<br /> SER
<br /> PERI ANENTE
<br /> Project
<br /> Kaiser Permanente Everett
<br /> MOB Backfill
<br /> PLUMBING FIXTURES 2018 WASHINGTON STATE ENERGY CODE COMPLIANCE
<br /> 2929 PINE STREET
<br /> TAG FIXTURE TYPE BASIS OF DESIGN VALVE/FAUCET/TRIM TYPE BASIS OF DESIGN FLOW CONNECTIONS ELEC NOTES 1. C103.&OPERATIONANDMAINTENANCEMANUALSSHALLBEPROVIDEDTOTHEOWNERASSPECIFIED. EVERETT,WA 98201
<br /> CW(IN) HW(IN) W(IN) V(IN) 2. C103.6.1-RECORD DRAWING SHALL BE PROVIDED TO THE OWNER.THE DRAWINGS SHALL INDICATE THE LOCATION
<br /> LAVATORY LAVATORY FAUCET PROVIDE WITH CONCEALED ARM CARRIER,GRID AND PERFORMANCE DATA OF EQUIPMENT,GENERAL CONFIGURATION OF DUCTWORK AND PIPING DISTRIBUTION Prepared for
<br /> S,INCLUDING FLOWRATESASA
<br /> LV1 WALL MOUNTED,VITREOUS CHINA,LESS OVERFLOW,3 HOLES, AM STD0954.904EC MANUAL TYPE,4-INCH WRISTBLADE HANDLES,CERAMIC CARTRIDGES, 802-V HIIE 6XKABCP 0.5GPM 1/2 1/2 1-1/2 1-1/2 - STRAICAGO NER,AND VITREOUS CHINA PIPE SHROUD, NY THE kTEMPERATU ECONTROLSEQUENCES.UM.SORSETPOINTSOFSDEGREESASREQUIREDORASDESCRIBED KAISER FOUNDATION
<br /> 4"CENTERS,NOMINAL 21"x 18",ADA COMPLIANT CHROME PLATED,LAMINAR NON-AERATING OUTLET,ADA COMPLIANT REFER TO ARCH DINGS FOR MOUNTING HEIGHT
<br /> 3. C403.10.3-ALL PIPING SHALL BE INSULATED AS REQUIRED BY TABLE C403.2.90F THE WSEC AND AS DESCRIBED INTHE HEALTH PLAN, INC.
<br /> SINK SINK FAUCET PROVIDE WITH GRID STRAINER AND ASSE 1070 PROJECT MANUAL.
<br /> SK1 COUNTER MOUNTED,SINGLE BOWL,1 HOLE,18 GA STAINLESS-STEEL, JUST SL-ADA-1921-A-GR SENSOR TYPE,5-1/4-INCH GOOSENECK,1-HOLE,SELF-SUSTAINING POWER CHICAGO 116.933.AB.1 1.5 GPM 1/2 1/2 2 2 - NATIONAL FACILITIES SERVICES
<br /> CENTER DRAIN,NOMINAL 19"x 21"x 6.5",ADA COMPLIANT SYSTEM,CHROME PLATED,LAMINAR NON-AERATING OUTLET,ADA COMPLIANT TEMPERATURE MIXING VALVE(SET AT 110 DEG F) TABLE C403.10.3 POST OFFICE BOX 12916
<br /> MINIMUM PIPE INSULATION THICKNESS(in inches)e,' OAKLAND,CA 94604
<br /> INSULATION CO NDUCTIVITY PIPE DIAMETER
<br /> WATER CLOSET PROVIDE WITH OPEN FRONT ELONGATED TOILET
<br /> FLUSH VALVE 1.6 GPF DN TEMPERATURE CONDUCTIVITY
<br /> , , , MEAN RATING <i" 1'T01-1/2" 1-112"T04' 4"T08" 28"
