Laserfiche WebLink
ZONE FCU-3 <br />Conditions at Time of Space Cooling Peak <br />Conditions at Time of Space Heating Peak <br />Peak Time (Mo/D/H:M) <br />7/21 09:00:00 <br />Peak Time (Mo/D/H:M) <br />12/21 24:00:00 <br />Outside DB / WB / HR <br />70.1 °F / 58.6 °F / <br />55.9 gr/lb <br />Outside DB / WB / HR <br />25.4 °F / 19.1 °F <br />/ 5.9 gr/lb <br />Zone DB / RH / HR <br />75.0 °F / 46.0 % / <br />60.3 gr/lb <br />Zone DB / RH / HR <br />70.0 °F / 7.8 % <br />/ 8.5 gr/lb <br />Time <br />Percent <br />Time <br />Percent <br />Instant <br />Delay <br />of <br />Instant <br />Delay <br />of <br />Sensible <br />Sensible Latent <br />Total <br />Total <br />Sensible <br />Sensible Latent <br />Total <br />Total <br />(Btu/h) <br />(Btu/h) (Btu/h) <br />(Btu/h) <br />(%) <br />(Btu/h) <br />(Btu/h) (Btu/h) <br />(Btu/h) <br />(%) <br />Roof <br />0 <br />12 0 <br />12 <br />0.1 <br />Roof <br />0 <br />-748 0 <br />-748 <br />8.2 <br />Other Roof <br />0 <br />0 0 <br />0 <br />0.0 <br />Other Roof <br />0 <br />0 0 <br />0 <br />0.0 <br />Glass <br />3,716 <br />12,749 0 <br />16,465 <br />75.8 <br />Glass <br />-2,703 <br />0 0 <br />-2,703 <br />29.6 <br />Door <br />0 <br />0 0 <br />0 <br />0.0 <br />Door <br />0 <br />0 0 <br />0 <br />0.0 <br />Wall <br />0 <br />1,177 0 <br />1,177 <br />5.4 <br />Wall <br />0 <br />-872 0 <br />-872 <br />9.5 <br />Below -Grade Wall <br />0 <br />0 0 <br />0 <br />0.0 <br />Below -Grade Wall <br />0 <br />0 0 <br />0 <br />0.0 <br />Other Wall <br />0 <br />0 0 <br />0 <br />0.0 <br />Other Wall <br />0 <br />0 0 <br />0 <br />0.0 <br />Partition <br />0 <br />-1,970 0 <br />-1,970 <br />-9.1 <br />Partition <br />0 <br />-530 0 <br />-530 <br />5.8 <br />Exterior Floor <br />0 <br />0 0 <br />0 <br />0.0 <br />Exterior Floor <br />0 <br />0 0 <br />0 <br />0.0 <br />Interior Floor <br />0 <br />0 0 <br />0 <br />0.0 <br />Interior Floor <br />0 <br />0 0 <br />0 <br />0.0 <br />Slab <br />0 <br />-1,426 0 <br />-1,426 <br />-6.6 <br />Slab <br />0 <br />-96 0 <br />-96 <br />1.0 <br />Other Floor <br />0 <br />0 0 <br />0 <br />0.0 <br />Other Floor <br />0 <br />0 0 <br />0 <br />0.0 <br />Infiltration <br />-107 <br />0 -60 <br />-167 <br />-0.8 <br />Infiltration <br />-3,941 <br />0 0 <br />-4,090 <br />44.7 <br />Envelope Subtotal <br />3,609 <br />10,541 -60 <br />14,090 <br />- <br />Envelope Subtotal <br />-6,644 <br />-2,246 0 <br />-9,038 <br />- <br />People <br />2,479 <br />0 1,820 <br />4,299 <br />19.8 <br />People <br />0 <br />0 0 <br />0 <br />0.0 <br />Lights <br />1,706 <br />0 0 <br />1,706 <br />7.9 <br />Lights <br />0 <br />0 0 <br />0 <br />0.0 <br />Miscellaneous Loads <br />1,842 <br />0 0 <br />1,842 <br />8.5 <br />Miscellaneous Loads <br />0 <br />0 0 <br />0 <br />0.0 <br />Internal Subtotal <br />6,028 <br />0 1,820 <br />7,847 <br />- <br />Internal Subtotal <br />0 <br />0 0 <br />0 <br />- <br />RA (All Other) <br />0 <br />0 0 <br />0 <br />0.0 <br />RA (All Other) <br />0 <br />0 0 <br />0 <br />0.0 <br />DOA Direct to Zone <br />0 <br />0 0 <br />0 <br />0.0 <br />DOA Direct to Zone <br />0 <br />0 0 <br />0 <br />0.0 <br />Ceiling <br />0 <br />0 0 <br />0 <br />0.0 <br />Ceiling <br />0 <br />0 0 <br />0 <br />0.0 <br />Refrigeration <br />0 <br />0 0 <br />0 <br />0.0 <br />Refrigeration <br />0 <br />0 0 <br />0 <br />0.0 <br />Service Water <br />0 <br />0 0 <br />0 <br />0.0 <br />Service Water <br />0 <br />0 0 <br />0 <br />0.0 <br />HVAC Equipment Losses <br />0 <br />0 0 <br />0 <br />0.0 <br />HVAC Equipment Losses <br />0 <br />0 0 <br />0 <br />0.0 <br />Adj Air Transfer Heat <br />0 <br />0 0 <br />0 <br />0.0 <br />Adj Air Transfer Heat <br />0 <br />0 0 <br />0 <br />0.0 <br />Sizing Factor Correction <br />0 <br />0 0 <br />0 <br />0.0 <br />Sizing Factor Correction <br />0 <br />0 0 <br />0 <br />0.0 <br />Time Delay Correction <br />0 <br />-219 0 <br />-219 <br />-1.0 <br />Time Delay Correction <br />0 <br />-105 0 <br />-105 <br />1.2 <br />Grand Total <br />9,637 <br />10,323 1,760 <br />21,719 <br />100.0 <br />Grand Total <br />-6,644 <br />-2,351 0 <br />-9,144 <br />100.0 <br />RA Sensible (Lights) <br />0 <br />0 0 <br />0 <br />- <br />RA Sensible (Lights) <br />0 <br />0 0 <br />0 <br />- <br />Engineering Checks <br />Engineering Checks <br />Cooling tons <br />1.81 <br />Input Ventilation cfm <br />80 <br />Heating Mbh <br />-9.14 <br />Input Ventilation cfm <br />80 <br />Cooling cfm <br />922 <br />Calculated Ventilation <br />cfm <br />80 <br />Heating cfm <br />922 <br />Calculated Ventilation <br />cfm <br />80 <br />Cooling ACH <br />8.46 <br />Calculated Ventilation <br />ACH <br />0.73 <br />Heating ACH <br />8.46 <br />Calculated Ventilation <br />ACH <br />0.73 <br />Sec Fan cfm <br />0 <br />Number of People <br />10.01 <br />Sec Fan cfm <br />0 <br />Number of People <br />10.01 <br />ft2/ton <br />276.22 <br />People per 1000 ft2 <br />20 <br />ft2/Mbh <br />-54.67 <br />People per 1000 ft2 <br />20 <br />cfm/ton <br />509.18 <br />Conditioned ft2 <br />499.9 <br />cfm/Mbh-100.81 <br />Conditioned ft2 <br />499.9 <br />Btu/h-ft2 <br />43.44 <br />Volume (ft3) <br />6,539.6 <br />Btu/h-ft2 <br />-18.29 <br />Volume (ft3) <br />6,539.6 <br />Alternative: Primary Calculated at: Feb 28, 2024 - 12:09 PM <br />File EDWARD JONES, EVERETTE, WA.mdf TRACE 3D Plus 5.20.117 <br />name: <br />