Laserfiche WebLink
,or"117 <br /> MacDonald-Miller <br /> FACILITY SOLUTIONS <br /> Energy Recovery Unit <br /> PROJECT: Terra Power Bldg B Laser Lab DATE: 6/25/2024 <br /> LOCATION: Everett,WA CONTACT: Mikhail Gadomskiy <br /> PROJECT#: 72247025 <br /> SYSTEM/UNIT: ERV-01/VAV-M2 Tested By: Mikhail Gadomskiy <br /> Date: 6/20/2024 <br /> Unit Data Term Box Test Data <br /> Manufacturer Nailor Max Setpoint 300 <br /> Model Number D30RE Min Setpoint 300 <br /> Serial Number 783463-3.01 <br /> Box Inlet Size 6" Term Box Test Data <br /> K Factor 1 Desian Actual <br /> Primary Max CFM 300 CFM 310 CFM <br /> Primary Min CFM 300 CFM 310 CFM <br /> Electric Heat <br /> Rated KW 3 KW <br /> Design DT 31.5 Deg F <br /> Measured DT 30.5 Deg F <br /> Design CFM 300 CFM <br /> Measured CFM 310 CFM <br /> ERV-01/VAV-M2 Supply Outlet Summary <br /> System/Unit Type of Outlet Size AK Design Prelim %Pre Final %Final T/O <br /> Readinq Type Factor Reading Reading Readin <br /> Outlet-01 Flowhood CD 101, 1 300 270 90 310 103 T/O <br /> Totals: - - 300 270 1 90 310 103 - <br /> MacDonald-Miller <br /> Page 11 of 14 <br />