Laserfiche WebLink
Grille, Register, & Diffuser Test Data <br />Project No. <br />2024-1113 <br />Project I.D. <br />Edward Jones Branch # 98316 <br />Test Date <br />9/16/2024 <br />Tested By <br />Vinh Nguyen <br />Area Served <br />Supply Air <br />Equipment I.D. <br />FCU-2 <br />Grille, Register, Duct, Test Data <br />Flow Spec + 10% - 10% <br />GIRD <br />No. <br />Area Served <br />Instrument <br />Used <br />GRID <br />Type <br />Size <br />Inches <br />AK <br />Design <br />CFM <br />Initial <br />CFM <br />Final Airflow <br />FPM <br />CFM <br />% <br />Notes <br />1 <br />Office 102A <br />Flowhood <br />SD-1 <br />6" <br />1.00 <br />55 <br />85 <br />51 <br />93% <br />2 <br />Office 102B <br />Flowhood <br />SD-1 <br />6" <br />1.00 <br />55 <br />80 <br />52 <br />95% <br />3 <br />Hallway <br />Flowhood <br />SD-1 <br />8" <br />1.00 <br />115 <br />155 <br />111 <br />97% <br />4 <br />Office 102C <br />Flowhood <br />SD-1 <br />6" <br />1.00 <br />55 <br />85 <br />51 <br />93% <br />5 <br />Office 102D <br />Flowhood <br />SD-1 <br />6" <br />1.00 <br />55 <br />45 <br />50 <br />91% <br />6 <br />Branch Support 101A <br />Flowhood <br />SD-1 <br />6" <br />1.00 <br />90 <br />95 <br />87 <br />97% <br />7 <br />Branch Support 101A <br />Flowhood <br />SD-1 <br />6" <br />1.00 <br />85 <br />100 <br />88 <br />104% <br />8 <br />Storage 108 <br />Flowhood <br />SD-1 <br />6" <br />1.00 <br />50 <br />95 <br />49 <br />98% <br />9 <br />Office 102F <br />Flowhood <br />SD-1 <br />6" <br />1.00 <br />55 <br />25 <br />52 <br />95% <br />10 <br />Office 102E <br />Flowhood <br />SD-1 <br />6" <br />1.00 <br />55 <br />65 <br />51 <br />93% <br />11 <br />Lounge 109 <br />Flowhood <br />SD-1 <br />6" <br />1.00 <br />55 <br />95 <br />50 <br />91% <br />12 <br />Hallway <br />Flowhood <br />SD-1 <br />8" <br />1.00 <br />120 <br />30 <br />114 <br />95% <br />13 <br />Equip/Supply 104 <br />Flowhood <br />SD-1 <br />6" <br />1.00 <br />70 <br />80 <br />64 <br />91% <br />14 <br />Branch Support 101 B <br />Flowhood <br />SD-1 <br />8" <br />1.00 <br />155 <br />155 <br />145 <br />94% <br />(1) <br />(This Page) Total Airflow <br />1070 <br />1190 <br />1015 <br />95% <br />Test Notes <br />Note (1) 1 The volume damper is full open. <br />Page 14 of 49 <br />