NOTES <br />A. ROMAC, FORD, OR MUELLER SERVICE SADDLE WITH C.C. THREAD TO BE USED ON ALL MAINS 4" DIA. AND <br />LARGER. ALL NEW TAPS ON EXISTING WATER MAINS SHALL BE DONE BY THE CITY OF EVERETT UTILITIES <br />DEPARTMENT AT THE DEVELOPERS OR CONTRACTORS EXPENSE <br />B. CORPORATION STOP: <br />3/4" OR 1" - FORD FB600, OR CITY APPROVED EQUAL <br />J I K C. FORD SERIES LAO-2-33S NL FOR 3/4" OR LA02-44S-NL FOR 1" BEND FITTING (1/8 OR 1/4) FOR FLARE x FLARE <br />COPPER. PHYSICAL BENDS IN POLYETHYLENE PIPE ARE NOTALLOWED. USE APPROPRIATE 1/4 OR 1/8 BENDS PER <br />NOTE B ABOVE. <br />D. USE MUELLER H-15073 N INSTA-TITE FITTING OR CITY APPROVED EQUAL FOR IPS-PE PLASTIC PIPE X FEMALE <br />COPPER FLARE THREAD. <br />z Q E. RESIDENTIAL SERVICE: <br />�2 <br />N K <br />r m > 1. PROVIDE 3/4" OR 1" POLYETHYLENE TUBING MEETING THE FOLLOWING REQUIREMENTS: <br />O a. AWWA C901. <br />w `- Z b. ASTM D2239, SIDR 7, FOR ID IRON PIPE SIZE (IPS). <br />Oc. ASTM 3350 - PE3608 OR PE4710. <br />z <br />N 2. PROVIDE A #10 AWG, SINGLE STRAND COPPER WIRE WITH BLUE TYPE OF OR USE COATING SUITABLE FOR <br />DIRECT BURY. <br />C H a. WRAP WIRE AROUND TUBING, ONE WRAP PER FT, ITS ENTIRE LENGTH. <br />b. SECURE ONE END AROUND THE SADDLE BOLT BETWEEN TWO NUTS AND EXPOSE A MINIMUM OF 18" OF THE <br />OTHER END IN THE METER BOX. <br />-_ F. NON-RESIDENTIAL SERVICE: <br />A <br />1. PROVIDE 3/4" OR 1" TYPE K COPPER TUBING MEETING ASTM B88, ANSI/NSF 61 & APPLICABLE IAPMO <br />STANDARDS. <br />G. USE 1/4 OR 1/8 BEND BRASS ST BEND WITH MUELLER H-15426 N INSTA-TITE FITTING OR CITY APPROVED EQUAL <br />E F G J a FOR IPS-PE PLASTIC PIPE X MALE IRON PIPE THREAD. <br />m > <br />D a a H. 3/4" METER SETTER SHALL BE "A.Y. MCDONALD" 62-212WWDD33-15 OR APPROVED EQUAL. <br />1" METER SETTER SHALL BE "A.Y. MCDONALD" 62-415WWDD44-15 OR CITY APPROVED EQUAL. <br />B <br />o <br />I. METERS SHALL BE SUPPLIED AND INSTALLED BY CITY UTILITIES DEPARTMENT AT THE DEVELOPERS OR <br />o <br />CONTRACTOR EXPENSE. <br />o <br />J. PROVIDE METER BOX BODY MANUFACTURED BY "RAVEN PRODUCTS, FOR A 3/4" USE MODEL RMB-11-18-12, <br />3 <br />3/4" OR 1" METERED WATER SERVICE FOR A 1" USE MODEL RMB-15-27-12", MOUSEHOLES CUT, WITH AASTHO H-20 RATED DI FLUSH SOLID COVER <br />Z <br />LID OR EQUAL. <br />° <br />> <br />0 <br />0 <br />K. PLACE SAWDUST IN METER BOX AROUND PIPE TO TOP OF METER TO PREVENT FREEZING. <br />V <br />21 <br />CITY OF EVERETT <br />0!$:PUBLIC <br />z <br />WORKS DEPARTMENT <br />0 <br />Ciry Enineer eRtioHEMFaTIer CADAnLaWLHELM D <br />wWRB 09/8/2017 <br />N <br />ao <br />DARODRAwIN5"a <br />METERED WATER SERVICES <br />E i <br />3/4" & 1" 501 <br />1 METERED WATER SERVICES 314" & 4" <br />C4.2 N.T.S. (CITY OF EVERETT STD. 501) <br />NOTES <br />1. CONNECTION TO SEWER MAIN PER SEC. 7 OF <br />STANDARD SPECIFICATIONS AND SPECIAL <br />PROVISIONS AND STANDARD DRAWING 602. <br />2. INSTALL 6" MINIMUM PIPE SIZE IN RIGHT OF <br />5' MAXIMUM IF <br />WAY. <br />GREATER THAN 5' <br />3. INSTALL 6" CLEAN OUT PER STANDARD. <br />INSTALL ADDITIONAL <br />DRAWING 604. <br />CLEAN OUT REQUIRED <br />CLEAN OUT AT <br />AT ALL ANGLE POINTS <br />BUILDING CONNECTION. <br />OVER 45' <br />4. PRIVATE SIDE SEWER PIPE DIAMETER: <br />4" MINIMUM FOR SINGLE FAMILY <br />6" MINIMUM FOR ALL OTHER USES. <br />GENERAL NOTES <br />1. SEE SECTION 7 OF STANDARD <br />SPECIFICATIONS FOR ROADS; BRIDGE AND <br />MUNICIPAL CONSTRUCTION WSDOT/APWA <br />AND CITY SPECIAL PROVISIONS SECTION <br />BUILDING <br />7-18 FOR DETAILS