Laserfiche WebLink
Grille, Register, & Diffuser Test Data <br />Project No. <br />2024-1113 <br />Project I.D. <br />Edward Jones Branch # 98316 <br />Test Date <br />9/16/2024 <br />Tested By <br />Vinh Nguyen <br />Area Served <br />Return Air <br />Equipment I.D. <br />FCU-2 <br />Grille, Register, Duct, Test Data <br />Flow Spec + 10% - 10% <br />GIRD <br />No. <br />Area Served <br />Instrument <br />Used <br />GRID <br />Type <br />Size <br />Inches <br />AK <br />Design <br />CFM <br />Initial <br />CFM <br />Final Airflow <br />FPM <br />CFM <br />% <br />Notes <br />1 <br />Office 102A <br />Flowhood <br />RG-1 <br />6" <br />1.00 <br />55 <br />34 <br />40 <br />73% <br />(1) <br />2 <br />Office 102B <br />Flowhood <br />RG-1 <br />6" <br />1.00 <br />55 <br />37 <br />39 <br />71 % <br />3 <br />Office 102C <br />Flowhood <br />RG-1 <br />6" <br />1.00 <br />55 <br />46 <br />41 <br />75% <br />4 <br />Office 102D <br />Flowhood <br />RG-1 <br />6" <br />1.00 <br />55 <br />63 <br />42 <br />76% <br />5 <br />Office 102F <br />Flowhood <br />RG-1 <br />6" <br />1.00 <br />55 <br />67 <br />47 <br />85% <br />6 <br />Office 102E <br />Flowhood <br />RG-1 <br />6" <br />1.00 <br />55 <br />56 <br />44 <br />80% <br />7 <br />Lounge 109 <br />Flowhood <br />RG-1 <br />6" <br />1.00 <br />55 <br />67 <br />43 <br />78% <br />8 <br />Hallway <br />Flowhood <br />RG-1 <br />14" <br />1.00 <br />685 <br />645 <br />564 <br />82% <br />(This Page) Total Airflow <br />1070 <br />1015 <br />860 <br />80% <br />Test Notes <br />Note (1) The volume damper is full open. <br />Page 15 of 49 <br />