• Seismic Bracing
<br /> 101CCTM Fig. 980 - Universal Swivel Sway Brace Attachment- 3/8" to 3/4" (UL Listed)
<br /> Size Range: One size fits bracing pipe 1"(25mm)thru 2"(50mm1, B-Line series OPM c us
<br /> 12 gauge(2.6mm) channel, and all structural steel up to 1/4"(31.7mm)thick. LISTED
<br /> co
<br /> N. Material: Steel
<br /> 3, Function: Multi-functional attachment to structure or braced pipe fitting. —
<br /> ;,' Features: This product's design incorporates a concentric attachmenttztoi
<br /> S• opening which is critical to the performance of structural seismic connections. �
<br /> NFPA 13 (2016)9.3,5.8.4 indicates clearly that fastener table load values are ,, 0
<br /> based only on concentric loading. Mounts to any surface angle. Break off bolt
<br /> head assures verification of proper installation. "-,,\
<br /> EE
<br /> Installation: Fig.980 is the structural or transitional attachment component n
<br /> of a longitudinal or lateral sway brace assembly. It is intended to be combined e
<br /> with the'bracing pipe"and TOLCO'braced pipe"attachment, Fig. 1000, 1001,
<br /> 2002, 3000,4L,4LA,4A or approved attachment to pipe to form a complete set Bon
<br /> bracing assembly. NFPA 13 guidelines should be followed. Included
<br /> Mounting Hardware
<br /> To Install: Place the Fig.980 onto the`bracing pipe'.Tighten the set bolt until Is Not Included
<br /> the head breaks off. Attachment can pivot for adjustment to proper brace angle.
<br /> Approvals:—Underwriters Laboratories Listed in the USA(UL)and
<br /> Canada (cUL). Included in our Seismic Engineering Guidelines approved by the lit
<br /> State of California Office of Statewide Health Planning and Development
<br /> (OSHPD). For additional load, spacing and placement information relating to
<br /> OSHPD projects, please refer to our Seismic Engineering Guidelines,
<br /> O PM-0052-13.
<br /> For FM Approval information refer to FM Approved page 61.
<br /> Note: Fig.980 Swivel Attachment and Fig. 1001, 1000, 2002, 4A,4L,4LA, or Ni
<br /> approved attachment to pipe that make up a sway brace system of UL Listed
<br /> attachments and bracing materials which satisfies the requirements of
<br /> Underwriters Laboratories and the National Fire Protection Association(NFPA)
<br /> Finish: Plain, Electro-Galvanized or Stainless Steel. i V.`
<br /> Contact customer service for alternative finishes. \
<br /> Fig.1001 \
<br /> Order By: Figure number and finish. \ Fig.980
<br /> / Fig.980
<br /> Pat.#6,273,372,Pat.#6,517,030,Pat.#6,953,174,
<br /> Pat.#6,708,930,Pat.#7,191,987,Pat.#7,441,730, 71, \\
<br /> Pat.#7,669,806 ' troy
<br /> -7 Brace Fig.980
<br /> Lateral Brace .`.g.. Longitudinal Brace
<br /> Fig.4B
<br /> shown
<br /> Part Mtg.Hdw. Mounting Hole Max.Design Approx.
<br /> Number Size A B D Load(cULus) Wt./100
<br /> in. (mm) in. (mm) in. (mm) in. (mm) in. (mm) lbs. (kg)
<br /> 980-3/8 3/8" (9.5) 51/4" (133.3) 17/8" (47.6) 13/32" (10.3) 2015 (8.96) 149 (67.6)
<br /> 980-1/2* 1/2" (12.7) 51/4" (133.3) 1 J/8" (47.6) 17/32" (13.51 2015 (8.96) 148 (67.1)
<br /> 980-5/8 5/8" (15.9) 51/4" (133.3) 17/8" (47.6) 11/16" (17.5) 2015 (8.96) 147 (66.7)
<br /> 980-3/4 3/4" (19.0) 51/4" (133.3) 17/8" (47.6) t3/15" (20.51 2015 (8.96) 146 (66.2)
<br /> * Standard size.
<br /> Important! -For load information when using Fig.980 with pre-installed or post-installed concrete anchors in
<br /> compliance with NFPA 13 (2016)or ASCE 7-10,including prying factors,see load tables on pages AL-1 thru AL-21.
<br /> Eaton's B-Line series seismic bracing components are designed to be compatible only with other B-Line series bracing components,
<br /> resulting in a listed seismic bracing assembly. Eaton B-Line Division warranty for seismic bracing components will be the warranty
<br /> provided in Eaton B-Line Division standard terms and conditions of sale made available by Eaton, except that, in addition to the other
<br /> exclusions from Eaton B-Line Division warranty, Eaton makes no warranty relating to B-Line series seismic bracing components that are
<br /> combined with products not provided by Eaton.
<br /> All dimensions in charts and on drawings are in inches.Dimensions shown in parentheses are in millimeters unless otherwise specified.
<br /> Eaton 60 B-Line series Fire Protection Solutions