AND REQUIREMENTS ON <br />LATERALS. <br />0 <br />2. ALL CLEAN OUT'S ON PRIVATE PROPERTY <br />-' <br />ARE TO BE ADJUSTED TO GRADE IF IN PAVED <br />AREAS PER STANDARD DRAWING 604. <br />3. CLEAN OUT'S ARE TO BE CONSTRUCTED <br />WITH WYES OR SANITARY "T"S (SWEEPS). <br />TYPICAL <br />INSTALL <br />STRAIGHT "T"S ARE NOT PERMITTED. <br />CLEAN OUT <br />AT BLDG. <br />4. ALLOWABLE GRADES ARE 2% (1/4"/FT) <br />ALTERNATES <br />CONNECTION <br />MINIMUM TO 100% (FT/FT) MAXIMUM. <br />4 <br />5. SEWER MUST BE STRAIGHT BETWEEN <br />ANGLE POINTS, CHANGES IN LINE OR <br />3 <br />GRADE SHALL BE MADE WITH APPROVED <br />FITTINGS. <br />o <br />PROPERTY <br />o <br />4 <br />V.-Iz <br />LINE <br />6. NORMALLY ONLY ONE(1) CONNECTION TO <br />- <br />2 <br />THE SEWER MAIN PER BLDG. IS ALLOWED. <br />3 <br />TWO (2) DIFFERENT LAYOUTS ARE SHOWN <br />F <br />1 <br />FOR ILLUSTRATIVE PURPOSES ONLY! <br />z <br />0 <br />> <br />0 <br />SEWER MAIN <br />0 <br />CITY OF EVERETT <br />.6 <br />OLT <br />0� <br />PUBLIC WORKS DEPARTMENT <br />o <br />Ciry Engineer Section Mager CAD Manager...... <br />aw. B urre ev <br />TITLERYAN SASS DAVID VOIGTnaPAUL WILHELM WRB 12/30/2016 <br />a o <br />TYPICAL SIDE SEWER LAYOUTS 601 <br />q <br />via <br />3 TYPICAL SIDE SEWER LAYOUTS <br />�,C4.2 N.T.S. (CITY OF EVERETT STD. 60 1) <br />NOTES <br />1. W = MAXIMUM WIDTH OF TRENCH. FOR PIPES 15" <br />OR LESS IN DIA W=40". FOR PIPES 18" OR GREATER <br />W=1.5 X I.D. + 18". PIPE MUST BE CENTERED IN <br />TRENCH. <br />2. ALTERNATE SLOPING TRENCH WALL TO MEET <br />EXISTING 7 <br />PAVEMENT <br />6 <br />8 10 <br />O.S.H.A. REQUIREMENTS (NO SLOPES STEEPER THAN <br />1:1 EXCEPT FOR ROCK). <br />6" <br />18"MIN <br />3. SUITABLE NATIVE MATERIAL OR IMPORTED GRAVEL <br />BORROW AS DIRECTED. COMPACT TO 90% <br />MAXIMUM DENSITY. <br />- _ <br />'`-`TT =I I <br />4. FOUNDATION GRAVEL IF REQUIRED BY THE <br />ENGINEER TO REPLACE UNSUITABLE MATERIAL. <br />I <br />II I =III- <br />SHALL BE FOUNDATION MATERIAL CLASS A, B OR AS <br />APPROVED BY THE ENGINEER. <br />- <br />5. FOR ADDITIONAL COMPACTION INFORMATION SEE <br />/ <br />STANDARD DWG 615. <br />1 <br />I'I} <br />2 <br />6. IF DIRECTED BYTHE ENGINEER THE TOP THREE TO <br />FIVE FEET OF BACKFILL SHALL BE IMPORTED GRAVEL <br />2 1 <br />U-- <br />BORROW OR SUITABLE NATIVE MATERIAL <br />- <br />COMPACTED TO 95% MAXIMUM DENSITY. <br />7. SEE CITY OF EVERETT STANDARD DWG 326 FOR <br />_ <br />- <br />PAVEMENT PATCH DETAILS. <br />8. VERTICALTRENCH WALLS WITH SHORING TO <br />CONFORM TO O.S.H.A. REGULATIONS. <br />8 <br />III- <br />9. SUBGRADE OR GROUND SURFACE IN NON -PAVED <br />AREAS. <br />10. EXCAVATED NATIVE MATERIAL OR STOCKPILED <br />BACKFILL MATERIAL. <br />3 <br />3 <br />11. FOR ALL TRENCHING TRANSVERSE TO THE ROADWAY <br />a <br />Lu LO <br />BACKFILL ABOVE THE PIPE ZONE SHALL BE <br />1 <br />z 1O <br />O <br />CONTROLLED DENSITY FILL. SEE SECTION 3-9.6 & <br />o <br />N <br />3-20.1 OF THESE STANDARDS. <br />- <br />LU <br />12. FOR UTILITY CUTS SUCH AS GAS, TELEPHONE, <br />w <br />POWER, AND CABLE TV LONGITUDINAL TO THE <br />o <br />- <br />ROADWAY, BACKFILL SHALL BE CONTROLLED <br />- <br />- <br />DENSITY FILL. SEE SECTION 3-9.5 OF THESE <br />0 <br />0 <br />- <br />- <br />STANDARDS. <br />u <br />o <br />_ <br />CITY OF EVERETT <br />_- <br />- <br />-III- <br />4 <br />PUBLIC WORKS DEPARTMENT <br />N <br />W (SEE NOTE1) <br />`-- <br />WO a <br />u a, <br />Clty EEngineer a ger ger a urre ev <br />RYAN SASS DAVID