• <br /> SER <br /> PER] ANENTE <br /> Project <br /> Kaiser Permanente Everett <br /> 2018 WASHINGTON STATE ENERGY CODE COMPLIANCE MOB Backfill <br /> 1. C402-DUCTS,SHAFTS AND PLENUMS CONVEYING OUTDOOR AIR FROM THE EXTERIOR OF THE BUILDING TO THE 15. C403.4.2-INDIVIDUAL ZONE TERMINAL UNITS AND HVAC SYSTEMS SERVING PORTIONS OF THE BUILDING HAVING LESS TABLE C403.10.1.2 <br /> MECHANICAL SYSTEM SHALL MEET ALL AIR LEAKAGE AND BUILDING ENVELOPE INSULATION REQUIREMENTS PLUS THAN 24-HOUR OPERATION OR DIFFERENT USES SHALL BE SHUT OFF OR SETBACK DURING UNOCCUPIED PERIODS SUPPLY,RETURN,EXHAUST AND RELIEF AIR DUCTWORK INSULATION 2929 PINE STREET <br /> BUILDING ENVELOPE VAPOR CONTROL AS REQUIRED BY TABLE C403.10.1.1 OF THE WSEC. AS REQUIRED AND AS DESCRIBED IN THE TEMPERATURE CONTROL SEQUENCES. MINIMUM INSTALLED DUCT 2929 PINE <br /> STREET <br /> EET <br /> DUCT SYSTEM DUCT LOCATION AND USE CLIMATE ZONE INSULATION R-VALUE NOTES <br /> 98201 <br /> 2. C403.1.1-THE HVAC TOTAL SYSTEM PERFORMANCE RATIO(HVAC TSPR)OF THE PROPOSED DESIGN HVAC SYSTEM 16. C403.4.2.3-AUTOMATIC START AND STOP CONTROLS SHALL BE PROVIDED FOR EACH HVAC SYSTEM. <br /> SHALL BE MORE THAN OR EQUAL TO THE HVAC TSPR OF THE STANDARD REFERENCE DESIGN.[FOR OFFICE,RETAIL, SUPPLY OR OUTSIDE THE BUILDING(OUTDOORS SEE SECTION 0403.10.1.2 <br /> LIBRARY AND EDUCATION OCCUPANCIES AND BUILDINGS SUBJECT TO SECTION C403.3.5 DEDICATED OUTDOOR AIR 17. C403.4.2.3-HEATING AND COOLING SYSTEMS SHALL BE EQUIPPED WITH AUTOMATIC START CONTROLS. RETURN AIR AND EXPOSED TO WEATHER)° 4C R-8 FOR DETAILS Prepared for <br /> SYSTEMS] UNCONDITIONEDSPACE(ENCLOSED KAISER FOUNDATION <br /> 18. C403.4.2-HVAC SYSTEMS SHALL BE EQUIPPED WITH AUTOMATIC CONTROLS CAPABLE OF BEING SET FOR SEVEN SUPPLY OR SEE SECTION C403.10.1.2 <br /> 3. C403.1.2-CALCULATION OF HEATING AND COOLING LOADS SHALL BE DETERMINED IN ACCORDANCE WITH THE DIFFERENT DAY TYPES PER WEEK AND ALSO ACCOMPLISHING SETBACK OR SHUTDOWN DURING UNOCCUPIED RETURN AIR CONDITIONED ENVELOPE)BUT NOT IN THE BUIDING 4C AND 5B RE FOR DETAILS HEALTH PLAN, INC. <br /> PROCEDURES DESCRIBED IN ANSIIASHRAEIACCA STANDARD 183 OR BY AN APPROVED EQUIVALENT COMPUTATIONAL PERIODS AS REQUIRED BY SECTION C403.4.2.1 THROUGH C403.4.2.5 OF THE WSEC AND AS DESCRIBED IN THE <br /> PROCEDURE PER THE REQUIREMENTS. TEMPERATURE CONTROL SEQUENCES. UNCONDITIONED SPACE WHERE THE SEE IMC SECTION 603.12 <br /> SUPPLY OR DUCT CONVEYS