Laserfiche WebLink
MCS Typical Point List <br /> Relay Outputs (contined) <br /> # Output Name Type Description <br /> 2-9 Spare X Not Used - Reserved for Expansion <br /> 2-10 Spare X Not Used - Reserved for Expansion <br /> 3-1 Spare X Not Used - Reserved for Expansion <br /> 3-2 Spare X Not Used - Reserved for Expansion <br /> 3-3 HwBmsR/S User Logic Hardwired BMS Run/Stop <br /> 3-4 NtBmsR/S User Logic Virtual Network Point for BMS Run/Stop <br /> 3-5 Spare X Not Used - Reserved for Expansion <br /> 3-6 Spare X Not Used - Reserved for Expansion <br /> 3-7 Spare X Not Used - Reserved for Expansion <br /> 3-8 DisHWRst User Logic Disallow Hardwire Reset <br /> 3-9 DisNetRst User Logic DisNetRst <br /> 3-10 HtrlLock User Logic Heater Lock (Lock is ON when Compressor is ON) <br /> Sensor Inputs <br /> # Input Name Type Description <br /> M-1 ChilWtrin MCST100 Chilled Water In Temperature <br /> M-2 ChilWtrOut MCST100 Chilled Water Leaving Temperature <br /> M-3 Suct Psi MCS--200 Suction Pressure <br /> M-4 DiscPsi MCS-500 Discharge Pressure <br /> M-5 OilFeedPsi MCS-500 Oil Supply Pressure <br /> M-6 OilSumpPsi CARR-5K Oil Sump Pressure <br /> M-7 SuctTmp MCST100 Suction Temperature <br /> M-8 DiscTmp MCST100 Discharge Temperature <br /> M-9 OilFeedTmp MCST100 Oil Supply Temperature <br /> M-10 Spare X Not Used - Reserved for Expansion <br /> M-11 OilSumpTmp CARR-5K Oil Sump Temperature <br /> M-12 Spare X Not Used - Reserved for Expansion <br /> M-13 VaneClosed Digital Vane Closed Switch: ON or OFF <br /> M-14 PhaseLoss Digiital Phase Loss: Phase Imbalance <br />