VOIGT PAPA" WILHELM wESH 06/23/2017 <br />STANDARD DRAwiruc"a. <br />so <br />s; <br />EQ� <br />TYPICAL TRENCH SECTION 614 <br />5 TYPICAL TRENCH SECTION <br />�C4.2 N.T.S. (CITY OF EVERETT STD. 601) <br />NW 1/4, SEC. 11 T.28 N, R.4 E, W.M. <br />CITY OFEVERETT, WASHINGTON <br />PARTS <br />A. HYDRANTS AND ALL MATERIALS SHALL CONFORM TO <br />AWWA STANDARDS AND SHALL BE OF STANDARD <br />MANUFACTURE (MUELLER SUPER CENTURION #250, <br />WATEROUS PACER #WB67, OR CITY APPROVED <br />EQUAL). <br />B. 5-1/4" VALVE MINIMUM. <br />C. 1-1/4" OPERATING NUT AND CAP NUT FOR 2-1/2" <br />B <br />MAX RAKE, 1/4" PER FT <br />PORTS. <br />FROM GROUND LEVEL <br />D. NATIONAL STANDARD THREAD ON 2-1/2" PORTS. <br />E. 5" STORZ FITTING WITH NATIONAL STANDARD THREAD <br />ON THE 4-1/2" PORT. <br />C <br />F. IF HYDRANT RISES THROUGH CONCRETE, USE <br />E <br />EXPANSION STRIP AROUND HYDRANT BARREL, PER STD <br />PLAN 509. IN ADDITION, INSTALLATION OF THE <br />HYDRANT ON PRIVATE PROPERTY SHALL EQUAL OR <br />EXCEED THE STANDARDS FOR INSTALLATION OF <br />TRAFFIC SAFETY <br />PUBLIC FIRE HYDRANTS IN THE CITY OF EVERETT. <br />FEATURE BREAK -OFF <br />VALVE BOX AND EXTENSION PER <br />I <br />FLANGE, BREAK OFF <br />STANDARD DRAWING 505 <br />G. PROVIDE FOR VEHICULAR TRAFFIC PROTECTION WHEN <br />NUTS AND BOLTS <br />NECESSARY PER STANDARD DRAWING 508. <br />�\� j\ <br />H. STEAMER PORT TO BE FACING STREET OR ROADWAY <br />FOR FIRE ENGINE ACCESS. <br />1/2 CU YD WASHED ROCK <br />F J <br />I. BREAK -OFF FLANGE TO BE 2"-4" ABOVE GROUND <br />1-1/2" DRAIN ROCK <br />DUCTILE IRON TEE <br />LEVEL. <br />RETAINER <br />(MJxMJxFL) OR <br />GLANDS <br />TAPPING TEE (FL) <br />J. INSTALL CONCRETE PAD AROUND HYDRANT IN <br />�@ <br />UNPAVED, SOD AND ASPHALT AREAS PER STANDARD <br />DRAWING 508. <br />\/ <br />� <br />- <br />K. HYDRANT CONNECTION PIPE TO BE DUCTILE IRON <br />6 6 <br />CLASS 52, ANY INTERMEDIATE JOINTS TO BE MJ WITH <br />O /O <br />RETAINER GLANDS, OR FIELD LOCK GASKETS. <br />��/��\ <br />\ <br />K <br />L. FIRE HYDRANTS SHALL BE PAINTED WITH TWO COATS <br />OF HIGH GLOSS CATERPILLAR YELLOW, LUXLITE <br />3 <br />#6100-516 OR "RUST-OLEUM" #7448 OR APPROVED <br />z <br />12" x 12" x 4" <br />CONIC BLOCK <br />GATE VALVE <br />EQUAL. THE PORT CAPS WILL BE PAINTED BLACK. <br />o <br />(MJ x FL) <br />M. PROVIDE FOR A MINIMUM OF 3' CLEAR ZONE AROUND <br />> <br />0 <br />6 MIL PLASTIC SHEETING WRAP <br />HYDRANT. <br />0 <br />I <br />UNDISTURBED EARTH <br />4CITY OF EVERETT <br />= <br />PUBLIC WORKS DEPARTMENT <br />a <br />WO m <br />Clty Engineer ager ger a n V Current Rev Date <br />RYAN SASS R HEFTI� "PAUL WILHELM W WRB 5/9/2018 <br />NA"DARDDRA <br />o <br />i" N. <br />FIRE HYDRANT <br />v <br />INSTALLATION 507 <br />x <br />az <br />25� <br />48", 54" OR 60" <br />zx <br />2� <br />00 <br />�Ln <br />`V STEPS PER <br />STD 606A <br />LADDER PER <br />STD 606 - <br />Q <br />2 <br />24:1 - <br />SLOPE <br />MORTAR <br />FILLET <br />'I I� <br />611 <br />ci L(. <br />SEPARATE BASE N <br />rocT IKI PI orF <br />• 0 <br />Know what's below. <br />Cal before you dig. <br />2 FIRE HYDRA NT INSTALLATION <br />C4.2 N.T.S. (CITY OF EVERETT STD. 507) <br />MANHOLE FRAME AND COVER <br />PER STANDARD DRAWING 610 OR 611. <br />CIRCULAR ADJUSTMENT SECTION TYPICAL <br />STEPS IN MH ENTRY AREA SHOULD EXTEND <br />ONLY 3" MAX FROM WALL (USED AS <br />HANDHOLDS NOT STEPS) SEE STD 609. <br />ECCENTRIC CONE SECTION <br />RUBBER GASKET AT JOINTS TYPICAL <br />PRECAST RISER