GRILLES, REGISTERS, & DIFFUSERS SCHEDULE <br />EQUIP TAG <br />TYPE <br />FACE SIZE IN. <br />MOUNTING TYPE <br />DAMPER REQUIRED <br />MATERIAL <br />MANUFACTURER & MODEL... <br />PLAN INFO <br />SPECIFIC NOTES <br />SD-1 <br />LOUVER FACE CEILING DIFFUSER <br />24' x 24" <br />TILE CLG <br />YES <br />STEEL <br />KRUEGER 1400 <br />NECK / CFM <br />- <br />RG-1 <br />PERFORATED FACE CEILING RETURN GRILLE <br />24' x 24' <br />TILE CLG <br />SEE NOTES <br />STEEL <br />KRUEGER 6490/6690 <br />NECK /CFM* <br />1, 2, 3 <br />GENERAL NOTES: <br />1. SEE PLANS FOR NECK SIZE <br />2. ALL GROG REQUIRING DAMPERS SHALL BE EQUIPPED WITH A REMOTE BALANCING DAMPER THAT IS ADJUSTABLE THROUGH THE GIRD FACE OR ANOTHER APPROVED <br />LOCATION UNLESS SUPPLIED FROM AN ACCESSIBLE TAKE -OFF WITH LOCKING DAMPER. FACE DAMPERS SUCH AS INTEGRAL OBDG ARE NOT ACCEPTABLE. <br />3. VERIFY GIRD FINISH AND CLGNVALUSILUFLOOR MOUNTING TYPE WITH ARCHITECT FOR EACH APPLICATION PRIOR TO ORDERING. <br />4. PROVIDE 4-WAY THROW FOR DIFFUSERS UNLESS OTHERWISE SHOWN ON PLANS. <br />5. PROVIDE MANUFACTURERS ROUND TO RECTANGULAR ADAPTIVE COLLAR FOR DIFFUSERS AND GRILLES AS REQUIRED, MATCH DUCT SIZE AND TYPE <br />6. MATERIAL SHALL BE STEEL UNLESS OTHERWISE INDICATED OR SPECIFIED. MATERIAL SHALL BE SUITABLE FOR INSTALLED ENVIRONMENT. FOR WET <br />LOCATIONS SUCH AS LOCKER ROOMS, RESTROOMS, SHOWER ROOMS, KITCHENS, POOL ROOMS, ETC PROVIDE ALUMINUM IN LIEU OF THE STEEL NOTED. <br />7. WHERE MULTIPLE DIFFUSERS ARE LOCATED IN A SINGLE ROOM; FACE SIZES SHALL BE THE SAME UNLESS NOTED OTHERWISE. <br />8. AFTER INSTALLATION, ADJUST DIFFUSERS, REGISTERS AND GRILLES TO AIR PATTERNS INDICATED, OR AS DIRECTED, BEFORE STARTING AIR BALANCING. <br />9. CONTRACTOR SHALL ENSURE ALL NEW GRUS PROVIDED MATCH THOSE WHICH ARE EXISTING IN TERMS OF FINISH AND VISUAL APPEARANCE. <br />* WHERE CFM IS INDICATED ON PLANS FOR RETURN AND TRANSFERS, BALANCE TO AIRFLOW INDICATED. <br />SPECIFIC NOTES: <br />1. PROVIDE DAMPER FOR A DUCTED RETURN/TRANSFER AIR SYSTEM THAT REQUIRES AIR BALANCE AT RETURWTRANSFER OPENINGS AS INDICATED BY <br />AIRFLOW (CFMs) ON DRAWINGS. <br />2. AS IDENTIFIED ON THE PLANS PROVIDE 12"x24" FACE FOR 10"x22" NECKS, PROVIDE 24"x24" FACE FOR 22"x22" NECKS <br />3. PROVIDE BACKPAN WHERE CONNECTED TO DUCT OR SOUND BOOT; WHERE NO DUCT OR SOUND BOOT IS PRESENT PROVIDE PERFORATED PANEL ONLY. <br />DUCTWORK INSULATION (WRAP & LINER) SCHEDULE <br />EXPOSED <br />CONCEALED <br />SYSTEM <br />LOCATION <br />SERVICE <br />NOTE1 <br />MINIMUM R-VALUE <br />SPECIFIC NOTES <br />RECTANGULAR <br />ROUND/OVAL <br />RECTANGULAR <br />ROUND/OVAL <br />MAIN <br />1-1/2" LINER <br />1-1/2" LINER <br />1-1/2" LINER <br />1-1/2" LINER <br />R-6 <br />SUPPLYAIR <br />INDOOR <br />MAIN TO TERMINAL <br />1-1/2" LINER <br />- <br />1-1/2" LINER <br />2" WRAP <br />R-6 <br />TERMINAL TO GIRD <br />1-1/2" LINER <br />- <br />1-1/2" LINER <br />2" WRAP <br />R-6 <br />MAIN <br />1" LINER <br />1" LINER <br />1" LINER <br />1" LINER <br />R-6 <br />RETURNAIR <br />INDOOR <br />BRANCH <br />1" LINER <br />- <br />1" LINER <br />1-1/2-WRAP <br />R-6 <br />GENERAL NOTES: <br />1) MINIMUM R-VALUE BASED ON 2018 WSEC REQUIREMENTS. <br />2) DUCT SIZES SHOWN ARE INSIDE CLEAR DIMENSIONS. LINER, WHERE USED, WILL NEED TO BE FACTORED INTO THE DUCT SIZE. <br />3) THE INSULATION THICKNESS GIVEN MEETS OR EXCEEDS THE REQUIRED R-VALUE FOR THE BASIS OF DESIGN (JOHNS MANVILLE). INSTALLED PRODUCT SHALL <br />MEET OR EXCEED THE LISTED R-VALUE; INSULATION THICKNESS AND CORRESPONDING DUCT SIZE (FOR LINER) SHALL BE INCREASED FOR ALTERNATES THAT <br />CANNOT MEET THIS THICKNESS TO PERFORMANCE CONDITION. <br />4) R-VALUES FOR WRAP SHALL BE SHOWN USING THEIR INSTALLED CONDITION RATING AS NOTED ON THE MANUFACTURER'S SPECIFICATION SHEET. <br />5) JACKET (PVC OR METAL) SHALL BE INSTALLED AS REQUIRED BY THE SPECIFICATIONS. <br />6) FLEXIBLE DUCT SHALL BE AS NOTED IN THE "AIR DUCT ACCESSORIES" SPECIFICATION. <br />7) DUCT WRAP IS ALLOWED TO BE BLANKET OR BOARD; CONTRACTOR OPTION. <br />8) MULTIPLE LAYERS OF WRAP OR LINER TO ACHIEVE TOTAL R-VALUE ARE ACCEPTABLE IF INSTALLED PER MANUFACTURER'S INSTRUCTIONS. <br />DEFINITIONS: <br />EXPOSED DUCT: DUCT THAT IS EXPOSED TO VIEW IN OCCUPIED OR UNOCCUPIED SPACES THAT ARE CONDITIONED. <br />CONCEALED DUCT: DUCT THAT IS CONCEALED IN CHASES, SHAFTS, CEILING PLENUMS OR OTHER ASSEMBLY WITHIN THE INSULATED BUILDING ENVELOPE. <br />MAIN DUCT: DUCT FROM THE AIR HANDLING UNIT TO FINAL TERMINAL TAKEOFF. <br />MAIN TO TERMINAL DUCT: THIS IS A BRANCH DUCT; TYPICALLY THE DUCT FROM THE MAIN TAKEOFF TO THE TERMINAL (VAV BOX OR EQUIVALENT). <br />TERMINAL TO GIRD DUCT: THIS IS A BRANCH DUCT DOWNSTREAM OF THE TERMINAL (VAV BOX, HEAT PUMP, FAN COIL OR EQUIVALENT). <br />OUTSIDE AIR TEMPERED: TEMPERED OUTSIDE AIR IS AIR THAT IS HEATED OR COOLED TO WITHIN 10 DEG F OF THE SPACE/SURROUNDING TEMPERATURE. <br />INDOOR: DUCT LOCATIONS WITHIN THE INSULATED BUILDING ENVELOPE. <br />PLUMBING FIXTURE AND EQUIPMENT SCHEDULE <br />PLAN <br />FIXTURE <br />ICC/ANSI A117.1 <br />MANUFACTURER <br />SERIES <br />TRIM <br />SERIES <br />SUPPLIES <br />TRAP / <br />DRAIN <br />CW <br />HW / <br />WASTE <br />VENT <br />WATER <br />NOTES / REMARKS <br />CODE <br />COMPLIANT# <br />WASTE <br />TEPID <br />CONSUMPTI... <br />BFP-1 <br />REDUCED PRESSURE <br />- <br />FEBCO <br />LF860/LF86OU <br />--- <br />1/2"-2" <br />INTEGRAL <br />-- <br />-- <br />SEE <br />- <br />- <br />- <br />- <br />1,W/MANUFACTURER'S MATCHING <br />PRIN. BACKFLOW PREVENTOR <br />WILKINS <br />375 <br />PLANS <br />AIR GAP DRAIN <br />GDA <br />GARBAGE <br />IN -SINK- <br />BADGERS <br />--- <br />- <br />-- <br />--- <br />INTEGRAL <br />-- <br />- <br />1 1/2" <br />- <br />- <br />ELECT: 1/2 HP, 115/1v, 6.3 FLA <br />DISPOSAL <br />ERATOR <br />OB-1 <br />OUTLET BOX <br />SIOUX CHIEF <br />6964 <br />--- <br />- <br />INTEGRAL <br />P-TRAP <br />--- <br />1/2" <br />112" <br />2" <br />1 1/2" <br />- <br />3, 4, 5 <br />BEVERAGE DISPENSER <br />ZURN <br />WM2961 <br />OB-2 <br />OUTLET BOX <br />SIOUX CHIEF <br />6964 <br />--- <br />- <br />INTEGRAL <br />--- <br />-- <br />- <br />- <br />2" <br />1 112" <br />- <br />5 <br />DRAIN <br />ZURN <br />WM2961 <br />SK-1 <br />SS SINK SINGLE <br />GLACIER BAY <br />VT3322TA2PA1 <br />INTEGRAL <br />W/STOPS <br />OFFSET <br />LKAD35 <br />112" <br />1/2" <br />2" <br />1 112" <br />1.5 GPM <br />2 <br />OFF -CENTER DRAIN, CT <br />9" DEPTH <br />P-TRAP <br />SA-1 <br />SHOCK ABSORBER <br />- <br />JOSAM <br />75000 <br />-- <br />- <br />-- <br />-- <br />-- <br />SEE <br />SEE <br />-- <br />- <br />- <br />1 <br />(WTR-HAMMER ARRESTERS) <br />ZURN <br />Z1700 <br />PLANS <br />PLANS <br />WMV-1 <br />THERMAL MIXING <br />WATTS <br />LFUSG-B <br />-- <br />- <br />-- <br />-- <br />-- <br />3/8" <br />3/8" <br />-- <br />- <br />- <br />INSTALL DOWNSTREAM OF <br />VALVE, FIXTURE <br />ZURN <br />ZW3870XLT <br />FIXTURE STOPS <br />LEGEND: CH = CHILD HEIGHT, CM = CEILING MOUNTED, CP = CHROME PLATED, CT = COUNTERTOP, FM = FLOOR MOUNTED, FV = FLUSH VALVE, PA = PRESSURE ASSIST, SS = STAINLESS STEEL, <br />TP = PROVIDE TRAP PRIMER (TP-1) ADJACENT TO FIXTURE, WM = WALL MOUNTED (PROVIDE WITH A FLOOR MOUNTED CONCEALED CARRIER), UCT = UNDER COUNTERTOP <br />DOMESTIC WATER HEATER SCHEDULE <br />HEATING CAPACITY <br />ELEC MOTOR DATA <br />ITEM <br />SERVICE <br />TANK CAP. [GAL] <br />OPERATING WEIGHT [LBS] <br />MANUFACTURER &MODEL <br />NOTES <br />CONTROLS <br />IOUTPUT [kW] <br />RECOVERY [GPH] <br />TEMP RISE [°FJ <br />Fa <br />V-PH <br />NO <br />EWH-1 <br />BREAK 108 <br />20 <br />2 <br />8 <br />100 <br />9.6 <br />1 208-1 <br />225 <br />AO SMITH DEL-20 <br />1.2 <br />INTEGRAL <br />GENERAL NOTES (APPLY TO ALL PRODUCT): <br />1) CONTROLS: INTEGRAL = INTERNAL CONTROLS PROVIDED WITH UNIT, DOC = DIRECT DIGITAL CONTROLS BY DIV 23, OTHER = SEE NOTES <br />2) VENT TYPE: DV = DIRECT VENT, AT = ATMOSPHERIC, FA = FAN