Laserfiche WebLink
_ Global Project Values: <br /> -- —- Project Name: HERITAGE BANK STE 501 Standby Hours: 24 <br /> Project ID: KL5162 Alarm Mins:� 5 <br /> 4°rs =•airy.T-- •::,:,; Prepared By: Western States Fire Protection Derating Factor: 1.2 <br /> '. •. • • Date: 6/3/2024 Voltage Drop Warning <br /> Threshold%: 10 <br /> Panel ID: JBPS6A Model: BPS6A Power Expander Max NAC Current: 3.0 Amps <br /> Location: 15TH FLR Electrical Room Volts: 24 VDC Max Panel Current: 6.0 Amps <br /> Ckt.# Circuit Name Current Draw W ire AW G Ohms Per Length(ft) Actual Volts @ %Drop <br /> Standby Alarm &Type 1000 Ft. One-Way Ohms EOL <br /> BPS6A BPS6A Pwr Module 1 1 0.075 1 0.205 <br /> NAC#1 Circuit 1 0.000 1.672 #14 Solid 2.52 201 1.01 18.71 8.30% <br /> NAC#2 Circuit 2 0.000 0.614 #14 Solid 2.52 0.00 20.40 0.00% <br /> NAC#3 Circuit 3 0.000 0.000 #14 Solid 2.52 0.00 20.40 0.00% <br /> NAC#4 Circuit 4 0.000 0.000 #14 Solid 2.52 0.00 20.40 0.00% <br /> Aux Aux Power Out 0.000 0.000 1#14 Solid 2.52 0.00 20.40 0.00% <br /> Total Standby Current(Amps) 0.075 2.491 Total Alarm Current(Amps) <br /> Standby Time In Hours 24 0.083 Alarm Time In Minutes/60 5 Mins <br /> Total StandbV AH Required 1.800 0.208 Total Alarm AH Required <br /> Total Combined AH Required 2.01 <br /> Wire resistances are based upon an ambient temperature of 72 degrees F. Because of <br /> Multiply By The Derating Factor 1.20 the minimal difference between solid and stranded wire no differential was made. <br /> Minimum Battery Am Hours Required 2.41 <br /> Configure Circuits Print Page <br />