SECTIONS <br />6" CLR TYPICAL <br />FIELD -FORMED CHANNEL AND SHELF <br />(SEE NOTE 8) <br />REINFORCING STEEL TYPICAL <br />��GRAVEL BACKFILL FOR PIPE <br />ZONE BEDDING. COMPACT 95% <br />I OF STD DENSITY. <br />INTEGRAL BASE <br />PRECAST WITH RISER <br />NOTES <br />1. MANHOLES TO BE CONSTRUCTED IN ACCORDANCE WITH AASHTO M-199 (ASTM C 478) <br />UNLESS OTHERWISE SHOWN ON PLANS OR NOTED IN STANDARD SPECIFICATIONS. <br />2. ALL REINFORCED CAST IN PLACE CONCRETE SHALL BE CLASS 4000. NON -REINFORCED <br />CONCRETE IN CHANNEL AND SHELF SHALL BE 7 SACK MIX SAND AND CEMENT GROUT. ALL <br />PRECAST CONCRETE SHALL BE CLASS 4000. <br />3. PRECAST BASES SHALL BE FURNISHED WITH CUTOUTS FOR KNOCKOUTS. KNOCKOUTS SHALL <br />HAVE A WALLTHICKNESS OR 2" MINIMUM. <br />4. ALL BASE REINFORCING STEEL SHALL HAVE A MINIMUM YIELD STRENGTH OF 60,000 PSI <br />AND BE PLACED IN THE UPPER HALF OF THE BASE WITH 1" MINIMUM CLEARANCE. <br />5. KNOCKOUT OR CUTOUT HOLE SIZE IS EQUAL TO PIPE OUTER DIAMETER PLUS MANHOLE <br />WALL THICKNESS. <br />6. MANHOLE DIA. DEPENDS ON: SIZE, LOCATION AND NUMBER OF PENETRATIONS FOR PIPES. <br />MANHOLE DESIGN AND SIZE SHALL BE APPROVED AND WARRANTED BY THE MANHOLE <br />SUPPLIER. <br />7. FOR HEIGHTS OVER 25' MANHOLE BASE SLAB SHALL BE DESIGNED BY A STRUCTURAL <br />ENGINEER. <br />8. CONCRETE CHANNEL AND SHELF SHALL BE FIELD -FORMED EXCEPT WHERE APPROVED IN <br />ADVANCE BY CITY. <br />NOTE: KNOCKOUTS SHALL HAVE A WALL THICKNESS OF 2" MINIMUM TO 2.5" MAXIMUM. <br />MANHOLE DIMENSIONS TABLE <br />DIA <br />WALL <br />THICKNESS <br />BASE <br />THICKNESS <br />MAXIMUM <br />KNOCKOUT <br />SIZE <br />MINIMUM <br />DISTANCE BWT <br />KNOCKOUTS <br />BASE REINFORCING STEEL <br />INZ FT IN EACH DIRECTION <br />SEPARATE BASE <br />INTEGRAL BASE <br />48" <br />4" <br />6" <br />36" <br />8" <br />0.23 <br />0.15 <br />54" <br />4.5" <br />8" <br />42" <br />8" <br />0.19 <br />0.19 <br />60" <br />5" <br />8" <br />48" <br />8" <br />0.25 <br />0.25 <br />"0" RING <br />WATER STOP <br />12" <br />GRAVEL <br />BACKFILL FOR <br />PIPE ZONE <br />1.0 o <br />BEDDING <br />SEPARATE BASE PRECAST <br />(___4 TYPICAL MANHOLE 48'; 54" & 60" <br />C4.2 N.T.S. (CITY OF EVERETT STD. 605) <br />UTILITY CONFLICT NOTE.• <br />CAUTION. <br />THE CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFYING THE LOCATION, <br />DIMENSION, AND DEPTH OF ALL EXISTING UTILITIES WHETHER SHOWN ON THESE <br />PLANS OR NOT, BY POTHOLING THE UTILITIES AND SURVEYING THE HORIZONTAL <br />AND VERTICAL LOCATION PRIOR TO CONSTRUCTION. THIS AND THEN SHALL <br />INCLUDE CALLING UTILITY LOCATE ® 1-800-424-5555 POTHOLING ALL OF THE <br />EXISTING UTILITIES AT LOCATIONS OF NEW UTILITY CROSSINGS TO PHYSICALLY <br />VERIFY WHETHER OR NOT CONFLICTS EXIST. LOCATIONS OF SAID UTILITIES AS <br />SHOWN ON THESE PLANS ARE BASED UPON THE UNVERIFIED PUBLIC <br />INFORMATION AND ARE SUBJECT TO VARIATION. IF CONFLICTS SHOULD OCCUR, <br />THE CONTRACTOR SHALL CONSULT WITH INSIGHT ENGINEERING COMPANY TO <br />RESOLVE ALL PROBLEMS PRIOR TO PROCEEDING WITH CONSTRUCTION. <br />4:CITY OF EVERETT <br />77- PUBLIC WORKS DEPARTMENT <br />�ryE�gi�eer �o�M �a er DMa�a r a ReyDa <br />c"`RTITLE YAN SASS DAVI DaVOIGT PAUL WILHELM El- <br />v3/3v/2vi <br />TYPE 1 MANHOLE 605 <br />48 , 54 & 60 <br />SEWER MAIN SYSTEM GENRAL NOTES: <br />CONSTRUCTION OF ALL SANITARY SEWER MAINS, SIDE <br />SEWERS (LATERALS) - WHETHER SIDE SEWERS ARE BY GRAVITY, BY FORCE <br />MAIN, OR PRESSURE SEWER -AND RELATED FACILITIES, INCLUDING