<br /> WC1 WALL HUNG,REAR OUTLET,ELONGATED BOWL,VITREOUS CHINA,TOP AM STD 2257.101 MANUAL DUAL FLUSH TYPE DIAPHRAGM CHROME PLATED ADA COMPLIANT SLOAN WES 111-1.6/1.1 1.1 GPF UP 1 - 4 2 - SEAT,REFER TO ARCH DWGS FOR MOUNTING 7 BTU'IIT(WFT-'F)" TEMP°F INSULATION THICKNESS
<br /> SPUD,1.1 GPF TO 1.6 GPF,ADA COMPLIANT HEIGHT
<br /> ABOVE 350 .32-.34 250 4.5 5.0 5.0 5.0 5.0
<br /> 251-350 .29-.32 200 3.0 4.0 4.5 4.5 4.5
<br /> 201-250 .27-.30 150 2.5 2.5 2.5 3.0 3.0
<br /> 141-200 .25-.29 125 1.5 1.5 2.0 2.0 2.0
<br /> 105-140 .21-.28 100 1.0 1.0 1.5 1.5 1.5
<br /> 40-60 .21-.27 75 0.5 0.5 1.0 1.0 1.0
<br /> BELOW40 .20-.26 75 01.5 1.01 1.0 1.0 1.10
<br /> NOTE:PIPING INSULATION MEETS OR EXCEEDS WSEC:
<br /> a. FOR PIPING SMALLER THAN 1-1/2 INCH(38 MM)AND LOCATED IN PARTITIONS WITHIN CONDITIONED SPACES, ,
<br /> REDUCTION OF THESE THICKNESSES BY 1 INCH(25 MM)SHALL BE PERMITTED(BEFORE THICKNESS ADJUSTMENT
<br /> REQUIRED IN FOOTNOTE b)BUT NOT TO A THICKNESS LESS THAN 1 INCH(25 MM).
<br /> b. FOR INSULATION OUTSIDE THE STATED CONDUCTIVITY RANGE,THE MINIMUM THICKNESS(T)SHALL BE
<br /> DETERMINED AS FOLLOWS:
<br /> T=r{(1+tlr)
<br /> K/k-1)
<br /> WHERE:
<br /> T=MINIMUM INSULATION THICKNESS,
<br /> r=ACTUAL OUTSIDE RADIUS OF PIPE, HeIInlUth,Obata&KSSSabaUfil,Inc.
<br /> t=INSULATION THICKNESS LISTED IN THE TABLE FOR APPLICABLE FLUID TEMPERATURE AND PIPE SIZE, Hell Third bata&,Suite aum
<br /> K=CONDUCTIVITY OF ALTERNATE MATERIAL AT MEAN RATING TEMPERATURE INDICATED FOR THE APPLICABLE
<br /> 315
<br /> FLUID TEMPERATURE(Btu x iNh x W x°F)AND Seattle,WA 98101 USA
<br /> k=THE UPPER VALUE OF THE CONDUCTIVITY RANGE LISTED IN THE TABLE FOR THE APPLICABLE FLUID t+1 206 493 1771 f+1 206 493 1778
<br /> TEMPERATURE.
<br /> c. FOR DIRECT-BURIED HEATING AND HOT WATER SYSTEM PIPING,REDUCTION OF THESE THICKNESSES BY 1-112 All regrod„o 6 intellectual oroaenv riahls reserved
<br /> INCHES(38 MM)SHALL BE PERMITTED(BEFORE THICKNESS ADJUSTMENT REQUIRED IN FOOTNOTE b BUT NOT TO 2020
<br /> THICKNESSES LESS THAN 1 INCH(25 MM). In Association with
<br /> 4. C403.10.3.1-PIPING INSULATION EXPOSED TO WEATHER SHALL BE PROTECTED FROM DAMAGE AS REQUIRED AND AS Mortensen
<br /> DESCRIBED IN THE PROJECT MANUAL.ADHESIVE TAPES SHALL NOT BE PERMITTED.
