NOTES
<br />A. ROMAC, FORD, OR MUELLER SERVICE SADDLE WITH C.C. THREAD TO BE USED ON ALL MAINS 4" DIA. AND
<br />LARGER. ALL NEW TAPS ON EXISTING WATER MAINS SHALL BE DONE BY THE CITY OF EVERETT UTILITIES
<br />DEPARTMENT AT THE DEVELOPERS OR CONTRACTORS EXPENSE
<br />B. CORPORATION STOP:
<br />3/4" OR 1" - FORD FB600, OR CITY APPROVED EQUAL
<br />J I K C. FORD SERIES LAO-2-33S NL FOR 3/4" OR LA02-44S-NL FOR 1" BEND FITTING (1/8 OR 1/4) FOR FLARE x FLARE
<br />COPPER. PHYSICAL BENDS IN POLYETHYLENE PIPE ARE NOTALLOWED. USE APPROPRIATE 1/4 OR 1/8 BENDS PER
<br />NOTE B ABOVE.
<br />D. USE MUELLER H-15073 N INSTA-TITE FITTING OR CITY APPROVED EQUAL FOR IPS-PE PLASTIC PIPE X FEMALE
<br />COPPER FLARE THREAD.
<br />z Q E. RESIDENTIAL SERVICE:
<br />�2
<br />N K
<br />r m > 1. PROVIDE 3/4" OR 1" POLYETHYLENE TUBING MEETING THE FOLLOWING REQUIREMENTS:
<br />O a. AWWA C901.
<br />w `- Z b. ASTM D2239, SIDR 7, FOR ID IRON PIPE SIZE (IPS).
<br />Oc. ASTM 3350 - PE3608 OR PE4710.
<br />z
<br />N 2. PROVIDE A #10 AWG, SINGLE STRAND COPPER WIRE WITH BLUE TYPE OF OR USE COATING SUITABLE FOR
<br />DIRECT BURY.
<br />C H a. WRAP WIRE AROUND TUBING, ONE WRAP PER FT, ITS ENTIRE LENGTH.
<br />b. SECURE ONE END AROUND THE SADDLE BOLT BETWEEN TWO NUTS AND EXPOSE A MINIMUM OF 18" OF THE
<br />OTHER END IN THE METER BOX.
<br />-_ F. NON-RESIDENTIAL SERVICE:
<br />A
<br />1. PROVIDE 3/4" OR 1" TYPE K COPPER TUBING MEETING ASTM B88, ANSI/NSF 61 & APPLICABLE IAPMO
<br />STANDARDS.
<br />G. USE 1/4 OR 1/8 BEND BRASS ST BEND WITH MUELLER H-15426 N INSTA-TITE FITTING OR CITY APPROVED EQUAL
<br />E F G J a FOR IPS-PE PLASTIC PIPE X MALE IRON PIPE THREAD.
<br />m >
<br />D a a H. 3/4" METER SETTER SHALL BE "A.Y. MCDONALD" 62-212WWDD33-15 OR APPROVED EQUAL.
<br />1" METER SETTER SHALL BE "A.Y. MCDONALD" 62-415WWDD44-15 OR CITY APPROVED EQUAL.
<br />B
<br />o
<br />I. METERS SHALL BE SUPPLIED AND INSTALLED BY CITY UTILITIES DEPARTMENT AT THE DEVELOPERS OR
<br />o
<br />CONTRACTOR EXPENSE.
<br />o
<br />J. PROVIDE METER BOX BODY MANUFACTURED BY "RAVEN PRODUCTS, FOR A 3/4" USE MODEL RMB-11-18-12,
<br />3
<br />3/4" OR 1" METERED WATER SERVICE FOR A 1" USE MODEL RMB-15-27-12", MOUSEHOLES CUT, WITH AASTHO H-20 RATED DI FLUSH SOLID COVER
<br />Z
<br />LID OR EQUAL.
<br />°
<br />>
<br />0
<br />0
<br />K. PLACE SAWDUST IN METER BOX AROUND PIPE TO TOP OF METER TO PREVENT FREEZING.
<br />V
<br />21
<br />CITY OF EVERETT
<br />0!$:PUBLIC
<br />z
<br />WORKS DEPARTMENT
<br />0
<br />Ciry Enineer eRtioHEMFaTIer CADAnLaWLHELM D
<br />wWRB 09/8/2017
<br />N
<br />ao
<br />DARODRAwIN5"a
<br />METERED WATER SERVICES
<br />E i
<br />3/4" & 1" 501
<br />1 METERED WATER SERVICES 314" & 4"
<br />C4.2 N.T.S. (CITY OF EVERETT STD. 501)
<br />NOTES
<br />1. CONNECTION TO SEWER MAIN PER SEC. 7 OF
<br />STANDARD SPECIFICATIONS AND SPECIAL
<br />PROVISIONS AND STANDARD DRAWING 602.
<br />2. INSTALL 6" MINIMUM PIPE SIZE IN RIGHT OF
<br />5' MAXIMUM IF
<br />WAY.
<br />GREATER THAN 5'
<br />3. INSTALL 6" CLEAN OUT PER STANDARD.
<br />INSTALL ADDITIONAL
<br />DRAWING 604.
<br />CLEAN OUT REQUIRED
<br />CLEAN OUT AT
<br />AT ALL ANGLE POINTS
<br />BUILDING CONNECTION.
<br />OVER 45'
<br />4. PRIVATE SIDE SEWER PIPE DIAMETER:
<br />4" MINIMUM FOR SINGLE FAMILY
<br />6" MINIMUM FOR ALL OTHER USES.
<br />GENERAL NOTES
<br />1. SEE SECTION 7 OF STANDARD
<br />SPECIFICATIONS FOR ROADS; BRIDGE AND
<br />MUNICIPAL CONSTRUCTION WSDOT/APWA
<br />AND CITY SPECIAL PROVISIONS SECTION
<br />BUILDING
<br />7-18 FOR DETAILS AND REQUIREMENTS ON
<br />LATERALS.