AIR THAT IS WITHIN FOR ADDITIONAL NATIONAL FACILITIES SERVICES <br /> 4. C403.2.1-HVAC SYSTEMS SERVING ZONES THAT ARE INTENDED TO OPERATE OR BE OCCUPIED NONSIMULTANEOUSLY 19. C403.4.2.5-FOR ALL OCCUPANCIES OTHER THAN GROUP R,TRANSFERFAIN ORMIXING FAN SYSTEMSSERVING RETURN AIR 15oFOF THE AIR TEMP OFTHE 4C AND 5B R-3.3 REQUIREMENTS FOR POST OFFICE BOX12916 <br /> SHALL BE DIVIDED INTO ISOLATION AREAS. SPACES WITHIN THE CONDITIONED ENVELOPE SHALL BE CONTROLLED AS REQUIRED. SURROUNDING UNCONDITIONED CONDENSATION OAKLAND,CA 94604 <br /> SPACE CONTROL AT DUCTWORK <br /> 5. C403.2.2-WHERE EXHAUST IS PROVIDED,SYSTEMS SHALL BE CONFIGURED TO PROVIDE NO GREATER THAN 150 20. C403.4.11-DIRECT DIGITAL CONTROL(DDC)SYSTEMS SHALL BE REQUIRED AS SPECIFIED IN SECTIONS C403.4.11.1 DUCT OR PLENUM IS <br /> PERCENT OF THE MINIMUM EXHAUST AIR REQUIRED BY THE IMC,FGI,OR ASHRAE 170.[NOT APPLICABLE TO 1-2 THROUGH C403A.11.3 OF THE WSEC. SEPARATED FROM <br /> OCCUPANCIES,CAN BE EXCEEDED WHEN USED FOR VOC DILUTION,ECONOMIZER,NIGHT FLUSHING, BUILDING ENVELOPE <br /> DEHUMIDIFICATION,PRESSURE EQUALIZATION,RELIEF,PROCESS EXHAUST] 21. C403.6-MECHANICAL SYSTEMS SERVING MULTIPLE ZONES INCLUDING VARIABLE AIR VOLUME(VAV),SINGLE DUCT SUPPLY OR WHERE LOCATED IN A BUILDING 4C AND 5B R-16 <br /> VARIABLE AIR VOLUME(VAV),DUAL DUCTAND MIXING VAV SYSTEMS SHALL HAVE ZONE CONTROLS AS REQUIRED BY RETURN AIR ENVELOPE ASSEMBLY ASSEMBLY WITH THE <br /> 6. C403.2.2.1-WHERE MECHANICAL VENTILATION IS PROVIDED,SYSTEMS SHALL BE CONFIGURED TO PROVIDE NO SECTION G403.6.1 THROUGH C403.6.10 OF THE WSEC.[INCLUDES SUPPLY-AIR TEMPERATURE RESET CONTROLS,SET MINIMUM INSULATION <br /> GREATER THAN 150 PERCENT OF THE MINIMUM OUTDOOR AIR REQUIRED BY THE IMC,FGI,OR ASHRAE 170.[NOT POINT FOR DDC CONTROL,STATIC PRESSURE SENSOR LOCATION,HIGH EFFICIENCY VAV CONTROLS] VALUE <br /> APPLICABLE TO 1-2 OCCUPANCIES.CAN BE EXCEEDED IF ENERGY RECOVERY IS PROVIDED] WITHIN CONDITIONED SPACE WHERE <br /> 22. C403.6.4-SUPPLY AIR TEMPERATURES SHALL BE AUTOMATICALLY RESET AS REQUIRED OR AS DESCRIBED IN THE SUPPLY AIR THE SUPPLY DUCT CONVEYS AIR 4C AND 5B R-3.3 SEE SECTION C403.10.1.2 <br /> 7. C403.2.3-FAN AND PUMP MOTORS 7.5 HP AND GREATER SHALL BE PROVIDED WITH VARIABLE FREQUENCY DRIVES OR TEMPERATURE CONTROL SEQUENCES. THAT IS LESS THAT 55°F OR FOR DETAILS <br /> OTHER CONTROLS AND DEVICES PER THE REQUIREMENTS AND AS DESCRIBED IN THE CONTRACT DOCUMENTS.THIS GREATER THAN 105°F <br /> REQUIREMENT APPLIES TO ALL SYSTEMS,INCLUDING CONSTANT SPEED SYSTEMS 23. C403.7-VENTILATION AND EXHAUST REQUIREMENTS IN ADDITION TO OTHER REQUIREMENTS OF SECTION C403 SHALL WITHIN CONDITIONED SPACE THAT , <br /> BE IN ACCORDANCE WITH SECTIONS C403.7.1 THROUGH G403.7.8 OF THE WSEC.