#r"V:F <br /> MacDonald-Miller <br /> FACILITY SOLUTIONS <br /> Energy Recovery Unit <br /> PROJECT: Terra Power Bldg B Laser Lab DATE: 6/25/2024 <br /> LOCATION: Everett,WA CONTACT: Mikhail Gadomskiy <br /> PROJECT#: 72247025 <br /> SYSTEM/UNIT: ERV-01/VAV-1-1 Tested By: Mikhail Gadomskiy <br /> Date: 6/20/2024 <br /> Unit Data Term Box Test Data <br /> Manufacturer Nailor Max Setpoint 1710 <br /> Model Number D30RE Min Setpoint 700 <br /> Serial Number 783463-.01 <br /> Box Inlet Size 12" Term Box Test Data <br /> K Factor 1 Design Actual <br /> Primary Max CFM 1710 CFM 1730 CFM <br /> Primary Min CFM 700 CFM 710 CFM <br /> Electric Heat <br /> Rated KW 6 KW <br /> Design DT 27 Deg F <br /> Measured DT 26.5 Deg F <br /> Design CFM 700 CFM <br /> Measured CFM 705 CFM <br /> ERV-01/VAV-1-1 Supply Outlet Summary <br /> System/Unit Type of Outlet Size AK Design Prelim %Pre Final %Final T/O <br /> Reading Type Factor Reading Reading Reading <br /> Outlet-01 Flowhood CD 16" 1 855 745 87 870 102 T <br /> Outlet-02 Flowhood CD 16" 1 855 690 81 860 101 O <br /> Totals: - - - 1710 1435 84 1730 101 - <br /> SYSTEM/UNIT: ERV-01/VAV-M1 Tested By: Mikhail Gadomskiy <br /> Date: 6/20/2024 <br /> Unit Data Term Box Test Data <br /> Manufacturer Nailor Max Setpoint 300 <br /> Model Number D30RE Min Setpoint 300 <br /> Serial Number 783463-2.01 <br /> Box Inlet Size 6" Term Box Test Data <br /> K Factor 1 Design Actual <br /> Primary Max CFM 300 CFM 295 CFM <br /> Primary Min CFM 300 CFM 295 CFM <br /> Electric Heat <br /> Rated KW 3 KW <br /> Design DT 31.5 Deg F <br /> Measured DT 32.1 Deg F <br /> Design CFM 300 CFM <br /> Measured CFM 295 CFM <br /> ERV-01/VAV-M1 Supply Outlet Summary <br /> System/Unit Type of Outlet Size AK Design Prelim %Pre Final %Final T/O <br /> Reading Type Factor Reading Reading Reading <br /> Outlet-01 Flowhood CD 101, 1 300 380 127 295 98 T/O <br /> Totals: - 300 380 1 127 295 98 - <br /> MacDonald-Miller <br /> Page 10 of 14 <br />