Laserfiche WebLink
• <br /> 3. Please provide a maximum height dimension on the drawings of the 6x6 posts provided to <br /> support the deck. Please note that if the posts exceed the values indicated in 2015 IRC <br /> Table 507.8, these posts are to be engineered and calculations stamped by a professional <br /> engineer in the State of Washington. <br /> 4. It appears that the handrail height of 72"min is being provided. Please confirm or revise <br /> the dimension as required. <br /> 5. A listing from the manufacturer should be provided that specifically shows the preservative- <br /> treated wood structural members are treated in accordance with AWPA U1 for above- <br /> ground use. IBC Section 2304.12 <br /> 6. It appears that the drawings are calling out plywood sheathing in the notes, but the section <br /> detail calls out Trex decking. Please clarify and provide engineering as required or refer to <br /> section IRC 2015 R507.3 and R507.4 for decking requirements. <br /> If you have any questions, please email or call me at (425) 257-7287. Upon submittal of the <br /> drawings, your application will be given priority and plan reviews will recommence. All required <br /> submittals shall be sufficient detail and contain sufficient information to ensure that the proposed <br /> structure will be constructed in compliance with all adopted codes. <br /> Sincerely, <br /> 3 es Bronder, PE <br /> Associate Engineer <br /> Plans Examiner <br /> Page 2 of 2 <br /> CITY OF EVERETT • 3200 Cedar Street • Everett, WA 98201 • (425) 257-8810 • Fax(425) 257-8857 <br />