BUT <br />NOT LIMITED TO SEWER LIFT STATIONS, TELEMETRY FACILITIES AND <br />APPURTENANCES WILL BE UNDER THE SUPERVISION OF THE CITY AND <br />SHALL BE IN COMPLIANCE WITH ALL ORDINANCES AND CURRENT <br />STANDARDS OF THE CITY OF EVERETT, WASHINGTON STATE DEPARTMENT <br />OF ECOLOGY CRITERIA FOR SEWAGE WORKS DESIGN (ORANGE BOOK), OR <br />THE UNIFIED PLUMBING CODE AS APPLICABLE. <br />SEWER MAIN EXTENSIONS WILL BE REQUIRED WHEN THE PROPERTY DOES <br />NOT FRONT ON A SEWER MAIN OR WHEN THE EXISTING SEWER MAIN IS <br />NOT ADEQUATE FOR THE INCREASED USE PROPOSED. THE MINIMUM <br />EXTENSION SHALL BE TO A POINT AT LEAST 5 FEET INSIDE THE <br />PROLONGATION OF THE PROPERTY LINE. <br />EACH SIDE SEWER SHALL SERVE ONLY ONE BUILDING AND ONE PARCEL <br />(ONE CONNECTION FROM LOT TO MAIN) PER SECTION 6-8.3 AND EMC <br />14.08.170. <br />ALL NEW SEWER CONNECTIONS SHALL COMPLY WITH BACKWATER VALVE <br />REQUIREMENTS IN EMC 14.08.180 B. 1. <br />ALL PIPE INSTALLED SHALL BE STRUCTURALLY SOUND FOR THE DESIGN <br />DEPTH. <br />REQUIREMENTS FOR NEW PROPOSED LIFT (PUMP) STATIONS TO BE <br />DEDICATED TO THE CITY ARE PROVIDED IN SECTION 6-5.1 AND PER THE <br />CITY'S CURRENT LIFT STATION STANDARDS AS ESTABLISHED BY THE CITY'S <br />MAINTENANCE DIVISION/SEWER UTILITY. LIFT STATIONS ARE DEFINED AS <br />SEWAGE PUMPING SYSTEMS THAT SERVE MULTIPLE RESIDENTIAL LOTS OR <br />A NON-RESIDENTIAL DEVELOPMENT GENERATING SIGNIFICANT SEWAGE <br />VOLUME. LIFT STATIONS MUST BE DEMONSTRATED TO BE NEEDED, COST <br />EFFECTIVE FOR THE CITY TO OWN AND MAINTAIN BASED ON SEWER RATES <br />AND LIFECYCLE 0&M COSTS, MEET THE MAINTENANCE DIVISION <br />STANDARDS, AND BE PERMITTED AND APPROVED SOLELY AT THE INTEREST <br />OF THE DEPARTMENT. GRINDER PUMP INSTALLATION FOR INDIVIDUAL <br />PARCELS MAY BE ALLOWED UNDER SEPARATE REVIEW PER SECTION 6-5.2. <br />ALL REQUESTS FOR INSPECTIONS AND FOR WITNESSING ACCEPTANCE <br />TESTS SHALL BE SCHEDULED WITH THE PUBLIC WORKS INSPECTOR AT <br />LEAST 24 HOURS IN ADVANCE. FAILURE TO GIVE ADEQUATE ADVANCE <br />NOTICE MAY RESULT IN DELAYS TO THE CONTRACTOR FOR REQUIRED <br />INSPECTIONS. <br />WATER MAIN SYSTEM GENERAL NOTES: <br />ALL CONSTRUCTION OF WATER MAINS AND RELATED APPURTENANCES SHALL <br />CONFORM TO THESE STANDARDS, APPLICABLE AMERICAN WATER WORKS ASSOCIATION <br />(AWWA) SPECIFICATIONS AND APPLICABLE SECTIONS OF DIVISION 7 OF THE <br />WSDOT/APWA STANDARD SPECIFICATIONS. THE GENERAL REQUIREMENTS OF AWWA <br />AND THE WSDOT/APWA STANDARD SPECIFICATIONS SHALL APPLY UNLESS THEY ARE <br />INCONSISTENT WITH ANY OF THE PROVISIONS OF THIS PARTICULAR SECTION. <br />SHOULD INCONSISTENCIES OCCUR, THESE STANDARDS SHALL HAVE PRECEDENCE. <br />ALL REFERENCE TO STANDARD SPECIFICATIONS SUCH AS AWWA OR WSDOT/APWA <br />SHALL REQUIRE THE USE OF THE LATEST EDITION. <br />ANY PUBLIC WATER SYSTEM OR ANY PLUMBING IN A RESIDENTIAL OR <br />NONRESIDENTIAL FACILITY PROVIDING WATER FOR HUMAN CONSUMPTION WHICH IS <br />CONNECTED TO A PUBLIC WATER SYSTEM SHALL BE LEAD FREE. WITH RESPECT TO <br />SOLDERS AND FLUX, "LEAD FREE" SHALL MEAN NO MORE THAN 0.2% LEAD. WITH <br />RESPECT TO PIPES AND PIPE FITTINGS, "LEAD FREE" SHALL MEAN NO MORE <br />THAN 8% LEAD. <br />WATER MAIN EXTENSIONS WILL BE REQUIRED WHEN THE PROPERTY DOES NOT <br />FRONT ON A WATER MAIN OR WHEN THE EXISTING WATER MAIN IS NOT ADEQUATE <br />TO MEET THE MINIMUM FIRE FLOW REQUIREMENT. THE NEW WATER MAIN EXTENSION <br />SHALL EXTENDED ACROSS THE PROPOSALS FULL FRONTAGE AND SHALL BE <br />EXTENDED THROUGH