OtENSEQUENCE OF OPERATIONS: Seattle// k a"Baltimore <br /> Copyright©FSi consulting engineers <br /> CONDENSER WATER SYSTEM <br /> 1.THE EMS SHALL CONTROL OPERATION OF THE TWO BOILERS (B-401 & B-402) VIA LOCAL <br /> BOILER MANAGEMENT SYSTEM, LOOP PUMPS CWP-401 & CWP-402, FLUID COOLER FC-401 <br /> WITH COMPANION DIVERTING VALVE. THE EMS SHALL OPERATE THE CONDENSER WATER <br /> SYSTEM TO PROVIDE CONDENSER WATER SUPPLY TEMPERATURE TO THE HEAT PUMPS (TS4) <br /> IN THE 70 TO 87.5 DEGREES F RANGE. DURING WARMUP MODE AND DAY MODE, WHETHER <br /> CONDENSER WATER PUMPS ARE VARIABLE FLOW OR CONSTANT FLOW VOLUME, WARMUP MODE <br /> SHALL BE INITIALLY SET FOR 6AM TO 7:30 AM (ADJUSTABLE), AND DAY MODE FROM 7:30 <br /> AM TO 6 PM (ADJUSTABLE). DURING NIGHT MODE, PUMPS SHALL BE ALLOWED TO RUN FROM <br /> 11PM TO MIDNIGHT (ADJUSTABLE) AND FROM 3AM TO 4AM (ADJUSTABLE), TO PREVENT <br /> MULTIPLE PUMP STARTS DURING THE NIGHT MODE, EMS SHALL START THE CONDENSER <br /> WATER LEAD PUMP CWP-401, AND VERIFY PROOF OF FLOW. IF FLOW IS NOT PROVED, <br /> ALARM SHALL SOUND AND LAG PUMP SHALL START. ALTERNATE LEAD/LAG PUMPS ON <br /> WEEKLY BASIS. AFTER PROOF OF FLOW IS ESTABLISHED, HEAT PUMPS SHALL OPERATE AS <br /> DESCRIBED. <br /> 2.LOOP TEMPERATURE "SATISFIED", WHERE TS4 IS BETWEEN 70 F AND 87.5 F (INCLUSIVE) <br /> AND TS6 IS LESS THAN 92.5 F. FLUID COOLER IS BYPASSED. z <br /> LJJ <br /> LOOP TEMPERATURE TOO COOL: 75 <br /> 1.FLUID COOLER IS BYPASSED. IF TS4 TEMP DROPS BELOW 70F (73F ADJUSTABLE) HEATING ui <br /> SETPOINT WITH 5 DEGREE THROTTLING RANGE, LEAD BOILER SHALL OPERATE AS FOLLOWS: U <br /> 1.1. VERIFY PROOF OF FLOW IN LOOP. Q <br /> 1.2. EMS SHALL SEND A FIXED 4-20 MA SIGNAL CORRESPONDING TO A CWS SETPOINT OF J <br /> 73F TO THE LOCAL BOILER MANAGEMENT SYSTEM (BMS) CONTROL PANEL. BMS SHALL <br /> HAVE A PROGRAM TO MODULATE THE BOILER(S) FOR THE AMOUNT OF HEATING NEEDED w <br /> SO THAT CWS (TS4) TEMPERATURE IS MAINTAINED WITHIN THE STATED RANGE. BOILER � z <br /> / <br /> HAS A 10:1 TURNDOWN RATIO (MODULATING GAS FIRED BOILER). 0. O <br /> 1.3. BMS SHALL FIRE BOILER(S) IN THE MOST ENERGY EFFICIENT MANNER. CONDENSING n/ � <br /> TYPE BOILERS ARE MOST EFFICIENT AT LOWER FIRING RATES SO BMS MAY OPERATE LAG LL <br /> BOILER BEFORE LEAD BOILER REACHES 100% U] J z <br /> 1.4. BMS WILL CONTINUE TO FIRE BOILERS UNTIL CWS (TS4) TEMP EXCEEDS 76F. AT WHICH <br /> POINT BMS SHALL SIGNAL BOILER(S) TO STOP FIRING. O O <br /> co <br /> LOOP TEMPERATURE TOO WARM: O m < <br /> 1.WHEN TS6 (CWR) IS GREATER THAN 92.6 DEGREES F, THEN DIVERTING VALVE FOR FLUID = 1 <br /> COOLER SHALL OPEN (FLOW THROUGH TOWER) AND OPERATE AS FOLLOW: U F <br /> 1.1. DISCHARGE DAMPER ON FLUID COOLER HOOD SHALL OPEN. U) W <br /> 1.2. SPRAY PUMP SHALL OPERATE. r , '^ <br /> 1.3. FLUID COOLER FAN SHALL OPERATE ON PONY (SMALL) MOTOR. IF AFTER 8 MINUTES `J (D <br /> CWR TEMP(TS6) IS