MODULE SPECIFICATIONS QCelIs Q PEAK DUO BLK ML-G10i 395 DESIGN LOCATION AND TEMPERATURES CONDUCTOR SIZE CALCULATIONS
<br /> RATED POWER(STC) 395 W TEMPERATURE DATA SOURCE ASHRAE 2%AVG.HIGH TEMP MICROINVERTER TO MAX.SHORT CIRCUIT CURRRENT(ISC)= 10.9 A AC
<br /> MODULE VOC 45.27 V DC STATE Washington JUNCTION BOX(1) MAX.CURRENT(ISC X1-25)= 13.6 A AC
<br /> MODULE VMP 36.88 V DC CITY EVERETT CONDUCTOR(TC-ER,COPPER(90'C))= 12 AWG BLUE RAVEN
<br /> MODULE IMP 10.71 A DC WEATHER STATION SNOHOMISH COI CONDUCTOR RATING= 30 A
<br /> MODULE ISC 11.1 A DC ASHRAE EXTREME LOW TEMP(-C) -Si AMB.TEMP.AMP.CORRECTION = 1
<br /> VOC CORRECTION .0.27%/'C ASHRAE 2%AVG.HIGH TEMP(-C) 30 ADJUSTED AMP.= 30 > 13.6 1403 N. Research Way
<br /> VMP CORRECTION -0.34 %/'C JUNCTION BOX TO MAX.SHORT CIRCUIT CURRRENT(ISC)= 10.9 A AC Orem, UT 84097
<br /> SERIES FUSE RATING 20 A DC SYSTEM ELECTRICAL SPECIFICATIONS CIR 1 CIR 2 CIR 3 CIR4 CIR 5 CIR6 JUNCTION BOX(2) MAX.CURRENT(ISC X1.25)= 13.6 A AC 8ERAV.4480
<br /> W W W.BLU RAVENSOLAR.COM
<br /> ADJ, MODULE VOC @ ASHRAE LOW TEMP 48.9 V DC NUMBER OF MODULES PER MPPT 9 CONDUCTOR(UF-B,COPPER(60'C))= 10 AWG CONFIDENTIAL-THE INFORMATION
<br /> AD) MODULE VMP @ ASHRAE 2%AVG.HIGH TEMP 32.2 V DC DC POWER RATING PER CIRCUIT(STC) 3555 CONDUCTOR RATING= 30 A HEREIN CONTAINED SHALL NOT BE
<br /> TOTAL MODULE NUMBER 9 CONDUIT FILL DERATE= I USED FOR THE BENEFIT OF ANYONE
<br /> EXCEPT BLUE RAVEN SOLAR NOR
<br /> MICROINVERTER SPECIFICATIONS En phase IQ8+Microinverters STC RATING OF ARRAY 3555 AMB.TEMP,AMP.CORRECTION = 1 SHALL IT BE DISCLOSED IN WHOLE OR
<br /> -7
<br /> IN PART TO OTHERS OUTSIDE
<br /> POWER POINT TRACKING(MPPT)MIN/MAX 30 - 58 V DC AC CURRENT @ MAX POWER POINT(IMP 10.9 ADJUSTED AMP.= 30 > 13.6 RECIPIENTS ORGANIZATION,EXCEPT
<br /> MAXIMUM INPUT VOLTAGE 60 V DC MAX.CURRENT(IMP X 1.25) 13.6125 JUNCTION BOX TO MAX.SHORT CIRCUIT CURRRENT(ISC)= 10.9 A AC IN CONNECTION WITH THE SALE AND
<br /> USE OF THE RESPECTIVE EQUIPMENT,
<br /> MAXIMUM DC SHORT CIRCUIT CURRENT 15 A DC OCPD CURRENT RATING PER CIRCUIT 20 COMBINER BOX(3) MAX.CURRENT(ISC X1.25)= 13.6 A AC WITHOUT THE WRITTEN PERMISSION
<br /> MAXIMUM USABLE DC INPUT POWER 440 W MAX COMB.ARRAY AC CURRENT(IMP) 10.9 CONDUCTOR(UF•B,COPPER(60'C))= 10 AWG OF BLUE RAVEN SOLAR LLC.
