Laserfiche WebLink
IVNEUDORFER •''"''� <br /> ENGINEERS E B� <br /> AN Cter-a COMDAN, <br /> Fan Coil Unit - DX <br /> PROJECT: St. Mary Magdalen Elementary HVAC Project DATE: 8/15/2024 <br /> LOCATION: Everett,WA CONTA Kami Valentine <br /> PROJECT#: 2024-0871 AUTHO <br /> 1 Disconnect switch properly operates Pass KV 8/8/24 8:59 <br /> 2 Electrical connections complete,unit Pass KV 8/8/24 8:59 <br /> energized <br /> OPT -Mechanical - FCU-02 <br /> Verification Response Notes By Date/Time <br /> 1 Condensate Pump is operating NA KV 8/8/24 8:59 <br /> without any issues <br /> 2 Fan belt tension&condition good NA KV 8/8/24 8:59 <br /> 3 Fan have no unusual noise or Pass KV 8/8/24 8:59 <br /> vibration <br /> 4 Fan rotation correct Pass KV 8/8/24 8:59 <br /> 0.1 PreFunctional Performance - FCU-02 Functional Performance Test <br /> Verification Response Notes By Date/Time <br /> 1 JPFPT Completed Pass KV 8/7/24 10:58 <br /> 2 IStartup Completed Pass KV 8/8/24 9:00 <br /> 1.0 Setpoints -FCU-02 Functional Performance Test <br /> Verification Response Notes By Date/Time <br /> 1 Building occupancy schedule= <br /> Monday to Sunday,6:OOAM to Pass KV 8/8/24 8:59 <br /> 6:OOPM <br /> 2 Heating/Cooling Temperature <br /> Setpoint=adjustable between 67°F Pass KV 8/8/24 8:59 <br /> to 76°F <br /> 3 Occupied Heating/Cooling <br /> Temperature Setpoint=71 OF to 73F. <br /> Uccupied Heating/Cooling Pass KV 8/8/24 8:59 <br /> Temperature Setpoint=650F to 80OF <br /> 1.1 As-Found Conditions - FCU-02 Functional Performance Test <br /> Verification Response Notes By Date/Time <br /> 1 JAs Found Room Temp 73°F KV 8/7/24 10:58 <br /> 2.0 Heating -FCU-02 Functional Performance Test <br /> Verification Response Notes By Date/Time <br /> 1 'TEST PROCEDURE,Set the <br /> heating setpoint to 50F above zone <br /> temperature <br /> 1. <br /> 2 Unit is ON in Heating mode Pass KV 8/7/24 10:58 <br /> 3 DAT increases.Record DAT 94°F KV 8/7/24 10:58 <br /> 2.1 Cooling - FCU-02 Functional Performance Test <br /> Verification Response Notes By Date/Time <br /> 1 TEST PROCEDURE,Set the cooling <br /> setpoint to 50F below zone <br /> temperature <br /> 2 Unit is ON in Cooling mode Pass KV 8/7/24 10:58 <br /> 3 DAT decreases.Record DAT 63°F KV 1 8/7/24 10:58 <br />