<br />0
<br />2. ALL CLEAN OUT'S ON PRIVATE PROPERTY
<br />-'
<br />ARE TO BE ADJUSTED TO GRADE IF IN PAVED
<br />AREAS PER STANDARD DRAWING 604.
<br />3. CLEAN OUT'S ARE TO BE CONSTRUCTED
<br />WITH WYES OR SANITARY "T"S (SWEEPS).
<br />TYPICAL
<br />INSTALL
<br />STRAIGHT "T"S ARE NOT PERMITTED.
<br />CLEAN OUT
<br />AT BLDG.
<br />4. ALLOWABLE GRADES ARE 2% (1/4"/FT)
<br />ALTERNATES
<br />CONNECTION
<br />MINIMUM TO 100% (FT/FT) MAXIMUM.
<br />4
<br />5. SEWER MUST BE STRAIGHT BETWEEN
<br />ANGLE POINTS, CHANGES IN LINE OR
<br />3
<br />GRADE SHALL BE MADE WITH APPROVED
<br />FITTINGS.
<br />o
<br />PROPERTY
<br />o
<br />4
<br />V.-Iz
<br />LINE
<br />6. NORMALLY ONLY ONE(1) CONNECTION TO
<br />-
<br />2
<br />THE SEWER MAIN PER BLDG. IS ALLOWED.
<br />3
<br />TWO (2) DIFFERENT LAYOUTS ARE SHOWN
<br />F
<br />1
<br />FOR ILLUSTRATIVE PURPOSES ONLY!
<br />z
<br />0
<br />>
<br />0
<br />SEWER MAIN
<br />0
<br />CITY OF EVERETT
<br />.6
<br />OLT
<br />0�
<br />PUBLIC WORKS DEPARTMENT
<br />o
<br />Ciry Engineer Section Mager CAD Manager......
<br />aw. B urre ev
<br />TITLERYAN SASS DAVID VOIGTnaPAUL WILHELM WRB 12/30/2016
<br />a o
<br />TYPICAL SIDE SEWER LAYOUTS 601
<br />q
<br />via
<br />3 TYPICAL SIDE SEWER LAYOUTS
<br />�,C4.2 N.T.S. (CITY OF EVERETT STD. 60 1)
<br />NOTES
<br />1. W = MAXIMUM WIDTH OF TRENCH. FOR PIPES 15"
<br />OR LESS IN DIA W=40". FOR PIPES 18" OR GREATER
<br />W=1.5 X I.D. + 18". PIPE MUST BE CENTERED IN
<br />TRENCH.
<br />2. ALTERNATE SLOPING TRENCH WALL TO MEET
<br />EXISTING 7
<br />PAVEMENT
<br />6
<br />8 10
<br />O.S.H.A. REQUIREMENTS (NO SLOPES STEEPER THAN
<br />1:1 EXCEPT FOR ROCK).
<br />6"
<br />18"MIN
<br />3. SUITABLE NATIVE MATERIAL OR IMPORTED GRAVEL
<br />BORROW AS DIRECTED. COMPACT TO 90%
<br />MAXIMUM DENSITY.
<br />- _
<br />'`-`TT =I I
<br />4. FOUNDATION GRAVEL IF REQUIRED BY THE
<br />ENGINEER TO REPLACE UNSUITABLE MATERIAL.
<br />I
<br />II I =III-
<br />SHALL BE FOUNDATION MATERIAL CLASS A, B OR AS
<br />APPROVED BY THE ENGINEER.
<br />-
<br />5. FOR ADDITIONAL COMPACTION INFORMATION SEE
<br />/
<br />STANDARD DWG 615.
<br />1
<br />I'I}
<br />2
<br />6. IF DIRECTED BYTHE ENGINEER THE TOP THREE TO
<br />FIVE FEET OF BACKFILL SHALL BE IMPORTED GRAVEL
<br />2 1
<br />U--
<br />BORROW OR SUITABLE NATIVE MATERIAL
<br />-
<br />COMPACTED TO 95% MAXIMUM DENSITY.
<br />7. SEE CITY OF EVERETT STANDARD DWG 326 FOR
<br />_
<br />-
<br />PAVEMENT PATCH DETAILS.
<br />8. VERTICALTRENCH WALLS WITH SHORING TO
<br />CONFORM TO O.S.H.A. REGULATIONS.
<br />8
<br />III-
<br />9. SUBGRADE OR GROUND SURFACE IN NON -PAVED
<br />AREAS.
<br />10. EXCAVATED NATIVE MATERIAL OR STOCKPILED
<br />BACKFILL MATERIAL.
<br />3
<br />3
<br />11. FOR ALL TRENCHING TRANSVERSE TO THE ROADWAY
<br />a
<br />Lu LO
<br />BACKFILL ABOVE THE PIPE ZONE SHALL BE
<br />1
<br />z 1O
<br />O
<br />CONTROLLED DENSITY FILL. SEE SECTION 3-9.6 &
<br />o
<br />N
<br />3-20.1 OF THESE STANDARDS.
<br />-
<br />LU
<br />12. FOR UTILITY CUTS SUCH AS GAS, TELEPHONE,
<br />w
<br />POWER, AND CABLE TV LONGITUDINAL TO THE
<br />o
<br />-
<br />ROADWAY, BACKFILL SHALL BE CONTROLLED
<br />-
<br />-
<br />DENSITY FILL. SEE SECTION 3-9.5 OF THESE
<br />0
<br />0
<br />-
<br />-
<br />STANDARDS.
<br />u
<br />o
<br />_
<br />CITY OF EVERETT
<br />_-
<br />-
<br />-III-
<br />4
<br />PUBLIC WORKS DEPARTMENT
<br />N
<br />W (SEE NOTE1)
<br />`--
<br />WO a
<br />u a,
<br />Clty EEngineer a ger ger a urre ev
<br />RYAN SASS DAVID VOIGT PAPA" WILHELM wESH 06/23/2017
<br />STANDARD DRAwiruc"a.