<br /> General Contractor
<br /> 5. C404.3-DOMESTIC HOT WATER PIPING SHALL NOT EXCEED THE FLOW RATE LIMITATIONS. 10230 NE Points Drive,Suite 300
<br /> Kirkland,WA 98033
<br /> 6. C404.3.1-THE DOMESTIC HOT WATER SYSTEM SHALL BE INSTALLED SUCH THAT THE MAXIMUM LENGTH OF
<br /> UNCIRCULATED HOT WATER PIPING SHALL NOT EXCEED THE VALUES LISTED IN TABLE C404.3.1.THE UNCIRCULATED
<br /> PIPE IS THE SECTION THAT EXPERIENCES ZERO FLOW WHEN THE PLUMBING FIXTURE IS NOT IN USE. Mazzettl
<br /> MEP+FP Englnee6ng
<br /> 7. C404.5-ELECTRIC WATER HEATERS IN UNCONDITIONED SPACES OR ON CONCRETE FLOORS SHALL BE PLACED ON AN 2013 4th Avenue,Suite 200
<br /> INCOMPRESSIBLE,INSULATED SURFACE WITH A MINIMUM THERMAL RESISTANCE OF R-10. Seattle,WA 98121
<br /> 8. C404.6-AUTOMATIC-CIRCULATING HOT WATER AND HEAT-TRACED SYSTEM PIPING SHALL BE INSULATED AS
<br /> REQUIRED.
<br /> SYSTEM INSULATION CONDUCTIVITY INSULATION THICKNESS
<br /> AUTOMATIC CIRCULATING <27 10
<br /> HOT WATER
<br /> HEAT TRACED SYSTEMS 1.27 1.0
<br /> SERVED BY EQUIPMENT 0.5
<br /> WITHOUT INTEGRAL HEAT <.27 (FIRST 8'OF PIPE)
<br /> TRAPS
<br /> TABLE C404.3.1
<br /> PIPING VOLUME AND MAXIMUM PIPING LENGTHS
<br /> MAXIMUM PIPING LENGTH FEE Key Plan
<br /> NOMINAL PIPE VOLUME(LIQUID (FEET)
<br /> SIZE OUNCES PER FOOT PUBLIC LAVATORY OTHER FIXTURES AND
<br /> (INCHES) LENGTH) FAUCETS APPLIANCES
<br /> 1/4 0.33 6 50
<br /> 5/16 0.5 4 50
<br /> 3/8 0.75 3 50
<br /> 1/2 1.5 2 43
<br /> 5/8 2 1 32
<br /> 3/4 3 0.5 21
<br /> 7/8 4 0.5 6
<br /> 5 0.5 13
<br /> 11/4 8 0.5 8
<br /> 11/2 11 0.5 6
<br /> 2 OR LARGER 18 0.5 1 4
<br /> 9. C406.2.2-EXCEPT AS NOTED IN EQUIPMENT SCHEDULES,ALL MECHANICAL EQUIPMENT SHALL EXCEED THE MINIMUM
<br /> EFFICIENCY REQUIREMENTS OF TABLES C403.2.3(1)THROUGH C403.2.3(9)BY 15 PERCENT.(ONLY REQUIRED FOR
<br /> PROJECTS PURSUING C406.2) Professional Seals
<br /> 10. C408.2.2-PROVIDE BALANCING DAMPERS,TEMPERATURE AND PRESSURE TEST CONNECTIONS AND BALANCING
<br /> VALVES IN ALL AIR OUTLETS/INLETS,BRANCH DUCTS AND PIPE RUNS TO TERMINAL DEVICES AS REQUIRED AND AS W Sp
<br /> INDICATED ON THE CONTRACT DOCUMENTS. Q"�OF
<br /> 11. C408.2.2-HVAC SYSTEMS SHALL BE BALANCED AS REQUIRED AND AS SPECIFIED. Fe o
<br /> � z
<br /> 24672
<br /> TONAL
<br /> No. Description Date
<br /> MOB BACK FILL ISSUED FOR PERMIT 2022/10/14
<br /> KP Project No: CAP022248
<br /> HOK Project No: 20.05003.00
<br /> Sheet Title:
<br /> PLUMBING 2018
<br /> WSEC COMPLIANCE
<br /> AND EQUIPMENT
<br /> SCHEDULES
<br /> origioel ie 30 x 42 D. oa or I-dewing.
<br /> Sheet Number R 1 P �//�/
<br /> e V 1 1 00/