[INCLUDES DEMAND CONTROL THE DUCT DIRECTLY SERVES WHERE <br /> 8. C403.218.3-LOCATION OF LOW,MEDIUM AND HIGH PRESSURE DUCTWORK IS IDENTIFIED IN THE PROJECT MANUAL AS VENTILATION,OCCUPANCY SENSORS,HEATING CONTROL,ENCLOSED LOADING DOCK AND PARKING GARAGE SEE SECTION C403.10.1.2 <br /> REQUIRED IN C403.2.8.3.1-.3. CONTROLS,ENERGY RECOVERY VENTILATION SYSTEMS,LABS] SUPPLY AIR THE SUPPLY DUCT CONVEYS AIR 4C AND 5B NONE FOR DETAILS <br /> THAT IS LESS THAN 55°F OR <br /> 9. C403.3-HEATING AND COOLING SYSTEMS HAVE BEEN SIZED IN ACCORDANCE WITH SECTION C403.3.1 AND NOT LESS 24. C403.7.8.1-OUTSIDE AIR INTAKES,EXHAUST OUTLETS AND RELIEF OUTLETS SERVING CONDITIONED SPACES SHALL GREATER THAN 105°F <br /> EFFICIENT IN THE USE OF ENERGY THAN AS SPECIFIED IN SECTION C403.3.2. BE EQUIPPED WITH MOTORIZED DAMPERS. WITHIN CONDITIONED SPACE WHERE <br /> SUPPLY AIR THE SUPPLY DUCT CONVEYS AIR 4C AND 5B NONE <br /> 10. C403.3.2-MECHANICAL EQUIPMENT SHALL HAVE MINIMUM PERFORMANCE AT SPECIFIED RATING CONDITIONS NOT 25. C4033.2-FOR EACH FAN,THE SELECTED FAN MOTOR NAMEPLATE HORSEPOWER SHALL BE NO LARGER THAN THE THAT IS 55°F OR GREATER AND 105-F <br /> LESS THAN THE VALUE INDICATED IN TABLE C403.3.2(1)A THROUGH C403.3.2(1)C,C403.3.2(2),C403.3.2(3),C4033.2(4), FIRST AVAILABLE MOTOR SIZE GREATER THAN THE BRAKE HORSEPOWER(BHP)AND SHALL BE INDICATED ON THE OR LESS <br /> C403.3.2(5),C403.3.2(7),C403.3.2(8),C403.3.2(9),C403.3.2(10),C403.3.2(11),C403.3.2(12),C403.3.2.2,AND AS INDICATED ON DESIGN DOCUMENTS. Hellmuth,Obata&Kassabaum,Inc. <br /> THE CONTRACT DOCUMENTS. WITHIN CONDITIONED SPACE, 1218 Third Avenue,Suite 1315 <br /> 26. C403.8.3-FANS SHALL HAVE A FAN EFFICIENCY GRADE OF 67 OR HIGHER.TOTAL EFFICIENCY OF FAN AT DESIGN RETURN OR DOWNSTREAM OF AN ENERGY <br /> 11. C403.3.5.2-HEATING AND COOLING EQUIPMENT FANS,HEATING AND COOLING CIRCULATION PUMPS,AND TERMINAL POINT OF OPERATION SHALL BE WITHIN 15 PERCENTAGE POINTS OF THE MAXIMUM TOTAL EFFICIENCY OF THE FAN. EXHAUST AIR RECOVERY MEDIA,UPSTREAM OF AN 4C R-8 Seattle,WA 98101 USA <br /> UNIT FANS SHALL CYCLE OFF AND TERMINAL UNIT PRIMARY COOLING