FIRE ALARM BATTERY CALCULATIONS <br /> FIRE ALARM REPLACEMENT <br /> PANEL CP QPA-4000)BATTERY CALCULATION <br /> (SECONDARY POWER SOURCE REQUIREMENTS) <br /> PANEL POWER SUPPLY MAX CURRENT=10A TOTAL USED CAPACITY(IN ALARM)=2.01102A(20.11%) <br /> STANDBY CURRENT(AMPS) SECONDARY ALARM CURRENT(AMPS) <br /> QTY PART NO. DESCRIPTION CURRENT DRAW(A) TOTAL(A) CURRENT DRAW(A) TOTAL <br /> PANEL COMPONENTS <br /> 1 IPA-4000 MAIN BOARD Main Board for <br /> Fire Alarm Control Pan IPA-0000el 0.13 0.13 022 0.22 <br /> 1 UD-2000 PFC Series Digital Alan 0.016 0.016 0.023 0.023 <br /> Communicator Transmitter <br /> CIRCUIT SYMBOL QTY PART NO DESCRIPTION CURRENT DRAW(A) TOTAL(A) CURRENT DRAW(A) TOTAL(A) <br /> IntelliNet 2.0 Fire <br /> Subscriber,8 Zone with <br /> CP•1101 AES El 1 7707P-88-ULP-M 7794A AES-InrmlliPro,and 0 0 0 0 <br /> integrated onboard Local <br /> Annunciator plus MCT,Red <br /> Enclosure NOTIFICATION, <br /> 1 ASWP-2475W-FR HORNSTROBE,RED, 0 0 0.168 0.168 <br /> CP•NAC1 WP WALL,WP 75cd <br /> �]F 12 MT-12124-W Multi-Tone Hom,white 0 0 D.035 0.42 <br /> NOTIFICATION, <br /> 1 ASWP-2475W-FR HORNSTROBE,RED, 0 0 0.168 0.16E <br /> CP•NAC2 WP WALL,WP 75cd <br /> �]F 12 MT-12124-W Multi-Tone Hom,white 0 0 0.035 0.42 <br /> NOTIFICATION, <br /> 1 ASWP-2475W-FR HORNSTROBE,RED, 0 0 0.168 0.168 <br /> CP•NAC3 WP WALL,WP 75cd <br /> I 12 MT-12124-W Multi Tone Hom,white 0 0 0.035 0.42 <br /> ❑F 15 PAD100-PSSA Addressable Pull Station 0.0002 0.003 0.0002 0.003 <br /> Single Action <br /> CP•SLC 3 PAD100-SIM Single Input Module 0.00024 0.00072 0.00024 0.00072 <br /> PAD200 PD Photoelectric Smoke <br /> O 6DB 1 wIPAD100SDB Detector with 6'Standard 0.0003 0.0003 0.0003 0.0003 <br /> Base <br /> TOTAL STANDBY(A) 0.15002 TOTAL ALARM(A) 2.01102 <br /> REQUIRED STANDBY TIME=24 HOURS <br /> REQUIRED ALARM TIME=5 MINUTES <br /> SECONDARY STANDBY LOAD(A) 0.15002 24 3.6 <br /> SECONDARY ALARM LOAD(A) 2.01102 0.08 0.17 <br /> STANDBY AND ALARM SUBTOTAL(AMP HOURS) 3.77 <br /> DERATING FACTOR 1.2 <br /> SECONDARY LOAD REQUIREMENTS(AMP HOURS) 4.52 <br /> PROVIDE(2)12V 8AH BATTERIES <br /> 'BATTERY BOX SIZE CAPACITY NOT SPECIFIED.REFER TO MANUFACTURER DOCUMENTATION. <br /> CIRCUIT SETTINGS TOTALS <br /> Starting Calculation Voltage: 20.4 Max.Voltage Drop: 0.17 <br /> CP NACI LUMP SUM REPORT Min.Operational Voltage: 16 End Of Line Voltage: 2023 <br /> Max.Circuit Current(A): 3 Voltage Drop Percent: 0.84% <br /> Wire Resistance(OIkFt): 3.07 Total Circuit Current(A): 0.588 <br /> Circuit Wiring Properties:'V 14/2 FPLPIR(NAC)14 AWG,2 Cond.Solid Copper FPLPIR Analog Unshielded Total Circuit Length(Ft): 47 Spare Current(A): 2.412 <br /> Distance measured