<br /> KAISER
<br /> VOLUME DAMPER i PERMANENTE
<br /> MINIMUM 2'LONG STUB
<br /> SUPPLY AIR DUCT,SAME SIZE AS Project
<br /> MINIMUM48"TO BRANCH DUCT SCHEDULED BRANCH DUCT Kaiser Permanente Everett
<br /> GER,ATTACH TO
<br /> SRANCHLINE OF FIRST —_ SSTRUCTURE,TWO PER MOB Ba ckfi I I
<br /> ----< DIFFUSER PLENUM FLEXIBLE DUCT CLAMP
<br /> SUPPLY AIR DUCT,SEE HANGER,ATTACH TO 2929 PINE STREET
<br /> SCHEDULE FOR SIZE SHEET METAL STRUCTURE PER SMACNA
<br /> ELECTRIC HEATING !/ DIFFUSER PLENUM GUIDELINES EVERETT,WA 98201
<br /> COIL PANEL ACCESS TRANSITION TO OUTLET PER NEC /CONNECTION 1"MINERAL FLEXIBLE DUCT(6'-0" Prepared for
<br /> FIBER BLANKET MAXIMUM LENGTH) KAISER FOUNDATION
<br /> FLEXIBLE CONNECTOR(TYP)
<br /> CEILING AND
<br /> HANGER BRACKET HEALTH PLAN, INC.
<br /> (TYR) ELECTRIC HEATING COIL SUPPORT,REFER TO
<br /> ARCHITECTURAL NATIONAL FACILITIES SERVICES
<br /> CONTROL PANEL
<br /> DRAWINGS 2" NOT OBSTRUCT OPENING POST OAKLAND,ICA94604
<br /> BOX SERIES FAN POWERED AIR 2916
<br /> —
<br /> o
<br /> TERMINAL(BOTTOM ACCESS) 2"WIDE SADDLE
<br /> F
<br /> CONTROL PANEL ACCESS P R NEC SHEE8"MINIMUM
<br /> \ MINIM METAL SCREW,REW,
<br /> PLENUM AIR INLET MINIMUM S"ON LIGHT FIXTURE,REFER TO
<br /> ATTENUATOR CENTER ENTER(TYP)L — — — ELECTRICAL DRAWINGS FOR
<br /> SIZE,TYPE AND LOCATIONS
<br /> LINEAR DIFFUSER
<br /> MINIMUM 3 DUCT
<br /> DIAMETERS OF DIFFUSER NECK
<br /> STRAIGHT DUCT FILTER
<br /> PRIMARY SUPPLY AIR NOTES: ,
<br /> DUCT,SEE SCHEDULE FILTER ACCESS
<br /> 1. TWO SLOT LINEAR DIFFUSER SHOWN,OTHER CONFIGURATIONS SIMILAR.
<br /> FOR SIZE p LAY-IN CEILING INDICATED,REFER TO ARCHITECTURAL DRAWINGS FOR
<br /> TRANSITION TO INLET CEILING TYPE.DIFFUSER BORDER STYLE TO BE COMPATABLE WITH
<br /> CONNECTION ADJACENT CEILING TYPE.
<br /> Hellmuth,Obata&Kassabaum,Inc.
<br /> 1218 Third Avenue,Suite 1315
<br /> Seattle,WA 98101 USA
<br /> 4 AIR TERMINAL - FAN POWERED - ELEC 1 DIFFUSER - LINEAR t+1 206 493 1771 f+1 206 493 1778
<br /> 61 M601 NOT TO SCALE 61 M601 NOT TO SCALE All recrca„cmo&lutellcctoal orcacry rights rasen as
<br /> 2020
<br /> In Association with
<br /> Mortensen
<br /> General Contractor
<br /> ON ALL SIDES OF
<br /> DAMPER •6 10230 NE Points Drive,Suite 300
<br /> •`WNG. O OPERATORIACTUATOR Kirkland,WA 98033
<br /> DUCT •YVAII
<br /> 1l4"MIN.