AIR SHALL BE SHUT OFF WHEN THERE IS NO AUTOMATIC SHUTOFF DAMPER t+1 206 493 1771 f+1 206 493 1778 <br /> CALL FOR HEATING OR COOLING IN THE ZONE. 27. C403.8.5.1-CONTROLS SHALL BE PROVIDED FOR FANS IN ACCORDANCE WITH SECTION C403.8.5.1 AND AS REQUIRED RETURN OR CONDITIONED SPACE AND 4C R-16 <br /> FOR SPECIFIC SYSTEMS PROVIDED IN SECTION C403 OF THE WSEC. EXHAUST AIR DOWNSTREAM All recrod-i-s intellectual oroaart rights rasen as <br /> 12. C403.4-HVAC SYSTEMS SHALL BE PROVIDED WITH THERMOSTATIC CONTROLS AS REQUIRED BY SECTIONS C403.4.1 2020 <br /> THROUGH C403A 11 OF THE WSEC. 28. C403.10.1.2-OTHER SUPPLY AND RETURN DUCTS AND PLENUMS SHALL BE INSULATED WITH A MINIMUM OF R-6 a. INCLUDE FILM RESISTANCE.THE REQUIRED MINIMUM THICKNESSES DO NOT CONSIDER WATER VAPOR In Association with <br /> INSULATION WHERE LOCATED IN UNCONDITIONED SPACES,AND WHERE LOCATED OUTSIDE THE BUILDING AS TRANSMISSION AND POSSIBLE SURFACE CONDENSATION.INSULATION RESISTANCE MEASURED ON A <br /> 13. C403.4.1.2-PROVIDE DEADBAND BETWEEN HEATINGICOOLING SPACE SENSOR SETPOINTSOF5 DEGREES AS REQUIRED BY SECTION AND TABLE r403.10.1.2 OF THE WSEC. HORIZONTAL PLANE IN ACCORDANCE WITH ASTMC518ATA MEAN TEMPERATURE OF75°FAT THE INSTALLED Mortensen <br /> REQUIRED OR AS DESCRIBED IN THE TEMPERATURE CONTROL SEQUENCES. THICKNESS. General Contractor <br /> 29. C403.10.2-ALL DUCTWORK SHALL BE CONSTRUCTED AND SEALED IN ACCORDANCE WITH THE INTERNATIONAL b. SEE INTERNATIONAL MECHANICAL CODE SECTIONS 603.12 AND 604 FOR FURTHER DETAILS ON DUCT 10230 NE Points Drive,Suite 300 <br /> 14. C403.4.1.3-WHERE A ZONE HAS A SEPARATE HEATING AND A SEPARATE COOLING THERMOSTATIC CONTROL MECHANICALCODE. INSULATION REQUIREMENTS. Kirkland,WA 98033 <br /> LOCATED WITHIN THE ZONE,THE ZONE CONTROL SHALL BE CONFIGURED TO PREVENTTHE HEATING SET POINT DUCTWORK STATIC PRESSURE AND SEAL CLASS: c. INCLUDES ATTICS ABOVE INSULATED CEILINGS,PARKING GARAGES,AND CRAWL SPACES. <br /> FROM EXCEEDING THE COOLING SET POINT AND TO MAINTAIN A DEAD BAND IN ACCORDANCE WITH SECTION WATER COLUMN SEAL CLASS <br /> C403.4.1.2. LESS THAN OR EQUAL TOY SEAL TRANSVERSE JOINTS AND LONGITUDINAL SEAMS 31, C406.2.2-EXCEPT AS NOTED IN EQUIPMENT SCHEDULES,ALL MECHANICAL EQUIPMENT SHALL EXCEED THE MINIMUM Mazzetti <br /> GREATER THAN 2"LESS THAN 3" IN ACCORDANCE WITH SECTION C403.10.1 EFFICIENCY REQUIREMENTS OF TABLES C403.2.3(1)THROUGH C403.2.3(9)BY 15 PERCENT.