<br />so
<br />s;
<br />EQ�
<br />TYPICAL TRENCH SECTION 614
<br />5 TYPICAL TRENCH SECTION
<br />�C4.2 N.T.S. (CITY OF EVERETT STD. 601)
<br />NW 1/4, SEC. 11 T.28 N, R.4 E, W.M.
<br />CITY OFEVERETT, WASHINGTON
<br />PARTS
<br />A. HYDRANTS AND ALL MATERIALS SHALL CONFORM TO
<br />AWWA STANDARDS AND SHALL BE OF STANDARD
<br />MANUFACTURE (MUELLER SUPER CENTURION #250,
<br />WATEROUS PACER #WB67, OR CITY APPROVED
<br />EQUAL).
<br />B. 5-1/4" VALVE MINIMUM.
<br />C. 1-1/4" OPERATING NUT AND CAP NUT FOR 2-1/2"
<br />B
<br />MAX RAKE, 1/4" PER FT
<br />PORTS.
<br />FROM GROUND LEVEL
<br />D. NATIONAL STANDARD THREAD ON 2-1/2" PORTS.
<br />E. 5" STORZ FITTING WITH NATIONAL STANDARD THREAD
<br />ON THE 4-1/2" PORT.
<br />C
<br />F. IF HYDRANT RISES THROUGH CONCRETE, USE
<br />E
<br />EXPANSION STRIP AROUND HYDRANT BARREL, PER STD
<br />PLAN 509. IN ADDITION, INSTALLATION OF THE
<br />HYDRANT ON PRIVATE PROPERTY SHALL EQUAL OR
<br />EXCEED THE STANDARDS FOR INSTALLATION OF
<br />TRAFFIC SAFETY
<br />PUBLIC FIRE HYDRANTS IN THE CITY OF EVERETT.
<br />FEATURE BREAK -OFF
<br />VALVE BOX AND EXTENSION PER
<br />I
<br />FLANGE, BREAK OFF
<br />STANDARD DRAWING 505
<br />G. PROVIDE FOR VEHICULAR TRAFFIC PROTECTION WHEN
<br />NUTS AND BOLTS
<br />NECESSARY PER STANDARD DRAWING 508.
<br />�\� j\
<br />H. STEAMER PORT TO BE FACING STREET OR ROADWAY
<br />FOR FIRE ENGINE ACCESS.
<br />1/2 CU YD WASHED ROCK
<br />F J
<br />I. BREAK -OFF FLANGE TO BE 2"-4" ABOVE GROUND
<br />1-1/2" DRAIN ROCK
<br />DUCTILE IRON TEE
<br />LEVEL.
<br />RETAINER
<br />(MJxMJxFL) OR
<br />GLANDS
<br />TAPPING TEE (FL)
<br />J. INSTALL CONCRETE PAD AROUND HYDRANT IN
<br />�@
<br />UNPAVED, SOD AND ASPHALT AREAS PER STANDARD
<br />DRAWING 508.
<br />\/
<br />�
<br />-
<br />K. HYDRANT CONNECTION PIPE TO BE DUCTILE IRON
<br />6 6
<br />CLASS 52, ANY INTERMEDIATE JOINTS TO BE MJ WITH
<br />O /O
<br />RETAINER GLANDS, OR FIELD LOCK GASKETS.
<br />��/��\
<br />\
<br />K
<br />L. FIRE HYDRANTS SHALL BE PAINTED WITH TWO COATS
<br />OF HIGH GLOSS CATERPILLAR YELLOW, LUXLITE
<br />3
<br />#6100-516 OR "RUST-OLEUM" #7448 OR APPROVED
<br />z
<br />12" x 12" x 4"
<br />CONIC BLOCK
<br />GATE VALVE
<br />EQUAL. THE PORT CAPS WILL BE PAINTED BLACK.
<br />o
<br />(MJ x FL)
<br />M. PROVIDE FOR A MINIMUM OF 3' CLEAR ZONE AROUND
<br />>
<br />0
<br />6 MIL PLASTIC SHEETING WRAP
<br />HYDRANT.
<br />0
<br />I
<br />UNDISTURBED EARTH
<br />4CITY OF EVERETT
<br />=
<br />PUBLIC WORKS DEPARTMENT
<br />a
<br />WO m
<br />Clty Engineer ager ger a n V Current Rev Date
<br />RYAN SASS R HEFTI� "PAUL WILHELM W WRB 5/9/2018
<br />NA"DARDDRA
<br />o
<br />i" N.
<br />FIRE HYDRANT
<br />v
<br />INSTALLATION 507
<br />x
<br />az
<br />25�
<br />48", 54" OR 60"
<br />zx
<br />2�
<br />00
<br />�Ln
<br />`V STEPS PER
<br />STD 606A
<br />LADDER PER
<br />STD 606 -
<br />Q
<br />2
<br />24:1 -
<br />SLOPE
<br />MORTAR
<br />FILLET
<br />'I I�
<br />611
<br />ci L(.
<br />SEPARATE BASE N
<br />rocT IKI PI orF
<br />• 0
<br />Know what's below.
<br />Cal before you dig.
<br />2 FIRE HYDRA NT INSTALLATION
<br />C4.2 N.T.S. (CITY OF EVERETT STD. 507)
<br />MANHOLE FRAME AND COVER
<br />PER STANDARD DRAWING 610 OR 611.
<br />CIRCULAR ADJUSTMENT SECTION TYPICAL
<br />STEPS IN MH ENTRY AREA SHOULD EXTEND
<br />ONLY 3" MAX FROM WALL (USED AS
<br />HANDHOLDS NOT STEPS) SEE STD 609.