ASSISTED, FD = FORCED DRAFT <br />3) INSTALL WATER HEATER AND PIPING PER SELECTED MANUFACTURER'S WRITTTEN INSTRUCTIONS <br />4) INSTALL BAROMETRIC DAMPER ON FLUE IF REQUIRED BY THE WATER HEATER MANUFACTURER. <br />5) WATER HEATER EFFICIENCIES NOTED ARE AT THE LISTED TEMPERATURE RISE NOTED IN THE SCHEDULE. <br />SPECIFIC NOTES (APPLY WHERE NOTED): <br />1) ALL ELEMENTS RUN SIMULTANEOUSLY. kW AND AMPERAGE LISTED ARE FOR ALL ELEMENTS BEING ON. <br />2) PROVIDE SINGLE POINT ELECTRICAL POWER CONNECTION WITH FACTORY INSTALLED FUSED DISCONNECT FOR HEATING ELEMENTS AND CONTROLS. <br />1. WHERE FIXTURE/EQUIPMENT MODEL NUMBERS ARE GIVEN THESE ARE FOR REFERENCE ONLY. WRITTEN # WHERE NOTED THE PLUMBING FIXTURE, EQUIPMENT AND ASSOCIATED ACCESSORIES <br />SPECIFICATION REQUIREMENTS AND SCHEDULE NOTES HOLD PRESIDENCE. THE MORE STRIGENT SHALL APPLY. SHALL BE ICC/ANSI Al 17.1 (ADA) COMPLIANT. EXPOSED CW, HW AND W PIPING ALONG WITH <br />2. SEE ARCHITECTURAL DWGS FOR MOUNTING HEIGHTS ON ALL WALL MOUNTED FIXTURES/EQUIPMENT, MIXING VALVE SHALL BE INSULATED. PIPING WITHIN CASEWORK THAT OPENS FOR FIXTURE <br />ARCHITECTURAL DRAWINGS TAKE PRECEDENCE OVER ANY VALUES WITHIN THIS SCHEDULE. USE IS CONSIDERED EXPOSED. <br />3. THE MINIMUM WASTENENT PIPE SIZE FOR BURIED PIPE SHALL BE 2". <br />4. ALL ACCESIBLE FIXTURES SHALL COMPLY WITH ICC/ANSI A117.1 (ADA), REFERENCE ARCH DWGS FOR SPECIFIC LOCATIONS. SEE NOTE # <br />5. ALL FIXTURES AND EQUIPMENT SHALL BE INSTALLED PER THE MANUFACTURER'S WRITTEN INSTALLATION INSTRUCTIONS. <br />1. EQUIPMENT AND/OR ISOLATION VALVE SHALL BE CONCEALED (WITHIN ADJACENT WALL OR WITHIN CASEWORK). WHERE LOCATED IN WALUCEILING COORDINATE FINAL DEVICE AND ACCESS DOOR LOCATION WITH ARCHITECT. <br />2. PROVIDE WITH ASSE 1070 RATED THERMAL MIXING VALVE (WMV-1) LOCATED DOWNSTREM OF FIXTURE STOPS UNLESS SERVED FROM AN ASSE 1070 RATED GROUP -FIXTURE THERMAL MIXING VALVE. <br />3. PROVIDE SHOCK ARRESTOR(S) ON HW, CW AND TEPID SUPPLIES. <br />4. PROVIDE AN ASSE 1022 BEVERAGE DISPENSING BACKFLOW PREVENTOR (BFP-1) FOR EACH BEVERAGE DISPENSER (COFFEE, SODA, ETC..) OR ICE MACHINE PRIOR TO CONNECTION/OUTLET BOX. <br />5. PROVIDE FIRE RATED BOX WHERE OUTLET BOX IS LOCATED IN A RATED WALL. <br />VRF FAN COIL UNIT SCHEDULE <br />E.S.P <br />CLG CAP <br />HTG <br />CAPACITIES MOTOR DATA <br />OF <br />UNIT <br />FCU TAG <br />CONDENSING UNIT <br />AREA(S) SERVED <br />IN. W.C. <br />CAP <br />WT MANUFACTURER <br />& MODEL # <br />SIZE <br />NOTES <br />CONTROLS <br />OSA <br />TOTAL <br />SENS <br />CLG EAT <br />HTG EAT <br />V-PH <br />MCA <br />MOCP <br />STRTR <br />DB <br />WB <br />DB <br />CFM <br />CFM <br />ALT. <br />MBH <br />MBH <br />MBH <br />LBS <br />TONS <br />FCU-1 <br />(E) ODU-1 <br />BREAK, SMALL CONFERENCE ROOMS <br />1800 <br />110 <br />0.5 <br />40.7 <br />38.9 <br />16.2 <br />75.4 <br />61.2 <br />67.3 <br />208/230-1 <br />7.2 <br />15 <br />INT <br />165 CARRIER <br />40VMV054A-3 <br />41/2 <br />ALL <br />TSTAT <br />FCU-2 <br />(E) ODU-1 <br />BRANCH SUPPORT, OFFICES, EQUIP/SUPPLY <br />1070 <br />155 <br />0.5 <br />22.8 <br />20.3 <br />14.4 <br />75.9 <br />61.4 <br />63.5 <br />208/230-1 <br />5.0 <br />15 <br />INT <br />130 CARRIER <br />40VMM03OA-3 <br />21/2 <br />ALL <br />TSTAT <br />FCU-3 <br />(E) ODUA <br />WELCOME, MEDIUM CONFERENCE <br />1070 <br />95 <br />0.5 <br />21.4 <br />19.9 <br />13.1 <br />75.5 <br />61.2 <br />66.0 <br />2081230-1 <br />5.0 <br />15 <br />INT <br />130 CARRIER <br />40VMM03OA-3 <br />21/2 <br />ALL <br />TSTAT <br />FCU-4 <br />(E)ODUA <br />LARGE CONFERENCE <br />430 <br />80 <br />0.5 <br />9.0 <br />7.7 <br />6.0 <br />76.1 <br />61.5 <br />61.7 <br />2081230-1 <br />3.2 <br />15 <br />INT <br />130 CARRIER <br />40VMM012A-3 <br />1 <br />ALL <br />TSTAT <br />NOTES: 1. UNIT SHALL BE CONNECTED TO EXISTING MULTIPORT DISTRIBUTION CONTROLLER AS REQUIRED BY THE MANUFACTURER AND CONNECTED IN ACCORDANCE WITH THE MANUFACTURER'S INSTRUCTIONS. <br />2. COORDINATE WITH LANDLORD AND BUILDING ENGINEER REGARDING PIPING AND DETAILS FOR EXISTING MULTIPORT DISTRIBUTION CONTROLLER. <br />3. PROVIDE REFRIGERANT PIPING INSTALLED PER THE MANUFACTURES INSTRUCTION AND BY A FACTORY CERTIFIED INSTALLER. <br />4. PROVIDE WITH INTEGRAL CONDENSATE PUMP AND CONDENSATE OVERFLOW SWITCH. REFER TO PLUMBING DRAWINGS REGARDING CONDENSATE DRAIN ROUTING. <br />5. PROVIDE WITH FACTORY CONTROLS, WALL -MOUNTED WIRED CONTROLLER; COORDINATE WITH TEMPERATURE CONTROLS PROVIDED WITH BASE BUILDING SYSTEMS. <br />6. ALL REQUIRED FIELD WIRING AND PROGRAMMING BY THE MANUFACTURER OR A CERTIFIED INSTALLER, COORDINATE WITH TEMPERATURE CONTROLS CONTRACTOR. <br />7. HEATING CAPACITY LISTED IS MINIMUM REQUIRED. SYSTEM SHALL BE SIZED TO ACCOUNT FOR THE REQUIRED DE -RATE ASSOCIATED WITH ALTITUDE, PIPING LENGTH, AND AN AMBIENT TEMPERATURE <br />OF 20 DEGREES F (WINTER) AND 90 DEGREES F (SUMMER). <br />8. UNIT SHALL BE PROVIDED WITH SINGLE POINT POWER CONNECTION INCLUDING CONTROLS, FAN, AND INTEGRAL CONDENSATE PUMP. <br />9. CONTACT JEFF MILLER AT LOHMILLER COMPANY (303) 598-8413 FOR ADDITIONAL PRODUCT INFORMATION AND ORDERING. <br />PLUMBING INSULATION SCHEDULE <br />PIPE SIZES <br />SYSTEM <br />INSULATION TYPE <br />FLUID TEMPERATURE RANGE <br />SPECIFIC NOTES <br /><1" 1"to <br />1-I N' <br />1-1Y2" to 3" <br />4" to 8" <br />8" and Larger <br />DOMESTIC COLD WATER <br />FLEXIBLE ELASTOMERIC OR GLASS FIBER PREFORMED PIPE INSULATION <br />- <br />1'.. <br />1/2" <br />1" <br />1" <br />1" <br />1 <br />141 TO 200 DEG F <br />1-1/2" <br />1-1/2" <br />2" <br />2" <br />2" <br />DOMESTIC HOT WATER AND DOMESTIC HOT WATER RECIRC <br />GLASS FIBER OR MINERAL FIBER PREFORMED PIPE INSULATION <br />< 140 DEG F <br />1" <br />1" <br />1-1/2" <br />1-112" <br />1-112" <br />GENERAL NOTES: <br />1) FOR PIPING EXPOSED TO THE OUTSIDE AMBIENT CONDITIONS OR PIPING PROVIDED WITH HEAT TRACE, INCREASE THICKNESS OF INSULATION BY 1/2". <br />2) FOR PIPING EXPOSED TO THE OUTSIDE AMBIENT CONDITIONS PROVIDE PROTECTIVE JACKET (SEE SPECIFICATIONS). <br />3) ALL INSULATION EXPOSED TO UV CONDITIONS SHALL BE PROTECTED IN ACCORDANCE WITH THE MANUFACTURERS WRITTEN INSTRUCTIONS. <br />4) MINIMUM THERMAL CONDUCTIVITY "k" VALUE FOR FLEXIBLE ELASTOMERIC SHALL BE 0.27 AT 75 DEG. F <br />5) MINIMUM THERMAL CONDUCTIVITY "k" VALUE FOR GLASS FIBER SHALL BE 0.23 AT 75 DEG. F <br />SPECIFIC NOTES: <br />1) PROVIDE PIPE INSULATION WICKING SYSTEM ON ALL EXISTING SYTEMS THAT ARE OPERATIONAL DURING INSTALLATION. <br />LAWRENCE <br />GROUP <br />St. Louis <br />319 North 4th Street <br />Suite 1000 <br />St. Louis, Missouri 63102 <br />(314)231-5700 <br />PmjeGTeam <br />GENERAL CONTRACTOR: <br />To Be Determined <br />PROFESSIONAL ENGINEER: <br />M E G <br />IMEG <br />7600 E Orchard Road, Suite 250-S <br />Greenwood Village, CO 80111 <br />Phone: 303.796.6000 <br />IMEG Project No: 24000280.07 <br />­­­1 S.1 <br />(^V' /`) <br />l^W <br />i _V <br />O O-) <br />W <br />T <br />v � <br />-U <br />C N `^ <br />i <br />it) > <br />U Q <br />0 ` L <br />0 _0 I I I � � �O <br />m W C N (M <br />to � �� <br />The Professional Architect's seal eMd to this cheat <br />applies only to the material and items shmn on this <br />sheet. All drawings, trots dume ocnts rot <br />'ibilirg this seal shallnot be considered prepared by <br />thia arohitect, and this architect aVnawy disclaims any <br />and all respomibility far such plans, drawing, or <br />doaments not exhibiting this seal. <br />This drawing and detail, on it are the axle property of the <br />architect and may be uwd for this specific project only. <br />It shall not be maned, copied or reproduced, in whole or <br />part or for any other purpose or project with- the <br />written consent of the erchXect. <br />No. Description Data <br />shear rule. <br />MECHANICAL AND <br />PLUMBING <br />SCHEDULES <br />Prged Number'. Sheer Number'. <br />2024906.011 <br />Drawn S <br />MSK A <br />lease Dace: 4 <br />MARCH 07, 2024 <br />