(ONLY REQUIRED FOR MEP+FP Englneedng <br /> EQUAL TO OR GREATER THAN 3" IN ACCORDANCE WITH SECTION C403.10.1; PROJECTS PURSUING C406.2) 2013 4th Avenue,Suite 200 <br /> DUCTS AND PLENUMS SHALL BE LEAK-TESTED ACCORDANCE <br /> WITH THE SMACNA HVAC AIR DUCT LEAKAGE TEST MANUAL. 32. G408.2.2-PROVIDE BALANCING DAMPERS,TEMPERATURE AND PRESSURE TEST CONNECTIONS AND BALANCING Seattle,WA 98121 <br /> 30. C403.10.2-DUCTWORK DESIGNED TO OPERATE IN EXCESS OF 3 INCHES W.G.SHALL BE TESTED AS REQUIRED. VALVES IN ALL AIR OUTLETS/INLETS,BRANCH DUCTS AND PIPE RUNS TO TERMINAL DEVICES AS REQUIRED AND AS <br /> PROVIDE TEST REPORTS TO THE OWNER. INDICATED ON THE CONTRACT DOCUMENTS. <br /> 33. C408.2.2-HVAC SYSTEMS SHALL BE BALANCED AS REQUIRED AND AS SPECIFIED. <br /> Key Plan <br /> AIR TERMINALS - SERIES FAN POWERED - ELECTRIC DIFFUSERS - LINEAR DIFFUSERS -CEILING <br /> MARK FTU•208 FTU•232 MARK LD1 LD2 MARK CD1 CD2 CD3 <br /> LOCATION RM N287 RM N287 TYPE DESCRIPTION SLOT SLOT TYPE DESCRIPTION MOD CORE MOD CORE MOD CORE <br /> DAMPER MAX AIRFLOW:CFM 160 395 SLOTS:[1] 1 1 MATERIAL STEEL STEEL STEEL <br /> MIN AIRFLOW:CFM 64 158 SLOT WIDTH:IN 1 1 NOM FACE SIZE:IN 2424 2424 2424 <br /> MAX PD:IN WG 0.50 0.50 LENGTH:FT 4 4 CAPACITY NECK SIZE:IN 8x8 10x10 12A2 <br /> FAN MAX AIRFLOW:CFM 160 395 CAPACITY INLET SIZE:IN[2] 6 8 MAX AIRFLOW:CFM 200 300 450 <br /> MOTOR HP 1/3 1/3 MAX AIRFLOW:CFM 100 190 MAX SP:IN WG 0.03 0.03 0.04 <br /> Professional Seals <br /> UNIT INLET:IN[1] 6 6 MAX SP:IN WG 0.03 0.05 MAX NECK VEL:FPM 450 450 450 <br /> MAX FILTER FV:FPM 350 350 MAX NC 20 25 MAX NC 15 15 15 <br /> ELECTRIC CAPACITY:KW 1.0 3.0 BRANCH CONN SIZE:IN 6 8 BRANCH CONN SIZE:IN 8 10 12 Q OF as <br /> HEATING COIL EAT DB:F 65 65 BASIS OF DESIGN MANUFACTURER TITUS TITUS BASIS OF DESIGN MANUFACTURER TITUS TITUS TITUS �w <br /> LAT DB:F 85 89 MODEL FL-10 FL-10 MODEL MCD MCD MCD % z <br /> STEPS 1 1 NOTES [3,4,51 [3,4,51 INOTES [1,2,31 [1,2,3] 11,2,3] <br /> 248 2 <br /> DUCT CONNECTIONS INLET:IN[2] 6 6 NOTES: NOTES: +P�o�,�,o� <br /> OUTLET:IN[3] - 14x10 1. TOTAL NUMBER OF SLOTS,DIVIDED THROW EACH DIRECTION. 