<br /> MAXIMUM OUTPUT CURRENT 1.21 A AC MAX.ARRAY AC POWER 261OW AC CONDUCTOR RATING= 30 A
<br /> AC OVERCURRENT PROTECTION 20 A CONDUIT FILL DERATE= 1 NABCEP
<br /> MAXIMUM OUTPUT POWER 290 W AC VOLTAGE RISE CALCULATIONS DIST(FT) COND. JRISE(V) VEND(V) %VRISE AMB.TEMP.AMP.CORRECTION= 1 CERTIFIED
<br /> CEC WEIGHTED EFFICIENCY 97% VRISE SEC. 1(MICRO TO JBOX) 32.4 12 Cu. 1.18 241.18 0.49% ADJUSTED AMP.= 30 > 13.6
<br /> VRISE SEC.2(JBOX TO COMBINER BOX) 45 10 Cu. 1.24 241.24 0.52% COMBINER BOX TO INVERTER RATED AMPS= 10.9 A AC PV INSTALLATION
<br /> AC PHOTOVOLTAIC MODULE MARKING NEC 690,52 VRISE SEC 3 JCOMBINER BOX TO POI 5 10 Cu 0.14 240,14 0.06% MAIN PV OCPD(15) MAX CURRENT(RATED AMPS XL25)= 13.61 A AC PROFESSIONAL
<br /> NOMINAL OPERATING AC VOLTAGE 240 V AC TOTAL VRISE 2.% 242.56 1.07% I CONDUCTOR(THWN•2,COPPER(75-C TERM.))= 10 AWG Scott Gurney
<br /> #PV-011719-015866
<br /> NOMINAL OPERATING AC FREQUENCY 47.68 HZ AC CONDUCTOR RATING= 35 A
<br /> MAXIMUM AC POWER 240 VA AC PHOTOVOLTAIC AC DISCONNECT OUTPUT LABEL NEC 690.54 CONDUIT FILL DERATE= 1 CONTRACTOR:
<br /> MAXIMUM AC CURRENT 1.0 A AC AC OUTPUT CURRENT 10.9 A AC AMB,TEMP,AMP.CORRECTION= 1 BRS FIELD OPS
<br /> MAXIMUM OCPD RATING FOR AC MODULE 20 A AC NOMINAL AC VOLTAGE 240 V AC ADJUSTED AMP.= 35 > 13.6 800-377-4480
<br /> U U
<br /> GROUNDING NOTES WIRING &CONDUIT NOTES Z < O Q
<br /> 1.A GROUNDING ELECTRODE SYSTEM IN ACCORDANCE WITH[NEC 690.47]AND[NEC 250.50-60]SHALL BE 1.ALL CONDUIT SIZES AND TYPES, SHALL BE LISTED FOR ITS PURPOSE AND APPROVED FOR THE SITE Y
<br /> PROVIDED. PER[NEC 690.47],THE GROUNDING ELECTRODE SYSTEM OF AN EXISTING BUILDING MAY BE APPLICATIONS. 0 a ' 00 Y LO
<br /> USED AND BE BONDED AT THE SERVICE ENTRANCE. IF EXISTING SYSTEM IS INACCESSIBLE, OR 2. BOLTED CONNECTION REQUIRED IN DC DISCONNECTS ON THE WHITE GROUNDED CONDUCTOR(USE Q
<br /> INADEQUATE,OR IS ONLY METALLIC WATER PIPING,A SUPPLEMENTAL GROUNDING ELECTRODE WILL BE POLARIS BLOCK OR NEUTRAL BAR). CC 0 C
<br /> USED AT THE INVERTER LOCATION CONSISTING OF A UL LISTED 8 FT GROUND ROD WITH ACORN CLAMP. 3.ANY CONNECTION ABOVE LIVE PARTS MUST BE WATERTIGHT.REDUCING WASHERS DISALLOWED ABOVE G > O CN M
<br /> 2.THE GROUNDING ELECTRODE CONDUCTOR SHALL BE PROTECTED FROM PHYSICAL DAMAGE BETWEEN LIVE PARTS,MEYERS HUBS RECOMMENDED W �
<br /> THE GROUNDING ELECTRODE AND THE PANEL(OR INVERTER) IF SMALLER THAN#6 AWG COPPER WIRE 4.UV RESISTANT CABLE TIES(NOT ZIP TIES)USED FOR PERMANENT WIRE MANAGEMENT OFF THE ROOF O c W LU
<br /> PER [NEC 250.64(B)]. THE GROUNDING ELECTRODE CONDUCTOR WILL BE CONTINUOUS, EXCEPT FOR SURFACE IN ACCORDANCE WITH[NEC 110.2,110.3(A-B)]. LL N N
<br /> SPLICES OR JOINTS AT BUSBARS WITHIN LISTED EQUIPMENT PER[NEC 250.64(C)]. 5. SOLADECK JUNCTION BOXES MOUNTED FLUSH WITH ROOF SURFACE TO BE USED FOR WIRE Z E N
<br /> 3.GROUNDING ELECTRODE CONDUCTORS SHALL BE NO LESS THAN 8 AWG AND NO GREATER THAN 6 AWG MANAGEMENT AND AS FLASHED ROOF PENETRATIONS FOR INTERIOR CONDUIT RUNS.
