Laserfiche WebLink
Envelope Leakage Test <br /> Test Readings: <br /> Target (Pa) Bldg (Pa) Adj Bldg-(Ea) Fan (Pa) Flow (cfm) Config <br /> Baseline -0.5 <br /> -60.0 -60.6 -60.2 -72.8 507.7 Ring B <br /> -48.0 -48.2 -47.7 -53.7 436.6 Ring B <br /> -35.0 -35.7 -35.3 -35.5 355.7 Ring B <br /> -23.0 -22.2 -21.8 -134.9 264.7 Ring C <br /> -10.0 -10.9 -10.5 -51.0 160.8 Ring C <br /> Test Equipment: <br /> Flow Device: Model 3 110V Fan <br /> Pressure Gauge: DG1000 <br /> Serial #: 10507 <br /> Calibration Date: 2022-02-03 <br /> Deviations from Standard: <br /> • None <br /> Comments: <br /> None <br /> Report by TEC Auto Test 1.9.1 (8), ©2023 The Energy Conservatory, Inc. Page 2 of 2 <br />