1. PROVIDE DIFFUSERS WITH BORDER STYLES THAT ARE COMPATIBLE WITH ADJACENT CEILING TONAL <br /> ISOLATOR TYPE SPRING HGR SPRING HGR 2. OVAL INLET SIZE TO SLOT DIFFUSER PLENUM. SYSTEMS.REFER TO ARCHITECTURAL PLANS. <br /> ELECTRICAL VOLT/PHASE 480/3 480/3 3. PROVIDE DIFFUSERS WITH BORDER STYLES THAT ARE COMPATIBLE WITH ADJACENT CEILING,WALL 2. NC BASED ON OCTAVE BANDS 2-7 SOUND POWER LEVELS MINUS A ROOM ABSORPTION OF 10 DB, No. Description Data <br /> FLA 1.20 3.61 OR SILL SYSTEMS.REFER TO ARCHITECTURAL PLANS. MEASURED PER ASHRAE 70-91. MOB BACK FILL ISSUED FOR PERMIT 2022/10/14 <br /> SCCR:AMPS 14,000 14,000 4. NC BASED ON OCTAVE BANDS 2-7 SOUND POWER LEVELS MINUS A ROOM ABSORPTION OF 10 DB, 3. PROVIDE ATTACHED PLENUM,EXTERNALLY LINED WITH 1 INCH DUCT LINER.SEE DETAIL 2 ON SHEET B1 M601. <br /> OPER WEIGHT WEIGHT:LBS 200 200 MEASURED PER ASHRAE 70-91. <br /> BASIS OF DESIGN IMANUFACTURER I TITUS I TITUS 1 5. PROVIDE ATTACHED PLENUM,EXTERNALLY LINED WITH 1 INCH DUCT LINER.SEE DETAIL 1 ON <br /> MODEL I DTFS I DTFS I I SHEET B1 M601. <br /> NOTES 1 [4,5,6,71 1 [4,5,6,7] <br /> NOTES: <br /> 1. NOMINAL INET SIZE AT AIR TERMINAL,PROVIDE MINIMUM 3 DUCT DIAMETERS OF STRAIGHT DUCT. <br /> 2. PRIMARY SUPPLY AIR DUCT SIZE,USE UNIT INLET SIZE IF BRANCH CONNECTION IS SHORTER THAN �± <br /> 5 FEET LONG. GRILLES <br /> 3. DUCT SIZE DOWNSTREAM OF AIR TERMINAL OUTLET,TRANSITION AS REQUIRED. <br /> 4. REFER TO ELECTRICAL DRAWINGS FOR DISCONNECT SWITCH. MARK RG1 EG1 EG2 EG3 <br /> 5. PROVIDE WITH STERI-LOC INSULATION. TYPE DESCRIPTION LOUVER LOUVER LOUVER LOUVER <br /> 6. PROVIDE WITH 1"DISPOSABLE FILTER. DEFLECTION 35 35 35 35 <br /> 7. SEE DETAIL 4 ON SHEET Bi M601. MATERIAL STEEL STEEL STEEL STEEL <br /> NOM FACE SIZE:IN 24A2 24A2 10x10 2424 <br /> CAPACITY DUCT SIZE:IN 22x10 22A0 8x8 2222 <br /> MAX AIRFLOW:CFM 600 600 180 1,500 <br /> MAX SP:IN WG 0.05 0.05 0.05 0.05 <br /> MAX CORE VEL:FPM 500 500 500 500 <br /> MAX NC 15 15 15 20 <br /> BRANCH CONN SIZE:IN - [3] [3] [3] <br /> BASIS OF DESIGN MANUFACTURER TITUS TITUS TITUS TITUS <br /> MODEL 35ORL 35ORL 35ORL 35ORL <br /> NOTES [1,2,4] [1,2] [1,2] [1,2] <br /> NOTES: <br /> 1. PROVIDE GRILLES WITH BORDER STYLES THAT ARE COMPATIBLE WITH ADJACENT CEILING SYSTEMS, <br /> REFER TO ARCHITECTURAL DRAWINGS. <br /> 2. NC BASED ON OCTAVE BANDS 2-7 SOUND POWER LEVELS MINUS A ROOM ABSORPTION OF 10 DB, KIP Project No: CAP022248 <br /> MEASURED PER ASHRAE 70-91. HOK Project No: 20.05003.00 <br /> 3. SEE PLANS FOR SIZE. Sheet Title: <br /> 4. PROVIDE ATTACHED PLENUM,SEE DETAIL 3 ON SHEET 131 M601. <br /> MECHANICAL 2018 <br /> WSEC COMPLIANCE <br /> AND EQUIPMENT <br /> SCHEDULES <br /> oriamal is 30 x a2.o is or lhis dra ins. <br /> Sheet Number <br /> B1 M011 <br />