<br /> O FUSIBLE ROD Mazzetti
<br /> MEP+FP Englneedng
<br /> 2 O AUXILIARY OPERATING JACK SHAFT 20134th Avenue,Suite 200
<br /> Seattle,WA 98121
<br /> 12 O DAMPER FRAME
<br /> 3
<br /> _ - � O FUSIBLE LINK WITH LOCK
<br /> F, -1 �l PERFORATED 20 GAUGE
<br /> 1 O SLEEVE GALVANIZED STEEL,0.156"HOLES ON
<br /> 1 MINERAL
<br /> STAGGERED CENTERS,FULL FIBER BLANKET
<br /> / WIDTH
<br /> O NEGATOR SPRING WIDTH OF DIFFUSER NECK,TOP AT
<br /> Lz— J 5 CENTERLINE OF INLET
<br /> OMOUNTING ANGLES MINIMUM 2'LONG STUB
<br /> DUCT,SAME SIZE AS
<br /> 7 9 SJOINT,SLEEVE TO DUCT
<br /> SCHEDULED BRANCH DUCT
<br /> Q10 9 10 CAULKING MATERIAL SHEET METAL DIFFUSER
<br /> \+ PLENUM,PHYSICAL CAP FLEXIBLE DUCT CLAMP Key Plan
<br /> 11 FIRE AND SMOKE DAMPER DIMENSIONS MAY VARY
<br /> L J PROTECTION BASED ON STUB DUCT HANGER ROD,ATTACH TO
<br /> L J SIZE STRUCTURE PER SMACNA
<br /> 8 WALL 11 12 GUIDELINES(TYP)
<br /> ACCESS DOOR
<br /> SQUARE DIFFUSER r — 8"MINIMUM
<br /> NOTES: NECK
<br /> 1. DAMPER SHALL BE'RUSKIN"MODEL NO.FSD60,COMBINATION FIRE-SMOKE AND LEAKAGE RATED CEILING AND
<br /> MULTIPLE BLADE DAMPER,CLASS 1,4 CFM PER SQ.FT.WITH ELECTRONIC OPERATOR. SUPPORT,REFER TO
<br /> 2. OPENING IN WALL SHALL BE 1l8"PER FOOT LARGER THAN DAMPER DIMENSION.MINIMUM ARCHITECTURAL FLEXIBLE DUCT(6'-0'
<br /> CLEARANCE OF 114 REQUIRED FOR ANY INSTALLATION. DRAWING MAXIMUM LENGTH)
<br /> SLEEVE
<br /> 3. ANGLE SIZE FOR SLEEVE MOUNTING:UP TO INSTALLATION.
<br /> WIDTH HEIGHT,1"x1"xi/8";2'-0'TO 6'-0"WIDTH
<br /> OR HEIGHT,2"x2"x118";OVER S-W HEIGHT,3"x3"x14 GAGE.OPTION:FORMED 10 GAGE ANGLES ALL
<br /> AROUND SLEEVE,ANGLES SHALL NOT BE ATTACHED TO WALL OVER LAP OF WALL FRAMING 2"WIDE SADDLE
<br /> SHALL BE 1"MINIMUM.ANGLES SHALL BE WELDED TO EACH OTHER.
<br /> 4. FIRE RATING OF PARTITION AS NOTED ON ARCHITECTURAL DRAWING.OPENING SHALL BE SQUARE CEILING f LIGHT FIXTURE,REFER TO
<br /> FRAMED WITH A MINIMUM OF 5/8"GYPSUM BOARD OR EQUIVALENT PROTECTION.CONCRETE DIFFUSER ELECTRICAL DRAWINGS FOR Professional Seals
<br /> AND MASONARY WALL OPENINGS NEED TO BE LINED. SIZE,TYPE AND LOCATIONS
<br /> 5. SLEEVE SHALL BE CONTINUOUS PER FIRE MARSHAL LISTING.
<br /> 6. COMBINATION DAMPER DETAIL FOR REFERENCE ONLY.FIRE AND SMOKE DAMPERS SHALL BE SHEET METAL SCREW,MINIMUM W. S�
<br /> STATE FIRE MARSHAL APPROVED OR AN APPROVED EQUAL AND INSTALLED STRICTLY PER THE TWO PER SIDE(TYP) C4 of W
<br /> MANUFACTURER'S PRINTED INSTRUCTION.MANUFACTURER'S INSTALLATION INSTRUCTION FOR �w
<br /> ALL FIRE AND SMOKE DAMPERS SHALL BE KEPT ON THE JOB SITE AND MADE AVAILABLE TO THE % z
<br /> INSPECTION AUTHORITY.