STILL ABOVE 87.5 DEGREES F, THEN PONY MOTOR SHALL STOP AND J z LLJ <br /> MAIN FAN MOTOR SHALL START. IF TS4 CWS TEMP DROPS TO BELOW 70 F WHEN FLUID m Q W <br /> COOLER IS OPERATING, BOILERS SHALL NOT COME ON, AND FLUID COOLER SHALL TURN <br /> OFF (FAN MOTOR TURNS OFF, SPRAY PUMP STOPS, DISCHARGE DAMPER SHALL CLOSE). J <br /> FLUID COOLER SHALL RUN FOR A MINIMUM OF 15 MINUTES (NO MORE THAN 4 STARTS — 0 <br /> PER HOUR). THE ADJUSTABLE COOLING SETPOINT FOR CWR (TS6) SHALL BE SET FOR O <br /> 90F WITH A 5 F THROTTLING RANGE. m <br /> BOILER BYPASS w J O <br /> 1.WHEN ONE BOILER SHUTOFF VALVE IS CLOSED, OPEN MODULATING BOILER BYPASS VALVE <br /> HALFWAY TO MAINTAIN FULL GPM SYSTEM FLOW. w O U) <br /> 2.WHEN BOTH BOILER SHUTOFF VALVES ARE CLOSED, OPEN MODULATING BOILER BYPASS = Q <br /> VALVE FULLY TO MAINTAIN FULL GPM SYSTEM FLOW. w r , () <br /> FREEZE PROTECTION W <br /> 1.WHEN OUTSIDE AIR TEMP IS LESS THAN 35 DEGREES F, LOOP CIRCULATION PUMP WILL <br /> OPERATE. VERIFY SECONDARY LOOP FLOW. ALSO, COOLING TOWER DIVERTING VALVE WILL V 00 <br /> OPEN TO FLOW THROUGH COOLER (BUT DISCHARGE DAMPER ON FLUID COOLER HOOD WILL = <br /> REMAIN CLOSED). THE DIVERTING VALVE WILL FAIL ON LOSS OF POWER TO THE BY PASS <br /> MODE (NO FLOW THROUGH COOLER). w <br /> 2."BOILER EMERGENCY SHUTOFF" SWITCH WIRED TO SHUT OFF BOILER SYSTEM VIA INTERTIE TO Q <br /> AUXILIARY CONTACT ON BMS PANEL. Q <br /> 3.SYSTEM WILL ALARM IF THERE IS A CALL FOR HEATING AND THE FLOW IS NOT PROVED. EMS U <br /> WILL ATTEMPT TO START LAG PUMP. ALARM WILL CONTINUE FOR LEAD PUMP. 0 <br /> 4.EMS WILL CONTROL CONDENSER WATER PUMPS TO PROVIDE FLOW WHENEVER ANY HEAT <br /> PUMP IS CALLING FOR HEATING OR COOLING (DURING OFF—HOURS OPERATION), CONDENSER Q <br /> WATER LEAD PUMP WILL OPERATE DURING MORNING WARMUP AND DAY MODE. PROVIDE U <br /> LEAD/LAG ON PUMPS ON WEEKLY BASIS. <br /> THE EMS MONITORS THE FOLLOWING POINTS: <br /> BOILER 1 ON <br /> FAIL <br /> BOILER 2 ON <br /> FAIL <br /> CWS TEMP <br /> CWR TEMP W. t4 <br /> LOOP FLOW STATUS <br /> BOILER BYPASS VALVE POSITION <br /> BOILER SUPPLY TEMP Z <br /> BOILER RETURN TEMP 48 <br /> 1 <br /> CONDENSER RETURN TEMP �FFSS ceni¢eoa` <br /> PUMP-1 STATUS <br /> re.,,may <br /> PUMP-2 STATUS s� <br /> Project No. <br /> SINGLE PHASE PROTECTION (FOR 3/4 HP & UP MOTORS) 23032 <br /> 1.THE EMS WILL MONITOR THE THREE PHASE POWER TO THE BUILDING. IF SINGLE PHASE Date <br /> OCCURS, IT WILL STOP ALL CONNECTED THREE PHASE ELECTRICAL EQUIPMENT, SOUND ALARM 09.11.2023 <br /> AT CPU AND WAIT TWO MINUTES AFTER THREE PHASE POWER HAS BEEN RESTORED BEFORE <br /> AUTOMATICALLY RESTARTING EQUIPMENT. ALL MOTOR LOADS LARGER THAN _ HP WILL BE Date Revision <br /> SEQUENTIALLY RESTARTED WITH 5 SECOND DELAY BETWEEN EACH START. <br /> Sheet Title <br /> SEQUENCE OF <br /> OPERATIONS <br /> &POINTS LIST <br /> Sheet <br /> PERMIT SET M8 . 1 <br />