<br />ECCENTRIC CONE SECTION
<br />RUBBER GASKET AT JOINTS TYPICAL
<br />PRECAST RISER SECTIONS
<br />6" CLR TYPICAL
<br />FIELD -FORMED CHANNEL AND SHELF
<br />(SEE NOTE 8)
<br />REINFORCING STEEL TYPICAL
<br />��GRAVEL BACKFILL FOR PIPE
<br />ZONE BEDDING. COMPACT 95%
<br />I OF STD DENSITY.
<br />INTEGRAL BASE
<br />PRECAST WITH RISER
<br />NOTES
<br />1. MANHOLES TO BE CONSTRUCTED IN ACCORDANCE WITH AASHTO M-199 (ASTM C 478)
<br />UNLESS OTHERWISE SHOWN ON PLANS OR NOTED IN STANDARD SPECIFICATIONS.
<br />2. ALL REINFORCED CAST IN PLACE CONCRETE SHALL BE CLASS 4000. NON -REINFORCED
<br />CONCRETE IN CHANNEL AND SHELF SHALL BE 7 SACK MIX SAND AND CEMENT GROUT. ALL
<br />PRECAST CONCRETE SHALL BE CLASS 4000.
<br />3. PRECAST BASES SHALL BE FURNISHED WITH CUTOUTS FOR KNOCKOUTS. KNOCKOUTS SHALL
<br />HAVE A WALLTHICKNESS OR 2" MINIMUM.
<br />4. ALL BASE REINFORCING STEEL SHALL HAVE A MINIMUM YIELD STRENGTH OF 60,000 PSI
<br />AND BE PLACED IN THE UPPER HALF OF THE BASE WITH 1" MINIMUM CLEARANCE.
<br />5. KNOCKOUT OR CUTOUT HOLE SIZE IS EQUAL TO PIPE OUTER DIAMETER PLUS MANHOLE
<br />WALL THICKNESS.
<br />6. MANHOLE DIA. DEPENDS ON: SIZE, LOCATION AND NUMBER OF PENETRATIONS FOR PIPES.
<br />MANHOLE DESIGN AND SIZE SHALL BE APPROVED AND WARRANTED BY THE MANHOLE
<br />SUPPLIER.
<br />7. FOR HEIGHTS OVER 25' MANHOLE BASE SLAB SHALL BE DESIGNED BY A STRUCTURAL
<br />ENGINEER.
<br />8. CONCRETE CHANNEL AND SHELF SHALL BE FIELD -FORMED EXCEPT WHERE APPROVED IN
<br />ADVANCE BY CITY.
<br />NOTE: KNOCKOUTS SHALL HAVE A WALL THICKNESS OF 2" MINIMUM TO 2.5" MAXIMUM.
<br />MANHOLE DIMENSIONS TABLE
<br />DIA
<br />WALL
<br />THICKNESS
<br />BASE
<br />THICKNESS
<br />MAXIMUM
<br />KNOCKOUT
<br />SIZE
<br />MINIMUM
<br />DISTANCE BWT
<br />KNOCKOUTS
<br />BASE REINFORCING STEEL
<br />INZ FT IN EACH DIRECTION
<br />SEPARATE BASE
<br />INTEGRAL BASE
<br />48"
<br />4"
<br />6"
<br />36"
<br />8"
<br />0.23
<br />0.15
<br />54"
<br />4.5"
<br />8"
<br />42"
<br />8"
<br />0.19
<br />0.19
<br />60"
<br />5"
<br />8"
<br />48"
<br />8"
<br />0.25
<br />0.25
<br />"0" RING
<br />WATER STOP
<br />12"
<br />GRAVEL
<br />BACKFILL FOR
<br />PIPE ZONE
<br />1.0 o
<br />BEDDING
<br />SEPARATE BASE PRECAST
<br />(___4 TYPICAL MANHOLE 48'; 54" & 60"
<br />C4.2 N.T.S. (CITY OF EVERETT STD. 605)
<br />UTILITY CONFLICT NOTE.•
<br />CAUTION.
<br />THE CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFYING THE LOCATION,
<br />DIMENSION, AND DEPTH OF ALL EXISTING UTILITIES WHETHER SHOWN ON THESE
<br />PLANS OR NOT, BY POTHOLING THE UTILITIES AND SURVEYING THE HORIZONTAL
<br />AND VERTICAL LOCATION PRIOR TO CONSTRUCTION. THIS AND THEN SHALL
<br />INCLUDE CALLING UTILITY LOCATE ® 1-800-424-5555 POTHOLING ALL OF THE
<br />EXISTING UTILITIES AT LOCATIONS OF NEW UTILITY CROSSINGS TO PHYSICALLY
<br />VERIFY WHETHER OR NOT CONFLICTS EXIST. LOCATIONS OF SAID UTILITIES AS
<br />SHOWN ON THESE PLANS ARE BASED UPON THE UNVERIFIED PUBLIC
<br />INFORMATION AND ARE SUBJECT TO VARIATION. IF CONFLICTS SHOULD OCCUR,
<br />THE CONTRACTOR SHALL CONSULT WITH INSIGHT ENGINEERING COMPANY TO
<br />RESOLVE ALL PROBLEMS PRIOR TO PROCEEDING WITH CONSTRUCTION.
<br />4:CITY OF EVERETT
<br />77- PUBLIC WORKS DEPARTMENT
<br />�ryE�gi�eer �o�M �a er DMa�a r a ReyDa
<br />c"`RTITLE YAN SASS DAVI DaVOIGT PAUL WILHELM El-
<br />v3/3v/2vi
<br />TYPE 1 MANHOLE 605
<br />48 , 54 & 60
<br />SEWER MAIN SYSTEM GENRAL NOTES:
<br />CONSTRUCTION OF ALL SANITARY SEWER MAINS, SIDE
<br />SEWERS (LATERALS) - WHETHER SIDE SEWERS ARE BY GRAVITY, BY FORCE
<br />MAIN, OR PRESSURE SEWER -AND RELATED FACILITIES, INCLUDING BUT
<br />NOT LIMITED TO SEWER LIFT STATIONS, TELEMETRY FACILITIES AND
<br />APPURTENANCES WILL BE UNDER THE SUPERVISION OF THE CITY AND
<br />SHALL BE IN COMPLIANCE WITH ALL ORDINANCES AND CURRENT
<br />STANDARDS OF THE CITY OF EVERETT, WASHINGTON STATE DEPARTMENT
<br />OF ECOLOGY CRITERIA FOR SEWAGE WORKS DESIGN (ORANGE BOOK), OR
<br />THE UNIFIED PLUMBING CODE AS APPLICABLE.
