Laserfiche WebLink
Fan -Coil Unit Test Data <br />Project No. <br />2024-1113 <br />Project I.D. <br />Edward Jones Branch # 98316 <br />Test Date <br />9/16/2024 <br />Tested By <br />Vinh Nguyen <br />Area Served <br />Branch Support, Offices, Equip/Supply <br />Equipment I.D. <br />FCU-2 <br />Unit Information <br />Manufacturer <br />Carrier <br />Model Number <br />40VMM030A--3 <br />Serial Number <br />1324VO0477 <br />Unit Location <br />Office 102 E <br />Supply Fan Quantity / Rotation <br />N/A / Correct <br />Supply Fan Drive Type <br />Direct Drive <br />Unit Filter Information <br />Filter I.D. <br />Type <br />Rating <br />Filter Size / Quantity <br />Filter Size / Quantity <br />Unit Filter <br />Pleated <br />N/A <br />11X43X2" / 1 <br />N/A / <br />Unit and Fan Test Data <br />Total Design Airflow <br />1,070 CFM <br />Total Actual Airflow <br />1,015 CFM <br />Design Return Airflow <br />1,070 CFM <br />Actual Return Airflow <br />860 CFM <br />Min OSA CFM Des / Act <br />155 CFM / 165 CFM <br />Min OSA Position OSA / RA <br />N/A / #VALUE! <br />Design ESP <br />0.50 in.wc <br />Actual ESP <br />0.27 in.wc <br />Actual Volts <br />207 <br />Actual Amps <br />1.04 <br />Fan Speed Setting <br />Med-High <br />Additional Settings <br />N/A <br />Unit Motor Information <br />HP / RPM <br />1/3 / <br />Motor Phase / Hz <br />1 / 60 <br />Motor Rated Volts / FLA <br />208-230 / 2.5 <br />1Motor Eff. / PF <br />/ - <br />Unit Pressure Data <br />Filter In / Out <br />-0.170 in.wc / -0.320 in.wc <br />Filter AID <br />0.150 in.wc <br />Supply Fan In / Out <br />- in.wc / 0.100 in.wc <br />Supply Fan A P <br />#VALUE! in.wc <br />External Static In / Out <br />-0.170 in.wc / 0.100 in.wc <br />External Static A P <br />0.270 in.wc <br />Unit Test Notes <br />Note (1) 1Thermostat fanspeed was set at Medium -High speed. <br />Page 13 of 49 <br />