AND TO THE LIMITS OF THE PROPERTY BEING DEVELOPED FOR <br />SYSTEM CIRCULATION OR FUTURE DEVELOPMENT AS DETERMINED BY THE PUBLIC <br />WORKS DEPARTMENT. THE MINIMUM SIZE WATER MAIN SHALL BE DETERMINED BY <br />THE PUBLIC WORKS DEPARTMENT AND SHALL BE AT LEAST 8" INCHES IN DIAMETER <br />UNLESS OTHERWISE APPROVED BY THE PUBLIC WORKS DIRECTOR OR HIS DESIGNEE. <br />WATER MAIN EXTENSIONS OR REPLACEMENTS AND/OR NEW FIRE HYDRANT <br />INSTALLATIONS MAY ALSO BE REQUIRED PER THE REQUIREMENTS OF THE CITY FIRE <br />MARSHAL. FIRE HYDRANT INSTALLATIONS ARE NOT ALLOWED ON WATER MAINS THAT <br />DO NOT MEET THE MINIMUM FIRE FLOW REQUIREMENTS OF THE AREA. IN A SINGLE <br />FAMILY / DUPLEX NEIGHBORHOOD, THE FIRE FLOW IN THE MAIN MUST BE A <br />MINIMUM OF 1000 GPM BEFORE THE INSTALLATION OF A FIRE HYDRANT IS <br />ALLOWED. <br />A FIRE HYDRANT IS REQUIRED WITHIN 350 FEET OF EVERY STRUCTURE FOR SINGLE <br />FAMILY HOMES AND DUPLEXES AS WELL AS NEW SUBDIVISIONS AND SHORT <br />SUBDIVISION FOR SINGLE FAMILY HOMES AND DUPLEXES. <br />FOR ALL OTHER BUILDINGS FROM TRIPLEXES TO COMMERCIAL USES, A FIRE <br />HYDRANT IS REQUIRED WITHIN 200 FEET, BUT NOT CLOSER THAN 50 FEET TO ANY <br />STRUCTURE (MEASURED DISTANCE TO BE ALONG ROUTE TO BE TRAVELED BY FIRE <br />EQUIPMENT). <br />WATER METERS ARE REQUIRED FOR ALL NEW SERVICES INCLUDING DOMESTIC, <br />IRRIGATION AND FIRE SERVICES. <br />AFTER THE INSTALLATION OF ANY WATER SERVICE BY THE PUBLIC WORKS <br />DEPARTMENT, THE PROPERTY OWNER SHALL BE HELD RESPONSIBLE FOR, AND MAY <br />BE CHARGED FOR, ANY AND ALL DAMAGES TO THE SERVICE LINE, METER SETTER, <br />METER AND METER BOXES/VAULT OR ANY OTHER APPURTENANCES UNTIL <br />COMPLETION OF CONSTRUCTION AND/OR THE STRUCTURE IS APPROVED FOR <br />OCCUPANCY. <br />ALL WATER MAINS ON PRIVATE PROPERTY THAT ARE LOOPED BACK TO THE PUBLIC <br />RIGHT-OF-WAY OR ARE OPEN TO THE GENERAL PUBLIC SYSTEM SHALL BE <br />INSTALLED IN EASEMENTS, GRANTED TO THE CITY, AND SHALL BE MAINTAINED BY <br />THE CITY. (SEE SECTION 5-8.6 FOR MAIN LOOPING REQUIREMENTS.) <br />THE MINIMUM WATER MAIN EASEMENT WIDTH SHALL BE 15 FEET, 5 FEET ON ONE <br />SIDE AND 10 FEET ON THE OTHER SIDE AND SHALL BE EXCLUSIVE FOR THE WATER <br />MAIN AND APPURTENANCES. THE LEGAL DESCRIPTION SHALL BE PREPARED BY A <br />SURVEYOR LICENSED TO PRACTICE IN THE STATE OF WASHINGTON. THE EASEMENT <br />SHALL BE REVIEWED AND APPROVED BY THE PUBLIC WORKS DIRECTOR OR HIS <br />DESIGNEE PRIOR TO ACCEPTANCE. <br />DUE TO THE COMPLEXITIES OF MANY WATER MAINS AND THEIR INTERFACE WITH <br />OTHER UNDERGROUND STRUCTURES, ALL WATER MAIN CONSTRUCTION SHALL BE <br />STAKED TO ENSURE PLACEMENT WITHIN DESIGNATED EASEMENTS. ANY DEVIATION <br />FROM THIS REQUIREMENT MUST BE APPROVED BY THE PUBLIC WORKS DIRECTOR OR <br />HIS DESIGNEE. <br />UPON COMPLETION OF THE INSTALLATION OF THE WATER SYSTEM, THE ORIGINAL <br />SIGNED DRAWING OF THE WATER CONSTRUCTION PLAN MUST BE EDITED TO REFLECT <br />ACTUAL CONSTRUCTED CONDITIONS (RECORD DRAWINGS) BY THE <br />DEVELOPER/CONTRACTOR, CERTIFIED AS SUCH BY HIM AND TURNED INTO THE CITY. <br />A RECORD DRAWING PRINT SHALL BE SUBMITTED FOR CHECKING BY THE CITY <br />INSPECTOR AND PUBLIC WORKS DEPARTMENT PRIOR TO SUBMITTING THE REVISED <br />ORIGINALS. THE WATER RECORD DRAWING SHALL BE SUBMITTED WITHIN 14 DAYS OF <br />THE PUBLIC WATER MAIN BECOMING LIVE. <br />THE INSTALLATION OF ALL WATER MAINS AND APPURTENANCES SHALL BE IN <br />ACCORDANCE WITH THE CONSTRUCTION PLANS AS APPROVED BY THE PUBLIC WORKS <br />DIRECTOR OR