<br />SEWER MAIN EXTENSIONS WILL BE REQUIRED WHEN THE PROPERTY DOES
<br />NOT FRONT ON A SEWER MAIN OR WHEN THE EXISTING SEWER MAIN IS
<br />NOT ADEQUATE FOR THE INCREASED USE PROPOSED. THE MINIMUM
<br />EXTENSION SHALL BE TO A POINT AT LEAST 5 FEET INSIDE THE
<br />PROLONGATION OF THE PROPERTY LINE.
<br />EACH SIDE SEWER SHALL SERVE ONLY ONE BUILDING AND ONE PARCEL
<br />(ONE CONNECTION FROM LOT TO MAIN) PER SECTION 6-8.3 AND EMC
<br />14.08.170.
<br />ALL NEW SEWER CONNECTIONS SHALL COMPLY WITH BACKWATER VALVE
<br />REQUIREMENTS IN EMC 14.08.180 B. 1.
<br />ALL PIPE INSTALLED SHALL BE STRUCTURALLY SOUND FOR THE DESIGN
<br />DEPTH.
<br />REQUIREMENTS FOR NEW PROPOSED LIFT (PUMP) STATIONS TO BE
<br />DEDICATED TO THE CITY ARE PROVIDED IN SECTION 6-5.1 AND PER THE
<br />CITY'S CURRENT LIFT STATION STANDARDS AS ESTABLISHED BY THE CITY'S
<br />MAINTENANCE DIVISION/SEWER UTILITY. LIFT STATIONS ARE DEFINED AS
<br />SEWAGE PUMPING SYSTEMS THAT SERVE MULTIPLE RESIDENTIAL LOTS OR
<br />A NON-RESIDENTIAL DEVELOPMENT GENERATING SIGNIFICANT SEWAGE
<br />VOLUME. LIFT STATIONS MUST BE DEMONSTRATED TO BE NEEDED, COST
<br />EFFECTIVE FOR THE CITY TO OWN AND MAINTAIN BASED ON SEWER RATES
<br />AND LIFECYCLE 0&M COSTS, MEET THE MAINTENANCE DIVISION
<br />STANDARDS, AND BE PERMITTED AND APPROVED SOLELY AT THE INTEREST
<br />OF THE DEPARTMENT. GRINDER PUMP INSTALLATION FOR INDIVIDUAL
<br />PARCELS MAY BE ALLOWED UNDER SEPARATE REVIEW PER SECTION 6-5.2.
<br />ALL REQUESTS FOR INSPECTIONS AND FOR WITNESSING ACCEPTANCE
<br />TESTS SHALL BE SCHEDULED WITH THE PUBLIC WORKS INSPECTOR AT
<br />LEAST 24 HOURS IN ADVANCE. FAILURE TO GIVE ADEQUATE ADVANCE
<br />NOTICE MAY RESULT IN DELAYS TO THE CONTRACTOR FOR REQUIRED
<br />INSPECTIONS.
<br />WATER MAIN SYSTEM GENERAL NOTES:
<br />ALL CONSTRUCTION OF WATER MAINS AND RELATED APPURTENANCES SHALL
<br />CONFORM TO THESE STANDARDS, APPLICABLE AMERICAN WATER WORKS ASSOCIATION
<br />(AWWA) SPECIFICATIONS AND APPLICABLE SECTIONS OF DIVISION 7 OF THE
<br />WSDOT/APWA STANDARD SPECIFICATIONS. THE GENERAL REQUIREMENTS OF AWWA
<br />AND THE WSDOT/APWA STANDARD SPECIFICATIONS SHALL APPLY UNLESS THEY ARE
<br />INCONSISTENT WITH ANY OF THE PROVISIONS OF THIS PARTICULAR SECTION.
<br />SHOULD INCONSISTENCIES OCCUR, THESE STANDARDS SHALL HAVE PRECEDENCE.
<br />ALL REFERENCE TO STANDARD SPECIFICATIONS SUCH AS AWWA OR WSDOT/APWA
<br />SHALL REQUIRE THE USE OF THE LATEST EDITION.
<br />ANY PUBLIC WATER SYSTEM OR ANY PLUMBING IN A RESIDENTIAL OR
<br />NONRESIDENTIAL FACILITY PROVIDING WATER FOR HUMAN CONSUMPTION WHICH IS
<br />CONNECTED TO A PUBLIC WATER SYSTEM SHALL BE LEAD FREE. WITH RESPECT TO
<br />SOLDERS AND FLUX, "LEAD FREE" SHALL MEAN NO MORE THAN 0.2% LEAD. WITH
<br />RESPECT TO PIPES AND PIPE FITTINGS, "LEAD FREE" SHALL MEAN NO MORE
<br />THAN 8% LEAD.
