Laserfiche WebLink
Circuit�. Configuration <br /> Project Information <br /> Project Name: HERITAGE BANK STE 501 Project ID: KL5162 <br /> Prepared By: Western States Fire Protection Date: 6/3/2024 <br /> Ckt. Number: NAC#1 Panel ID: BPS6A <br /> Ckt. Name: Circuit 1 Max Circuit Current: 3 Amps <br /> Qty Device Current Draw Each Current Draw Total <br /> Standby Alarm Standby Alarm <br /> 5 EST EGCF-HDVM Ceiling H/S 15CD 0.000 0.071 0.000 0.355 <br /> 1 EST EGCF-HDVM Ceiling H/S 30CD 0.000 0.101 0.000 0.101 <br /> 4 EST EGCF-HDVM Ceiling H/S 95CD 0.000 0.207 0.000 0.828 <br /> 2 EST EGCF-VM Ceiling Strobe 95CD 0.000 0.194 0.000 0.388 <br /> 0.000 0.000 <br /> Totalsl 0.000 1.672 <br /> Ckt. Number: NAC#2 Panel ID: BPS6A <br /> Ckt. Name: Circuit 2 Max Circuit Current: 3 Amps <br /> Qty Device Current Draw Each Current Draw Total <br /> Standby Alarm Standby Alarm <br /> 2 System Sensor P2/PC2 Horn/Strobe 30cd 0.000 0.116 0.000 0.232 <br /> 1 System Sensor S/SC Strobe 95cd 0.000 0.181 0.000 0.181 <br /> 1 System Sensor P2/PC2 Horn/Strobe 95cd 0.000 0.201 0.000 0.201 <br /> Unused 0.000 0.000 0.000 0.000 <br /> 0.000 0.000 <br /> Totals 0.000 --r 0.614 <br /> Ckt. Number: NAC#3 Panel ID: BPS6A <br /> Ckt. Name: Circuit 3 Max Circuit Current: 3 Amps <br /> Qty Device Current Draw Each Current Draw Total <br /> Standby Alarm Standby Alarm <br /> Unused 0.000 0.000 0.000 0.000 <br /> Unused 0.000 0.000 0.000 0.000 <br /> Unused 0.000 0.000 0.000 0.000 <br /> Unused 0.000 0.000 0.000 0.000 <br /> 0.000 0.000 <br /> Totalsl 0.000 r 0.000 <br /> Ckt. Number: NAC#4 Panel ID: BPS6A <br /> Ckt. Name: Circuit 4 Max Circuit Current: 3 Amps <br /> Qty Device Current Draw Each Current Draw Total <br /> Standby Alarm Standby Alarm <br /> Unused 0.000 0.000 0.000 0.000 <br /> Unused 0.000 0.000 0.000 0.000 <br /> Unused 0.000 0.000 0.000 0.000 <br /> Unused 0.000 0.000 0.000 0.000 <br /> 0.000 0.000 <br /> Totalsl 0.000 r 0.000 <br />