HIS DESIGNEE FOR THE PROJECT. ANY DEVIATIONS OR CHANGES ARE <br />TO BE APPROVED BY PUBLIC WORKS DIRECTOR OR HIS DESIGNEE BEFORE THE <br />CHANGES ARE INCORPORATED INTO THE WORK. <br />ALL MATERIALS SHALL BE NEW AND UNDAMAGED. UNLESS OTHERWISE APPROVED BY <br />THE PUBLIC WORKS DIRECTOR OR HIS DESIGNEE, THE SAME MANUFACTURER OF <br />EACH ITEM SHALL BE USED THROUGHOUT THE WORK. CONTRACTORS SHALL FURNISH <br />A WATER TIGHT PLUG OF THE APPROPRIATE SIZE WHICH SHALL BE INSTALLED IN <br />THE END OF THE WATER MAIN ANYTIME WORK IS DELAYED OR STOPPED. <br />WA TER MAINS YSTEM REQ UIRED NOTES: <br />A. NO CONNECTION TO THE EXISTING MAINS WILL BE ALLOWED EXCEPT BY <br />MEANS OF AN APPROVED BACKFLOW PREVENTION DEVICE PRIOR TO <br />SATISFACTORY FLUSHING, TESTING, DISINFECTION, AND RECEIPT OF <br />SATISFACTORY BACTERIOLOGICAL TEST RESULTS. <br />B. CONNECTIONS TO AND TAPS ON EXISTING MAINS WILL BE MADE BY THE <br />PUBLIC WORKS DEPARTMENT AT THE DEVELOPER'S EXPENSE. THE PUBLIC <br />WORKS DEPARTMENT SHALL BE GIVEN AT LEAST 5 BUSINESS DAYS NOTICE <br />FOR EACH CONNECTION. THE PUBLIC WORKS DEPARTMENT SHALL THEREAFTER <br />DETERMINE THE DATE AND TIME AT WHICH THE CONNECTION SHALL BE MADE. <br />C. ALL WORK AND MATERIALS MUST CONFORM TO CITY OF EVERETT <br />STANDARDS. <br />D. A PRE -CONSTRUCTION MEETING SHALL BE HELD WITH THE CITY PRIOR TO <br />THE START OF CONSTRUCTION. THE CITY OF EVERETT PUBLIC WORKS <br />CONSTRUCTION DIVISION MUST BE NOTIFIED AT LEAST 24 HOURS PRIOR TO <br />COMMENCEMENT OF CONSTRUCTION. <br />E. THE DEVELOPER OR THE DEVELOPER'S AUTHORIZED AGENT SHALL NOTIFY <br />THE PUBLIC WORKS DEPARTMENT OF A PERSON WHO CAN BE CONTACTED <br />REGARDING PROBLEMS DURING CONSTRUCTION ON A 24 HOUR BASIS. <br />F. MAINTAIN A MINIMUM OF 10 FEET HORIZONTAL AND 18 INCHES VERTICAL <br />SEPARATION BETWEEN POTABLE AND NON -POTABLE CONVEYANCE SYSTEMS. <br />G. ALL CITY OF EVERETT VALVES SHALL BE OPERATED BY PUBLIC WORKS <br />DEPARTMENT PERSONNEL ONLY. ALL VALVES, NEW AND EXISTING, SHALL BE <br />ACCESSIBLE AT ALL TIMES. <br />SEWER MAIN SYSTEM CONSTRUCTION PLAN NOTES: <br />THE INSTALLATION OF ALL EXTENSIONS TO THE SANITARY SEWER SYSTEM SHALL BE DONE <br />PER PLANS WHICH HAVE BEEN APPROVED BY THE CITY ENGINEER. <br />SANITARY SEWER PLANS ARE TO BE SEPARATE FROM OTHER UTILITY PLANS, BUT ALL <br />OTHER UTILITIES ARE TO BE SHOWN, WITH SANITARY SEWER PORTIONS HIGHLIGHTED. <br />UNLESS APPROVED OTHERWISE, PLANS SHOULD BE PREPARED ON 22 INCH BY 34 INCH <br />PLAN/PROFILE TYPE SHEETS AND SHALL SHOW BOTH PLAN AND PROFILE VIEWS. OTHER <br />UTILITIES ARE TO BE SHOWN IN PROFILE VIEW AND IN PLAN VIEW. <br />THE MINIMUM ALLOWABLE SCALE SHALL BE 1 INCH = 40 FEET, ON SMALL PROJECTS, IT <br />SHALL BE EXPECTED THAT THE SCALE WILL BE ENLARGED TO ADEQUATELY UTILIZE THE <br />FULL PLAN SHEET. <br />PROVIDE NOTES ON PLANS THAT REFER TO SPECIFIC CITY STANDARDS FOR SUCH THINGS <br />AS MANHOLES, DROP CONNECTIONS, SIDE SEWERS, ETC. <br />PLANS SHALL SHOW INVERT ELEVATIONS OF THE MAIN AT THE OUTLET AND ALL INLETS <br />OF EACH MANHOLE, SLOPE OF THE MAIN AND SURFACE ELEVATIONS OF THE MANHOLE <br />LID. IN THE PROFILE VIEW, THE FINISH GROUND ELEVATION OVER THE PIPE SHALL BE <br />SHOWN AS WELL AS CROSSINGS OF OTHER EXISTING OR PROPOSED UTILITIES. STATIONING <br />OF SIDE SEWERS FROM THE DOWNHILL MANHOLE IS REQUIRED. <br />IN ALL CASES WHERE A NEW SEWER LINE IS TO BE LOCATED IN AN EASEMENT, THE <br />EASEMENT IS TO BE SHOWN WITH MEASUREMENT INFORMATION TO ACCURATELY FIELD <br />SURVEY