<br />WATER MAIN EXTENSIONS WILL BE REQUIRED WHEN THE PROPERTY DOES NOT
<br />FRONT ON A WATER MAIN OR WHEN THE EXISTING WATER MAIN IS NOT ADEQUATE
<br />TO MEET THE MINIMUM FIRE FLOW REQUIREMENT. THE NEW WATER MAIN EXTENSION
<br />SHALL EXTENDED ACROSS THE PROPOSALS FULL FRONTAGE AND SHALL BE
<br />EXTENDED THROUGH AND TO THE LIMITS OF THE PROPERTY BEING DEVELOPED FOR
<br />SYSTEM CIRCULATION OR FUTURE DEVELOPMENT AS DETERMINED BY THE PUBLIC
<br />WORKS DEPARTMENT. THE MINIMUM SIZE WATER MAIN SHALL BE DETERMINED BY
<br />THE PUBLIC WORKS DEPARTMENT AND SHALL BE AT LEAST 8" INCHES IN DIAMETER
<br />UNLESS OTHERWISE APPROVED BY THE PUBLIC WORKS DIRECTOR OR HIS DESIGNEE.
<br />WATER MAIN EXTENSIONS OR REPLACEMENTS AND/OR NEW FIRE HYDRANT
<br />INSTALLATIONS MAY ALSO BE REQUIRED PER THE REQUIREMENTS OF THE CITY FIRE
<br />MARSHAL. FIRE HYDRANT INSTALLATIONS ARE NOT ALLOWED ON WATER MAINS THAT
<br />DO NOT MEET THE MINIMUM FIRE FLOW REQUIREMENTS OF THE AREA. IN A SINGLE
<br />FAMILY / DUPLEX NEIGHBORHOOD, THE FIRE FLOW IN THE MAIN MUST BE A
<br />MINIMUM OF 1000 GPM BEFORE THE INSTALLATION OF A FIRE HYDRANT IS
<br />ALLOWED.
<br />A FIRE HYDRANT IS REQUIRED WITHIN 350 FEET OF EVERY STRUCTURE FOR SINGLE
<br />FAMILY HOMES AND DUPLEXES AS WELL AS NEW SUBDIVISIONS AND SHORT
<br />SUBDIVISION FOR SINGLE FAMILY HOMES AND DUPLEXES.
<br />FOR ALL OTHER BUILDINGS FROM TRIPLEXES TO COMMERCIAL USES, A FIRE
<br />HYDRANT IS REQUIRED WITHIN 200 FEET, BUT NOT CLOSER THAN 50 FEET TO ANY
<br />STRUCTURE (MEASURED DISTANCE TO BE ALONG ROUTE TO BE TRAVELED BY FIRE
<br />EQUIPMENT).
<br />WATER METERS ARE REQUIRED FOR ALL NEW SERVICES INCLUDING DOMESTIC,
<br />IRRIGATION AND FIRE SERVICES.
<br />AFTER THE INSTALLATION OF ANY WATER SERVICE BY THE PUBLIC WORKS
<br />DEPARTMENT, THE PROPERTY OWNER SHALL BE HELD RESPONSIBLE FOR, AND MAY
<br />BE CHARGED FOR, ANY AND ALL DAMAGES TO THE SERVICE LINE, METER SETTER,
<br />METER AND METER BOXES/VAULT OR ANY OTHER APPURTENANCES UNTIL
<br />COMPLETION OF CONSTRUCTION AND/OR THE STRUCTURE IS APPROVED FOR
<br />OCCUPANCY.
<br />ALL WATER MAINS ON PRIVATE PROPERTY THAT ARE LOOPED BACK TO THE PUBLIC
<br />RIGHT-OF-WAY OR ARE OPEN TO THE GENERAL PUBLIC SYSTEM SHALL BE
<br />INSTALLED IN EASEMENTS, GRANTED TO THE CITY, AND SHALL BE MAINTAINED BY
<br />THE CITY. (SEE SECTION 5-8.6 FOR MAIN LOOPING REQUIREMENTS.)
<br />THE MINIMUM WATER MAIN EASEMENT WIDTH SHALL BE 15 FEET, 5 FEET ON ONE
<br />SIDE AND 10 FEET ON THE OTHER SIDE AND SHALL BE EXCLUSIVE FOR THE WATER
<br />MAIN AND APPURTENANCES. THE LEGAL DESCRIPTION SHALL BE PREPARED BY A
<br />SURVEYOR LICENSED TO PRACTICE IN THE STATE OF WASHINGTON. THE EASEMENT
<br />SHALL BE REVIEWED AND APPROVED BY THE PUBLIC WORKS DIRECTOR OR HIS
<br />DESIGNEE PRIOR TO ACCEPTANCE.
<br />DUE TO THE COMPLEXITIES OF MANY WATER MAINS AND THEIR INTERFACE WITH
<br />OTHER UNDERGROUND STRUCTURES, ALL WATER MAIN CONSTRUCTION SHALL BE
<br />STAKED TO ENSURE PLACEMENT WITHIN DESIGNATED EASEMENTS. ANY DEVIATION
<br />FROM THIS REQUIREMENT MUST BE APPROVED BY THE PUBLIC WORKS DIRECTOR OR
<br />HIS DESIGNEE.
<br />UPON COMPLETION OF THE INSTALLATION OF THE WATER SYSTEM, THE ORIGINAL
<br />SIGNED DRAWING OF THE WATER CONSTRUCTION PLAN MUST BE EDITED TO REFLECT
<br />ACTUAL CONSTRUCTED CONDITIONS (RECORD DRAWINGS) BY THE
<br />DEVELOPER/CONTRACTOR, CERTIFIED AS SUCH BY HIM AND TURNED INTO THE CITY.
<br />A RECORD DRAWING PRINT SHALL BE SUBMITTED FOR CHECKING BY THE CITY
<br />INSPECTOR AND PUBLIC WORKS DEPARTMENT PRIOR TO SUBMITTING THE REVISED
<br />ORIGINALS. THE WATER RECORD DRAWING SHALL BE SUBMITTED WITHIN 14 DAYS OF
<br />THE PUBLIC WATER MAIN BECOMING LIVE.
