MCS Typical Point List <br /> Relay Outputs <br /> # Output Name Type Description <br /> M-1 CompM Standard Compressor Start Main <br /> M-2 CompD Standard Compressor Start Delta <br /> M-3 OpenVane Standard Vane open: relay output used to open the compressor guide vane. <br /> M-4 CloseVane Standard Vane closed: relay output used to close the compressor guide vane. <br /> M-5 OilPump Standard Oil pump: Turn ON or OFF <br /> M-6 OilHeater Standard Oil heater: Turn ON or OFF <br /> M-7 HtrLock User Logic Heater Lock (Lock is ON when Compressor is ON) <br /> M-8 Spare X Not Used - Reserved for Expansion <br /> M-9 Spare X Not Used - Reserved for Expansion <br /> Fm <br /> -10 Spare X Not Used - Reserved for Expansion <br /> 1-1 Spare X Not Used - Reserved for Expansion <br /> 1-2 Warning Standard Warning Light: unit is in a safety condition prior to a safety shutdown. <br /> 1-3 Alarm Standard Alarm Light: unit is in a safety shutdown <br /> 1-4 RunStatus User Logic Hardwired or BMS point to notify BMS that the unit is running <br /> 1-5 Spare X Not Used - Reserved for Expansion <br /> 1-6 Spare X Not Used - Reserved for Expansion <br /> 1-7 Spare X Not Used - Reserved for Expansion <br /> 1-8 ChwPump Standard Chilled Water Pump: Turn ON or OFF <br /> 1-9 CondPump Standard Condenser Pump: Turn ON or OFF <br /> 1-10 Spare X Not Used - Reserved for Expansion <br /> 2-1 Spare X Not Used - Reserved for Expansion <br /> 2-2 Spare X Not Used - Reserved for Expansion <br /> 2-3 MtrCooling User Logic Motor Cooling: Turn ON or OFF <br /> 2-4 Spare X Not Used - Reserved for Expansion <br /> 2-5 Spare X Not Used - Reserved for Expansion <br /> 2-6 Spare X Not Used - Reserved for Expansion <br /> 2-7 Spare X Not Used - Reserved for Expansion <br /> 2-8 Spare X Not Used - Reserved for Expansion <br />