AND STAKE LOCATION PRIOR TO CONSTRUCTING THE PIPE LINE. <br />UPON COMPLETION OF CONSTRUCTION, THE ORIGINAL OF THE PLAN SHALL BE AS -BUILT <br />BY THE DEVELOPER AND CERTIFIED AS AS -BUILT BY HIM AND TURNED INTO THE PUBLIC <br />WORKS DEPARTMENT WITH PROPERLY EXECUTED EASEMENT DEEDS AS APPLICABLE FOR <br />THE PROJECT. <br />SEWER MAIN SYSTEMREQUIRED NOTES: <br />THE FOLLOWING STANDARD NOTES ARE REQUIRED ON ALL SANITARY SEWER PLANS: <br />A. ALL WORK AND MATERIALS SHALL CONFORM TO THE CITY OF EVERETT STANDARDS <br />AND WSDOT/APWA STANDARD SPECIFICATIONS. <br />B. NO PART OF THE SANITARY SEWER SYSTEM SHALL BE COVERED, CONCEALED OR PUT <br />INTO USE UNTIL IT HAS BEEN TESTED, INSPECTED, AND APPROVED BY THE CITY <br />INSPECTOR. <br />C. APPROXIMATE LOCATIONS OF EXISTING UTILITIES HAVE BEEN OBTAINED FROM AVAILABLE <br />RECORDS AND ARE SHOWN FOR CONVENIENCE. THE CONTRACTOR SHALL BE RESPONSIBLE <br />FOR VERIFICATION OF LOCATIONS AND TO AVOID DAMAGE TO ANY ADDITIONAL UTILITIES <br />NOT SHOWN. IF CONFLICTS WITH EXISTING UTILITIES ARISE DURING CONSTRUCTION, THE <br />CONTRACTOR SHALL NOTIFY THE PUBLIC WORKS INSPECTOR AND ANY CHANGES REQUIRED <br />SHALL BE APPROVED BY THE CITY ENGINEER PRIOR TO COMMENCEMENT OF RELATED <br />CONSTRUCTION ON THE PROJECT. <br />D. ALL SEWER MAIN EXTENSIONS WITHIN THE PUBLIC RIGHT-OF-WAY OR IN EASEMENTS <br />MUST BE STAKED BY SURVEY FOR LINE AND GRADE PRIOR TO STARTING CONSTRUCTION. <br />WATER MAIN SYSTEM CONSTR UCTION PLAN NOTES: <br />A. WATER PLANS ARE TO BE SEPARATE FROM OTHERS AND SHALL HAVE WATER MAINS <br />HIGHLIGHTED AND INDICATE LOCATIONS OF OTHER UTILITIES. <br />B. PLANS MUST SHOW EASEMENTS WHERE MAINS ARE ON PRIVATE PROPERTY AND ALL <br />HYDRANTS, METERS, AND OTHER APPURTENANCES MUST BE WITHIN THE EASEMENTS. <br />EASEMENTS MUST MEET THE REQUIREMENTS OF SECTION 5-1. <br />C. EASEMENTS MUST BE EXECUTED AT COMPLETION OF CONSTRUCTION. EASEMENTS FOR <br />WATER MAINS MUST BE 15 FEET WIDE WITH THE CENTER OF THE WATER MAIN 5 FEET FROM <br />ONE OF THE SIDES LEAVING 10 FEET ON THE OTHER. ACCESS TO EASEMENTS FOR <br />MAINTENANCE MUST REMAIN OPEN. STRUCTURES, FENCES, AND SHRUBS ARE NOT TO BE <br />PLANTED ON EASEMENTS. <br />D. SHOW ELEVATIONS OF SEWER MAINS, WATER MAINS AND STORM DRAINS WHERE THEY <br />CROSS EACH OTHER. <br />E POTABLE WATER MAINS SHALL MAINTAIN A MINIMUM OF 10 FEET HORIZONTAL CLEARANCE <br />AND 18 INCHES VERTICAL SEPARATION ABOVE NON -POTABLE UTILITIES (INCLUDING SEWER, <br />STORM DRAINAGE AND IRRIGATION) WHENEVER POSSIBLE. IF SITE CONDITIONS DO NOT ALLOW <br />SUCH MINIMUM SEPARATIONS, PIPELINES MAY BE LOCATED CLOSER TO EACH OTHER <br />PROVIDED ADDITIONAL PRECAUTIONS ARE IDENTIFIED AND INSTITUTED TO ASSURE PROTECTION <br />OF THE POTABLE LINE. NO OTHER UTILITIES, POTABLE OR NON -POTABLE, SHALL BE WITHIN 5 <br />FEET HORIZONTAL AND 12 INCHES VERTICAL FROM THE WATER MAIN. <br />F. ALL INSTALLED HYDRANTS MUST BE COVERED BY A BURLAP BAG OR OTHER SUITABLE <br />COVERING UNTIL ACCEPTED BY THE PUBLIC WORKS DIRECTOR OR HIS DESIGNEE AND PLACED <br />IN SERVICE. <br />G. A WASHINGTON STATE APPROVED BACKFLOW PREVENTION DEVICE IS REQUIRED FOR ALL <br />IRRIGATION SYSTEMS. <br />H. ALL ENVIRONMENTAL SENSITIVE AREAS SHALL BE SHOWN ON THE WATER SYSTEM <br />CONSTRUCTION PLANS. <br />I. PLANS MUST SHOW REQUIRED THRUST RESTRAINT PER SECTION 5-13 OF THESE <br />STANDARDS. <br />J. ALL WATER CONSTRUCTION PLANS SHALL BE PREPARED, STAMPED AND SIGNED BY AN <br />ENGINEER REGISTERED IN THE STATE OF WASHINGTON. <br />