(E,) POTTER IPA-4000
<br /> The Symbol of Protection Fire Alarm Control Panel
<br /> Features
<br /> • 4,064 addresses available on this analog addressable system QygEMe��o
<br /> • Additional system capacity achieved via multi-point SLC modules
<br /> • 1500 software zones
<br /> • NFPA 72 Compliant Smoke Sensitivity Test Built-In •�yOp
<br /> p ty HE
<br /> • System Operates as Class A or Class B for SLC,P-Link and NACs
<br /> • 10 Amp Power Supply,Expandable to 315 amps
<br /> • 6 NACS,Regulated,Rated at 3 Amps each,expandable to 192
<br /> • 4 Input/Output(1/0)Circuits for system flexibility rated at 1 Amp each, ■■■
<br /> ideal for manual release and abort
<br /> • Strobe Synchronization and System Wide Sync for Potter/AMSECO®,
<br /> Gentex®,Cooper Wheelock®and System Sensor®strobes
<br /> • Dedicated Alarm,Supervisory and Trouble Relays
<br /> • 4,000 Event History Buffer
<br /> • Cabinet will house up to 18 AH batteries
<br /> • Optional two line DACT with UD-2000 that can report General,Zone or
<br /> Point Information
<br /> • Built in IP communicator
<br /> • Ethernet Port for Programming and Network Connectivity
<br /> • E-Mail System Status,Reports and Event Information NYC Fire Dept. FM
<br /> • Product includes 5 year warranty Certificate of Approval
<br /> •Fs�:a�
<br /> • UUKL Listed for Smoke Control 6266 APPROVED LISTED
<br /> Description Technical Specifications
<br /> The IPA4000 is an expandable analog/addressable releasing fire alarm Dimensions 18%6"W x 27%6"H x 4/6"D
<br /> system with a total system capacity of 4,064 addresses. Additional
<br /> capacity on the system is achieved using multi-point SLC modules AC Mains 5.0 Amps @ 120 VAC 50/60 HZ
<br /> The control panel utilizes the exclusive Potter protocol that includes a 3.0 Amps @ 240 VAC 50/60 HZ
<br /> complete line of sensors and modules.The system is expandable with a 16 gauge cold rolled steel with removable
<br /> total of thirty-one additional addressable Signaling Line Circuits(SLC) Enclosure locked door with Lexan viewing window
<br /> each with a maximum of 127 devices.Each SLC may be comprised of any Standby Current-130 mA
<br /> combination of smoke sensor,heat detectors or modules and allows for a Alarm Current-220 mA
<br /> total of 50 ohms of impedance and may use any wire compliant with the • 10 Amps power for NACS,I/O,and P-Link
<br /> National Electrical Code(NEC). Battery • 3 Amps per NAC,regulated
<br /> The IPA-4000 has a 10 Amp power supply with six Notification 1 Amp per I/O circuit,regulated
<br /> Appliance Circuits (NACS) and four Input/Output (1/0) circuits. The Battery Charger range 8-55 Ah
<br /> NACS are rated at 3 Amps each and the I/Os are rated at 1 Amp each. Battery Charger voltage 27.3 VDC
<br /> Each output is regulated and power limited. In addition, each output is P-Link maximum current of 1 Amp
<br /> uniquely programmable and may be configured for steady signal,strobe Temperature and 32'to 120'(0°C to 49°C)with a maximum
<br /> synchronization, constant power, door holder power, or releasing. The Humidity Range humidity of 93%non-condensing.
<br /> strobe synchronization includes Potter/AMSECO,Gentex,System Sensor NFPA 12, 12A, 13, 15, 16, 17, 17A,70,
<br /> and Cooper/Wheelock and with the exclusive Quadrasync each output
<br /> may have a unique brand and all strobes will flash together.The I/Os are 72,92,750,and 2001
<br /> designed for inputs such as manual release stations and abort switches that ANSI/UL 864-Local(L),Remote Station
<br /> will not require polling and react nearly instantaneously. (RS),Central Station(CS),Propriety
<br /> (PPU),Auxiliary(AUX).Type of Service:
<br /> The IPA4000 is listed for releasing of fire suppression systems. The Automatic(A),Manual(M),Water flow
<br /> Standards WF Sprinkler Supervisory SS Type of
<br /> software allows cross zones,counting zones,and timers for suppression. ( ) p � P rY( ) Yh
<br /> The system is capable of multiple release outputs across multiple hazards. Signaling:Digital Alarm Communicator
<br /> In addition,the PSN-1000 may be used to extend releasing capability. (DAC),March Time(March),Non Coded
<br /> The NACS may be expanded using the PSN-1000 series intelligent power (NC),Reverse Polarity(Rev Pol),Other
<br /> supplies. Each PSN-1000 adds another 10 Amps of power,2 additional Technologies(OT)
<br /> input circuits and the IPA4000 will support up to 31 power supplies.The IBC(International Building Code)
<br /> system will synchronize the strobes system wide. In addition,the PSN-
<br /> 1000E has space to allow the installation of up to six PAD 100-SLCE SLC
<br /> loop expansion cards.The cards mount on a stacker bracket that allows
<br /> access to all SLC circuit connections.
<br /> Potter Electric Signal Company, LLC St. Louis, MO Phone: 800-325-3936 www.pottersignal.com
<br /> 8830102-REV J 5/23 PAGE 1 OF 5