Laserfiche WebLink
III <br /> THERMO Peak-performance <br /> ROOD heating systems Revision 0—February 2019 <br /> 5. ELECTRIC CIRCUIT <br /> SINGLE PHASE, 60HZ <br /> • The electrical connection must be 2-wire cable with ground. <br /> THREE-PHASE, 60HZ <br /> • The electrical connection must be 3-wire cable with ground. <br /> SINGLE PHASE, 60HZ &THREE-PHASE, 60HZ <br /> • The heating elements will be square flange immersion type.They will be low density equipped with high-temperature <br /> nickel-iron-chrome "incoloy" alloy. <br /> • The boiler will be equipped with two limit controls,the first will be adjustable with an automatic reset and the second <br /> will be at a fixed temperature with a manual reset. <br /> • Control circuit ON/OFF switch <br /> • Electrical control circuits will be equipped with fuses to protect the low-voltage circuits. <br /> • Electrical circuits will be equipped with fuses to protect the high-voltage circuits. <br /> • A low water level control with an automatic reset will shut down the boiler when the water level is low and includes <br /> a test button and light indicators. <br /> • The unit's power can be modulated through a solid-state SCR relay from 0 to 100% based on the demand. In <br /> addition, it rotates through the stages to ensure components wear equally. <br /> • A contact to activate an auxiliary boiler as a backup or in dual-energy mode <br /> • Return temperature sensor <br /> • Amperage measurement to detect anomalies and estimate power consumption <br /> • An external contact lowers the heat demand when the building is unoccupied <br /> III - IDENTIFICATION <br /> VOLTMAX SCR (KW)-(VOLTAGE)- (X) PH <br /> Example: <br /> VOLTMAX SCR 77-240-1 PH <br /> VOLTMAX SCR 408-600-3 PH <br /> IV- HEATING ELEMENT <br /> The tank will be made of steel according to CSA B-51-14 standards and will bear a Canadian Registration Number (CRN) <br /> as well as an "H"seal certifying that the tank's construction conforms to the standards of Section IV of the ASME Boiler and <br /> Pressure Vessel code. The tank will have a maximum operating pressure of 160 psi (1103 kPa) and will hold 62 US gal <br /> (235 litres) of water. It will undergo an ASME-compliant 240psi (1655 kPa) hydrostatic test. <br /> The boiler will be installed directly on the ground by means of four(4) seismic resistant holes. It will be equipped with four <br /> (4) 3" NPT M connections, located on the sides of the tank to enable a multi-position installation and facilitate connection. <br /> There are 24 openings to install the square flange elements. The tank will be equipped with a 1 '/4" ball drain valve and will <br /> be shipped from the plant equipped with an ASME compliant safety valve with 150 psi (1034 kPa)trigger point. See section <br /> VI for safety valves of 60 psi (441 kPa) or 125 psi (862 kPa). <br /> THERMO 2000 INC <br /> 500, 9th avenue, Richmond (Quebec) JOB 2H0 <br /> TEL.: 819-826-5613 FAX: 819-826-6370 <br />