<br />THE INSTALLATION OF ALL WATER MAINS AND APPURTENANCES SHALL BE IN
<br />ACCORDANCE WITH THE CONSTRUCTION PLANS AS APPROVED BY THE PUBLIC WORKS
<br />DIRECTOR OR HIS DESIGNEE FOR THE PROJECT. ANY DEVIATIONS OR CHANGES ARE
<br />TO BE APPROVED BY PUBLIC WORKS DIRECTOR OR HIS DESIGNEE BEFORE THE
<br />CHANGES ARE INCORPORATED INTO THE WORK.
<br />ALL MATERIALS SHALL BE NEW AND UNDAMAGED. UNLESS OTHERWISE APPROVED BY
<br />THE PUBLIC WORKS DIRECTOR OR HIS DESIGNEE, THE SAME MANUFACTURER OF
<br />EACH ITEM SHALL BE USED THROUGHOUT THE WORK. CONTRACTORS SHALL FURNISH
<br />A WATER TIGHT PLUG OF THE APPROPRIATE SIZE WHICH SHALL BE INSTALLED IN
<br />THE END OF THE WATER MAIN ANYTIME WORK IS DELAYED OR STOPPED.
<br />WA TER MAINS YSTEM REQ UIRED NOTES:
<br />A. NO CONNECTION TO THE EXISTING MAINS WILL BE ALLOWED EXCEPT BY
<br />MEANS OF AN APPROVED BACKFLOW PREVENTION DEVICE PRIOR TO
<br />SATISFACTORY FLUSHING, TESTING, DISINFECTION, AND RECEIPT OF
<br />SATISFACTORY BACTERIOLOGICAL TEST RESULTS.
<br />B. CONNECTIONS TO AND TAPS ON EXISTING MAINS WILL BE MADE BY THE
<br />PUBLIC WORKS DEPARTMENT AT THE DEVELOPER'S EXPENSE. THE PUBLIC
<br />WORKS DEPARTMENT SHALL BE GIVEN AT LEAST 5 BUSINESS DAYS NOTICE
<br />FOR EACH CONNECTION. THE PUBLIC WORKS DEPARTMENT SHALL THEREAFTER
<br />DETERMINE THE DATE AND TIME AT WHICH THE CONNECTION SHALL BE MADE.
<br />C. ALL WORK AND MATERIALS MUST CONFORM TO CITY OF EVERETT
<br />STANDARDS.
<br />D. A PRE -CONSTRUCTION MEETING SHALL BE HELD WITH THE CITY PRIOR TO
<br />THE START OF CONSTRUCTION. THE CITY OF EVERETT PUBLIC WORKS
<br />CONSTRUCTION DIVISION MUST BE NOTIFIED AT LEAST 24 HOURS PRIOR TO
<br />COMMENCEMENT OF CONSTRUCTION.
<br />E. THE DEVELOPER OR THE DEVELOPER'S AUTHORIZED AGENT SHALL NOTIFY
<br />THE PUBLIC WORKS DEPARTMENT OF A PERSON WHO CAN BE CONTACTED
<br />REGARDING PROBLEMS DURING CONSTRUCTION ON A 24 HOUR BASIS.
<br />F. MAINTAIN A MINIMUM OF 10 FEET HORIZONTAL AND 18 INCHES VERTICAL
<br />SEPARATION BETWEEN POTABLE AND NON -POTABLE CONVEYANCE SYSTEMS.
<br />G. ALL CITY OF EVERETT VALVES SHALL BE OPERATED BY PUBLIC WORKS
<br />DEPARTMENT PERSONNEL ONLY. ALL VALVES, NEW AND EXISTING, SHALL BE
<br />ACCESSIBLE AT ALL TIMES.
<br />SEWER MAIN SYSTEM CONSTRUCTION PLAN NOTES:
<br />THE INSTALLATION OF ALL EXTENSIONS TO THE SANITARY SEWER SYSTEM SHALL BE DONE
<br />PER PLANS WHICH HAVE BEEN APPROVED BY THE CITY ENGINEER.
<br />SANITARY SEWER PLANS ARE TO BE SEPARATE FROM OTHER UTILITY PLANS, BUT ALL
<br />OTHER UTILITIES ARE TO BE SHOWN, WITH SANITARY SEWER PORTIONS HIGHLIGHTED.
<br />UNLESS APPROVED OTHERWISE, PLANS SHOULD BE PREPARED ON 22 INCH BY 34 INCH
<br />PLAN/PROFILE TYPE SHEETS AND SHALL SHOW BOTH PLAN AND PROFILE VIEWS. OTHER
<br />UTILITIES ARE TO BE SHOWN IN PROFILE VIEW AND IN PLAN VIEW.
<br />THE MINIMUM ALLOWABLE SCALE SHALL BE 1 INCH = 40 FEET, ON SMALL PROJECTS, IT
<br />SHALL BE EXPECTED THAT THE SCALE WILL BE ENLARGED TO ADEQUATELY UTILIZE THE
<br />FULL PLAN SHEET.
<br />PROVIDE NOTES ON PLANS THAT REFER TO SPECIFIC CITY STANDARDS FOR SUCH THINGS
<br />AS MANHOLES, DROP CONNECTIONS, SIDE SEWERS, ETC.
<br />PLANS SHALL SHOW INVERT ELEVATIONS OF THE MAIN AT THE OUTLET AND ALL INLETS
<br />OF EACH MANHOLE, SLOPE OF THE MAIN AND SURFACE ELEVATIONS OF THE MANHOLE
<br />LID. IN THE PROFILE VIEW, THE FINISH GROUND ELEVATION OVER THE PIPE SHALL BE
<br />SHOWN AS WELL AS CROSSINGS OF OTHER EXISTING OR PROPOSED UTILITIES. STATIONING
<br />OF SIDE SEWERS FROM THE DOWNHILL MANHOLE IS REQUIRED.
<br />IN ALL CASES WHERE A NEW SEWER LINE IS TO BE LOCATED IN AN EASEMENT, THE
<br />EASEMENT IS TO BE SHOWN WITH MEASUREMENT INFORMATION TO ACCURATELY FIELD
<br />SURVEY AND STAKE LOCATION PRIOR TO CONSTRUCTING THE PIPE LINE.