<br /> COPPER AND BONDED TO THE EXISTING GROUNDING ELECTRODE TO PROVIDE FOR A COMPLETE SYSTEM. 6. ALL PV CABLES AND HOMERUN WIRES BE TYPE USE-2,AND SINGLE-CONDUCTOR CABLE LISTED AND 0
<br /> 4.PV SYSTEM SHALL BE GROUNDED IN ACCORDANCE TO[NEC 250.21],[NEC TABLE 250.122],AND ALL METAL IDENTIFIED AS PV WIRE,TYPE TC-ER,OR EQUIVALENT;ROUTED TO SOURCE CIRCUIT COMBINER BOXES AS IJ J Q- O > W W
<br /> PARTS OR MODULE FRAMES ACCORDING TO[NEC 690.461. REQUIRED. LUC
<br /> 5.MODULE SOURCE CIRCUITS SHALL BE GROUNDED IN ACCORDANCE TO[NEC 690.42]. 7.ALL CONDUCTORS AND OCPD SIZES AND TYPES SPECIFIED ACCORDING TO[NEC 690.8]FOR MULTIPLE G N �
<br /> L
<br /> 6. THE GROUNDING CONNECTION TO A MODULE SHALL BE ARRANGED SUCH THAT THE REMOVAL OF A CONDUCTORS. O a M LJJ
<br /> MODULE DOES NOT INTERRUPT A GROUNDED CONDUCTOR TO ANOTHER MODULE. 8.ALL PV DC CONDUCTORS IN CONDUIT EXPOSED TO SUNLIGHT SHALL BE INSTALLED AT LEAST 7/81,ABOVE
<br /> 7. EACH MODULE WILL BE GROUNDED USING THE SUPPLIED CONNECTION POINTS IDENTIFIED IN THE THE ROOF SURFACE AND DERATED ACCORDING TO [NEC TABLE 310.15 (B)(2)(A)], [NEC TABLE N E
<br /> MANUFACTURER'S INSTALLATION INSTRUCTIONS. 310.15(B)(3)(A)],&[NEC 310.15(13)(3)(C)]. w
<br /> 8.ENCLOSURES SHALL BE PROPERLY PREPARED WITH REMOVAL OF PAINT/FINISH AS APPROPRIATE WHEN 9.EXPOSED ROOF PV DC CONDUCTORS SHALL BE USE-2,90-C RATED,WET AND UV RESISTANT,AND UL = N > V V
<br /> GROUNDING EQUIPMENT WITH TERMINATION GROUNDING LUGS. LISTED RATED FOR 600V, UV RATED SPIRAL WRAP SHALL BE USED TO PROTECT WIRE FROM SHARP C) Y M W Q
<br /> 9.GROUNDING SYSTEM COMPONENTS SHALL BE LISTED FOR THEIR PURPOSE,AND GROUNDING DEVISES EDGES.
