Laserfiche WebLink
Confidential Draft Hydrogen Fueling Station Performance Validation Testing—DO NOT CITE OR QUOTE <br /> HyStEP Summary Test Report for Linde—Mobile Refueler Hydrogen Station Updated Revision Date:September 27,2023 <br /> V. General Fault Detection Tests Summary <br /> Test Comment <br /> Pass Fail <br /> E-stop ® ❑ Confirmed hydrogen station and dispenser shutdown. <br /> E-Customer Stop ® ❑ Confirmed fueling terminated. <br /> CHSS Capacity Range. ® ❑ Before initiating fueling,TV was set to 45 L and 250 L on hystep. Dispenser <br /> Note:Performed in communication terminated fueling after connection pulse with code"25". <br /> Ambient Temperature. ® ❑ Before initiating fueling,station operator applied offset to ambient <br /> temperature sensors in the PLC so that Tamb=-41.5 C and 51.5 C.Fueling did <br /> not begin with codes'temp_too_low'and'temp_too_high'respectively. <br /> Minimum Fuel Delivery Temperature. ® ❑ During fueling,station operator applied offset to fuel temperature sensors in <br /> the PLC,causing Tfuel=-43C.Dispenser terminated fueling immediately. <br /> Ambient Temperature Limits for Station operator simulates ambient temperature inputs in the PLC before <br /> Ambient Fueling- Tamb>Tfuel+5C; ® ❑ start:Tamb>Tfuel+5C;Tamb<Tfuel—5C <br /> Tamb<Tfuel—5C <br /> Fuel Delivery Temperature Tolerance During fueling,station operator simulates ambient temperature inputs in the <br /> for Ambient Fueling-Tfuel<Tamb— ® ❑ PLC: Tfuel<Tamb—5C;Tfuel>Tamb+5C <br /> 5C;Tfuel>Tamb+5C <br /> Maximum CHSS Gas Temperature. ® ❑ During fueling after 30 sec main fueling time,MT was set to 360 K on hystep. <br /> Dispenser terminated immediately with code"19"'vehicle tempt.out of <br /> boundary'. <br /> Minimum CHSS Initial Pressure. NOT APPLICABLE Non-Communication fills:station only fills in <br /> Note:Performed only in communication ❑ ❑ communication mode,for more details see executive summary#10. <br /> (station does not fuel in non- <br /> communication mode)when pressure is H70 Communication passed.Before initiating fueling MP was set to 1.5 MPa <br /> <2 MPa. ® ❑ on hystep. Dispenser terminated fill after connection pulse. <br /> Maximum CHSS Initial Pressure. ® ❑ In communication mode with CHSS pressure of 38.0 MPa,dispenser did not <br /> start with code'CHSS pressure over limit". <br /> Maximum CHSS Pressure(with ® ❑ During fueling after 30 sec main fueling time, MP was set to 44 MPa on <br /> communication). hystep.Dispenser terminated immediately with code'12'"J2601 POS criteria <br /> met". <br /> Maximum State of Charge(SOC). ® ❑ During fueling after 30 sec main fueling time,MT was set to 243 K on hystep <br /> Note:Performed in Communication @ P=30 MPa. Dispenser terminated immediately with code"12"J2601 POS <br /> criteria met. <br /> (MT value was calculated using MT=PO*3.76+20.7-5) <br /> Lower pressure corridor limit Confirmed during an actual test(Max.CHSS Gas Tempt)when dispenser <br /> Run in communication or non- ® ❑ stopped due to a lower pressure corridor limit fault,with code"18""lower <br /> communication mode. limit boundary failure". <br /> Upper pressure corridor limit Confirmed during an actual test(Max.CHSS Gas Tempt)when dispenser <br /> Run in communication or non- ® ❑ stopped due to an upper pressure corridor limit fault,with code"upper limit <br /> communication mode. boundary failure". <br /> 12 <br /> Page 21 of 38 <br />