<br />UPON COMPLETION OF CONSTRUCTION, THE ORIGINAL OF THE PLAN SHALL BE AS -BUILT
<br />BY THE DEVELOPER AND CERTIFIED AS AS -BUILT BY HIM AND TURNED INTO THE PUBLIC
<br />WORKS DEPARTMENT WITH PROPERLY EXECUTED EASEMENT DEEDS AS APPLICABLE FOR
<br />THE PROJECT.
<br />SEWER MAIN SYSTEMREQUIRED NOTES:
<br />THE FOLLOWING STANDARD NOTES ARE REQUIRED ON ALL SANITARY SEWER PLANS:
<br />A. ALL WORK AND MATERIALS SHALL CONFORM TO THE CITY OF EVERETT STANDARDS
<br />AND WSDOT/APWA STANDARD SPECIFICATIONS.
<br />B. NO PART OF THE SANITARY SEWER SYSTEM SHALL BE COVERED, CONCEALED OR PUT
<br />INTO USE UNTIL IT HAS BEEN TESTED, INSPECTED, AND APPROVED BY THE CITY
<br />INSPECTOR.
<br />C. APPROXIMATE LOCATIONS OF EXISTING UTILITIES HAVE BEEN OBTAINED FROM AVAILABLE
<br />RECORDS AND ARE SHOWN FOR CONVENIENCE. THE CONTRACTOR SHALL BE RESPONSIBLE
<br />FOR VERIFICATION OF LOCATIONS AND TO AVOID DAMAGE TO ANY ADDITIONAL UTILITIES
<br />NOT SHOWN. IF CONFLICTS WITH EXISTING UTILITIES ARISE DURING CONSTRUCTION, THE
<br />CONTRACTOR SHALL NOTIFY THE PUBLIC WORKS INSPECTOR AND ANY CHANGES REQUIRED
<br />SHALL BE APPROVED BY THE CITY ENGINEER PRIOR TO COMMENCEMENT OF RELATED
<br />CONSTRUCTION ON THE PROJECT.
<br />D. ALL SEWER MAIN EXTENSIONS WITHIN THE PUBLIC RIGHT-OF-WAY OR IN EASEMENTS
<br />MUST BE STAKED BY SURVEY FOR LINE AND GRADE PRIOR TO STARTING CONSTRUCTION.
<br />WATER MAIN SYSTEM CONSTR UCTION PLAN NOTES:
<br />A. WATER PLANS ARE TO BE SEPARATE FROM OTHERS AND SHALL HAVE WATER MAINS
<br />HIGHLIGHTED AND INDICATE LOCATIONS OF OTHER UTILITIES.
<br />B. PLANS MUST SHOW EASEMENTS WHERE MAINS ARE ON PRIVATE PROPERTY AND ALL
<br />HYDRANTS, METERS, AND OTHER APPURTENANCES MUST BE WITHIN THE EASEMENTS.
<br />EASEMENTS MUST MEET THE REQUIREMENTS OF SECTION 5-1.
<br />C. EASEMENTS MUST BE EXECUTED AT COMPLETION OF CONSTRUCTION. EASEMENTS FOR
<br />WATER MAINS MUST BE 15 FEET WIDE WITH THE CENTER OF THE WATER MAIN 5 FEET FROM
<br />ONE OF THE SIDES LEAVING 10 FEET ON THE OTHER. ACCESS TO EASEMENTS FOR
<br />MAINTENANCE MUST REMAIN OPEN. STRUCTURES, FENCES, AND SHRUBS ARE NOT TO BE
<br />PLANTED ON EASEMENTS.
<br />D. SHOW ELEVATIONS OF SEWER MAINS, WATER MAINS AND STORM DRAINS WHERE THEY
<br />CROSS EACH OTHER.
<br />E POTABLE WATER MAINS SHALL MAINTAIN A MINIMUM OF 10 FEET HORIZONTAL CLEARANCE
<br />AND 18 INCHES VERTICAL SEPARATION ABOVE NON -POTABLE UTILITIES (INCLUDING SEWER,
<br />STORM DRAINAGE AND IRRIGATION) WHENEVER POSSIBLE. IF SITE CONDITIONS DO NOT ALLOW
<br />SUCH MINIMUM SEPARATIONS, PIPELINES MAY BE LOCATED CLOSER TO EACH OTHER
<br />PROVIDED ADDITIONAL PRECAUTIONS ARE IDENTIFIED AND INSTITUTED TO ASSURE PROTECTION
<br />OF THE POTABLE LINE. NO OTHER UTILITIES, POTABLE OR NON -POTABLE, SHALL BE WITHIN 5
<br />FEET HORIZONTAL AND 12 INCHES VERTICAL FROM THE WATER MAIN.
<br />F. ALL INSTALLED HYDRANTS MUST BE COVERED BY A BURLAP BAG OR OTHER SUITABLE
<br />COVERING UNTIL ACCEPTED BY THE PUBLIC WORKS DIRECTOR OR HIS DESIGNEE AND PLACED
<br />IN SERVICE.
<br />G. A WASHINGTON STATE APPROVED BACKFLOW PREVENTION DEVICE IS REQUIRED FOR ALL
<br />IRRIGATION SYSTEMS.
<br />H. ALL ENVIRONMENTAL SENSITIVE AREAS SHALL BE SHOWN ON THE WATER SYSTEM
<br />CONSTRUCTION PLANS.
<br />I. PLANS MUST SHOW REQUIRED THRUST RESTRAINT PER SECTION 5-13 OF THESE
<br />STANDARDS.
<br />J. ALL WATER CONSTRUCTION PLANS SHALL BE PREPARED, STAMPED AND SIGNED BY AN
<br />ENGINEER REGISTERED IN THE STATE OF WASHINGTON.
<br />
|