Laserfiche WebLink
Envelope Leakage Test <br /> Testing Company: Technician: <br /> Name: Name: <br /> Address: Credentials: <br /> Email: <br /> Building Information: Customer Information: <br /> Project ID: Lot 6 - 9914 18th OF Name: <br /> Address: Address: <br /> Geo-Tag Data: Latitude: 47.907642 <br /> Longitude: -122.258344 <br /> Timestamp: 2024-07-19 11:11:20 <br /> Measured Leakage: 1.91 ACH50 <br /> Leakage Target: 3.00 ACH50 <br /> Compliance with Leakage Target: Pass <br /> Test ID: 1 <br /> Purpose of Test: Seattle <br /> Measured CFM50: 450.1 (+/- 1.8%) Effective Leakage Area: 24.5 in2 <br /> Building Volume: 14,110.0 ft3 Enclosure Surface Area: 0.0 ft2 <br /> Coefficient (C): 34.8 (+/- 7.6%) Exponent (n): 0.654 (+/- 0.022) <br /> Correlation Coefficient: 0.99983 <br /> Test Standard: RESNET 380 Multi-Point Test Mode: Depressurize <br /> Test Characteristics: Indoor Temp: 73 °F Outdoor Temp: 69 °F <br /> Altitude: 555.0 ft Time Average Period: 10 seconds <br /> Test Date and Time: 2024-07-19 11:11:38 <br /> 600 <br /> 500 0 Depressurize <br /> 400 <br /> U <br /> a� 300 <br /> 0) <br /> c� <br /> Y <br /> fa <br /> 3 200 <br /> 0) <br /> C <br /> CD <br /> 100 <br /> 90 <br /> 80 <br /> 4 5 6 7 8 910 20 30 40 50 60 70 <br /> Building Pressure (Pa) <br />