FIGURE 3.TYPICAL 2-WIRE INITIATING CIRCUIT CONFIGURATION,NFPA STYLE B OR SECURITY SYSTEMS: <br /> NOTE:For UL Listed security installations,the SK-Monitor must be mounted within the control panel enclosure. <br /> TO NEXT FROM PANEL OR <br /> DEVICE + 00000 + PREVIOUS DEVICE <br /> MONITOR <br /> ANY NUMBER OF UL LISTED CONTACT MODULE <br /> CLOSURE DEVICES MAY BE USED.DO NOT MIX CONNECT MODULES TO LISTED COMPATIBLE <br /> FIRE ALARM INTIATING,SUPERVISORY,OR CONTROL PANELS ONLY <br /> SECURITY DEVICES ON THE SAME MODULE. LLLL5555 e o <br /> rn � <br /> TO TI H <br /> T9 T2 (+) <br /> TB T3 <br /> 47K EOL n is SIGNAL LINE CIRCUIT(SLC) <br /> RESISTOR TB 32 VDC MAX. <br /> ' " <br /> ELR-47K THi6 a ars nn�^J TWISTED PAIR <br /> Q❑O t IS RECOMENDED <br /> INITIATING DEVICE CIRCUIT(IDC)-NFPA STYLE B Li <br /> POWER LIMITED:450NA MAX.@ 11 VDC MAX <br /> INSTALL CONTACT CLOSURE DEVICES PER ALL WIRING SHOWN IS SUPERVISED AND POWER LIMITED <br /> MANUFACTURER'S INSTALLATION INSTRUCTIONS. <br /> C0918-00 <br /> FIGURE 4.TYPICAL 4-WIRE FAULT TOLERANT INITIATING CIRCUIT CONFIGURATION,NFPA STYLE D: <br /> TO NEXT () FROM PANEL OR <br /> DEVICE ) PREVIOUS DEVICE <br /> MONITOR <br /> ANY NUMBER OF UL LISTED CONTACT MODULE <br /> CLOSURE DEVICES MAY BE USED.DO NOT MIX CONNECT MODULES TO LISTED COMPATIBLE <br /> FIRE ALARM INTIATING,SUPERVISORY,OR 10 Qo CONTROL PANELS ONLY <br /> SECURITY DEVICES ON THE SAME MODULE. s <br /> TM <br /> TID T1 (-) <br /> To Tn <br /> » (*) <br /> T3 <br /> " SIGNAL LINE CIRCUIT(SLC) <br /> Ts 32 VDC MAX. <br /> re <br /> EOL RESISTOR IS Tea a af" TWISTED PAIR <br /> INTERNALAT �0� �❑ / IS RECOMENDED <br /> TERMINALS 8&9 <br /> INSTALL CONTACT CLOSURE DEVICES PER ALL WIRING SHOWN IS SUPERVISED AND POWER LIMITED <br /> MANUFACTURER'S INSTALLATION INSTRUCTIONS. <br /> C0919-00 <br /> SK-460-013 2 I56-3442-000 <br /> ©2009 Silent Knight <br />