<br /> EXPOSED TO THE ELEMENTS SHALL BE RATED FOR DIRECT BURIAL. 10. PHASE AND NEUTRAL CONDUCTORS SHALL BE DUAL RATED THHN/THWN-2 INSULATED, 90°C RATED,
<br /> 10.GROUNDING AND BONDING CONDUCTORS SHALL BE COPPER,SOLID OR STRANDED,AND BARE WHEN WET AND UV RESISTANT,RATED FOR 600V DRAWING BY:
<br /> EXPOSED. 11.MAR WIRE DELTA CONNECTED SYSTEMS HAVE THE PHASE WITH THE HIGHER VOLTAGE TO GROUND OW W 2023 .03 . 1
<br /> 11. EQUIPMENT GROUNDING CONDUCTORS SHALL BE SIZED ACCORDING TO [NEC 690.45] AND BE A MARKED ORANGE OR IDENTIFIED BY OTHER EFFECTIVE MEANS. 1 / PremIumCAD
<br /> ,MINIMUM OF 10 AWG WHEN NOT EXPOSED TO DAMAGE (6 AWG SHALL BE USED WHEN EXPOSED TO 12.ALL SOURCE CIRCUITS SHALL HAVE INDIVIDUAL SOURCE CIRCUIT PROTECTION �` WASE( �'DAMAGE). 13.VOLTAGE DROP LIMITED TO 2%FOR DC CIRCUITS AND 3%FOR AC CIRCUITS � � `' PLOT DATE:
<br /> 12.GROUNDING AND BONDING CONDUCTORS,IF INSULATED,SHALL BE COLOR CODED GREEN(OR MARKED 14. NEGATIVE GROUNDED SYSTEMS DC CONDUCTORS SHALL BE COLOR CODED AS FOLLOWS: DC j
<br /> GREEN IF 4 AWG OR LARGER). POSITIVE-RED(OR MARKED RED),DC NEGATIVE-GREY(OR MARKED GREY)
<br /> 13.ALL CONDUIT BETWEEN THE UTILITY AC DISCONNECT AND THE POINT OF CONNECTION SHALL HAVE 15.POSITIVE GROUNDED SYSTEMS DC CONDUCTORS COLOR CODED: C-0 March 13, 2023
<br /> GROUNDED BUSHINGS AT BOTH ENDS. DC POSITIVE-GREY(OR MARKED GREY),DC NEGATIVE-BLACK(OR MARKED BLACK) i
<br /> 14. SYSTEM GEC SIZED ACCORDING TO [NEC 690.47], [NEC TABLE 250.661, DC SYSTEM GEC SIZED 16.AC CONDUCTORS>4AWG COLOR CODED OR MARKED: PHASE A OR L1-BLACK,PHASE B OR L2-RED, !1�
<br /> 7 PROJECT NUMBER:
<br /> '; -
<br /> ACCORDING TO[NEC 250.166],MINIMUM 8 AWG WHEN INSULATED,6 AWG WHEN EXPOSED TO DAMAGE. PHASE C OR L3-BLUE,NEUTRAL-WHITE/GRAY /j ,
<br /> 15. EXPOSED NON-CURRENT CARRYING METAL PARTS OF MODULE FRAMES, EQUIPMENTS, AND 'USE-2 IS NOT INDOOR RATED BUT PV CABLE IS RATED THWN/THWN-2 AND MAY BE USED INSIDE io 7224 01
<br /> CONDUCTOR ENCLOSURES SHALL BE GROUNDED IN ACCORDANCE WITH[NEC 250.134]OR[NEC 250.136(A)] "USE-2 IS AVAILABLE AS UV WHITE (V
<br /> REGARDLESS OF VOLTAGE. 17.RIGID CONDUIT,IF INSTALLED,(AND/OR NIPPLES)MUST HAVE A PULL BUSHING TO PROTECT WIRES. �e 1154072 FO ' '
<br /> MEAN
<br /> 18. IF CONDUIT DETERMINED TO BE RAN THROUGH ATTIC IN FIELD THEN CONDUIT WILL BE EITHER EMT, �� CIsn �� O 0 O SHEET NAMEFMC, :
<br /> S SHALL COMPLY WITH[NEC R MC CABLE IF DC CURRENT
<br /> 3]OAND[NEC MPLYING ITH51.[NEC 690.31], [NEC 250.118(10)]. DISCONNECTING S`S��NALG
<br /> 19.CONDUIT RAN THROUGH ATTIC WILL BE AT LEAST 18"BELOW ROOF SURFACE COMPLYING WITH[NEC ELEC CALCS
<br /> 230.6(4)]AND SECURED NO GREATER THAN 6'APART PER[NEC 330.30(B)].
<br /> REVISION: PAGE NUMBER:
<br /> 0 PV6
<br />
|