<br /> 7. "S"SLIP DUCT CONNECTION DUCT SHALL NOT BE BOLTED OR SCREWED TO DUCT OR SLEEVE. NOTE:
<br /> 8. ACCESS DOOR SHALL BE LOCATED IN SIDE OR BOTTOM ON ONE SIDE OF COMBINATION FIRE/ LAY-IN CEILING INDICATED,REFER TO ARCHITECTURAL DRAWINGS FOR 24672 9
<br /> SMOKE DAMPER. CEILING TYPE.DIFFUSER BORDER STYLE TO BE COMPATABLE WITH
<br /> 9. COMBINATION FIRE AND SMOKE DAMPER FRAME SHALL BE WELDED TO SLEEVE WITH 1"FILLETS ADJACENT CEILING. TONAL '
<br /> AT 8"ON CENTER MAXIMUM EACH SIDE(MINIMUM 2 PER SIDE)OPTION:DAMPER FRAME MAY BE
<br /> FLANGED AND BOLTED TO SLEEVE WITH 1WO BOLTS AT 8"ON CENTERS MAXIMUM EACH SIDE
<br /> OF FRAME(MINIMUM 2 PER SIDE).
<br /> No. Description Data
<br /> MOB BACK FILL ISSUED FOR PERMIT 2022/10/14
<br /> 5 DUCT- FSD - COMBINATION FIRE/SMOKE DAMPER 2 DIFFUSER - CEILING SQUARE
<br /> Bi M601 12'=1'-0" B M601 NOT TO SCALE
<br /> CLEARANCE PER
<br /> ILL RATING AND
<br /> CODE(TYP) GALVANIZED
<br /> RETAINING
<br /> ANGLEAND
<br /> FASTENERS
<br /> (TYP)
<br /> METAL
<br /> SLEEVE HANGER,ATTACH
<br /> TO STRUCTURE
<br /> o BREAK AWAY
<br /> CURTAIN DUCT
<br /> DAMPER WITH CONNECTION, 12'MINIMUM
<br /> CLOSURE - — — — — — — - SEAL AIR-
<br /> SPRING TIGHT(TYP)
<br /> SHEET METAL �12x24
<br /> BOOTDUCT ACCESS SEAL EDGES AND
<br /> FACTORY DOOR,SEE SEAMS WITH EDGE
<br /> COLLAR(TYP) SPECIFICATIONS CEILING AND COATING(TYP)
<br /> FOR MINIMUM SUPPORTS,REFER
<br /> SIZE TO ARCHITECTURAL
<br /> DRAWINGS
<br /> FIRE RATED 8'MINIMUM
<br /> CONSTRUCTION,
<br /> REFER TO ARCH
<br /> DRAWINGS ARCH
<br /> 6" 6" DUCT,REFER TO RETURN GRILLE LIGHT FIXTURE,
<br /> PLANS FOR REFER TO
<br /> AAX MAX SIZES AND ELECTRICAL KIP Project No: CAP022248
<br /> (16"MAX IF FACTORY LOCATIONS SHEET METAL SCREW,MINIMUM DRAWINGS FOR ECK Project No: 20.05003.00
<br /> SLEEVE INCLUDES (TYP) TWO PER SIDE(TYP) SIZE,TYPE AND
<br /> Sheet Title:
<br /> ACCESS DOOR) LOCATIONS
<br /> NOTES: NOTES: MECHANICAL
<br /> SHWN,2412 NOMINAL GRILLE
<br /> 1. INSTALL PER UL AND MANUFACTURER'S INSTALLATION INSTRUCTIONS. 2. LAY-N MI CCEIL2424 IING NDIICATEDO REFER TO ARCHITECTURAL DIRAWINGS FOR CEILING DETAILS AND
<br /> 2. VERTICAL INSTALLATION SHOWN,HORIZONTAL INSTALLATION SIMILAR. TYPE.GRILLE BORDER STYLE TO BE COMPATIBLE WITH ADJACENT CEILING TYPE.
<br /> 3. FIELD FABRICATED SLEEVE SHOWN,FACTORY SLEEVE WITH FACTORY ACCESS DOOR IS OPTIONAL. DIAGRAMS
<br /> 4. NOT APPLICABLE FOR MOIST ENVIRONMENTS.
<br /> 6 DAMPER - FIRE 3 GRILLE - CEILING RETURN - BOOT orisioei mr a°x42_D —of,his Crawl
<br /> Bi M601 NOT TO SCALE Bi M601 NOT TO SCALE Sheet Number
<br /> B1 M601