using drawn segment lengths with 10.00%additional length calculated Total Circuit Resistance(0): 0.290015 Spare Current(A)Percent: 80.40% <br /> Symbol Part No. Description City. Device Current(A) Total Current(A) <br /> �F MT-12I24-W Multi-Tone Hom,white 12 0.035 0.42 <br /> DEVICE TOTALS <br /> NOTIFICATION, <br /> WP ASWP-2475W-FR HORNSTROBE,RED, 1 0.168 0.16E <br /> WALL,WP 75cd <br /> Calculation Methods: <br /> Total Resistance(0)=Wire Resistance(OIFt)x 2 x Total Circuit Length(Ft) <br /> Total Voltage Drop=Total Resistance(0)x Total Cimult Current(A) <br /> CIRCUIT SETTINGS TOTALS <br /> Starting Calculation Voltage: 20.4 Max.Voltage Drop: 0.84 <br /> CP NAC2 LUMP SUM REPORT Min.Operational Voltage: 16 End Of Line Voltage: 19.56 <br /> Max.Circuit Current(A): 3 Voltage Drop Percent: 4.13% <br /> Wire Resistance(QIkFt): 3.07 Total Circuit Current(A): 0.588 <br /> Circuit Wiring Properdes:'V 1412 FPLPIR(NAC)14 AWG,2 Cond.Solid Copper FPLPIR Analog Unshielded Total Circuit Length(Ft): 233 Spare Current(A): 2.412 <br /> Distance measured using drawn segment lengths with 10.00%additional length calculated Total Circuit Resistance(D): IA33518 Spare Current(A)Percent: 80.40% <br /> Symbol Part No. Description City. Device Current(A) Total Current(A) <br /> �F MT-12I24-W Multi-Tone Hom,while 12 0.035 0.42 <br /> DEVICE TOTALS <br /> NOTIFICATION, <br /> ASWP-2475W-FR HORNSTROBE,RED, 1 0.168 0.11 WP <br /> WALL,WP 75cd <br /> Calculation Methods: <br /> Total Resistance(0)=Wire Resistance(DIFt)x 2 x Total Circuit Length(Ft) <br /> Total Voltage Drop=Total Resistance(Q)x Total Circuit Current(A) <br /> CIRCUIT SETTINGS TOTALS <br /> Starling Calculation Voltage: 20.4 Max.Voltage Drop: 1.2 <br /> CP NAC3 LUMP SUM REPORT Min.Operational Voltage: 16 End Of Line Voltage: 19.2 <br /> Max.Circuit Current(A): 3 Voltage Drop Percent: 5.90% <br /> Wire Resistance(OIkFt): 3.07 Total Circuit Current(A): 0.588 <br /> Circuit Wiring Properdes:'V 1412 FPLPIR(NAC)14 AWG,2 Cond.Solid Copper FPLPIR Analog Unshielded Total Circuit Length(Ft): 333 Spare Current(A): 2.412 <br /> Distance measured using drawn segment lengths with 10.00%additional length calculated Total Circuit Resistance(0): 2.047518 Spare Current(A)Percent: 80.40% <br /> symbol Part No. Description Oty. Device Current(A) Total Current(A) <br /> 1F MT-12124-W Multi-Tone Hom,while 12 0.035 0.42 <br /> DEVICE TOTALS <br /> NOTIFICATION, <br /> WP ASWP-2475W-FR HORNSTROBE,RED, 1 0.168 0.14 <br /> WALL,WP 75cd <br /> Calculation Methods: <br /> Total Resistance I.)=Wire Resistance(OIFt)x 2 x Total Circuit Length(FI) <br /> Total voltage Drop=Total Resistance(Q)x Total Circuit Current(A) <br />