1E60 <br />