Page 4 of 7
<br />C MICROMATICO STANDARD
<br />RESPONSE PENDENT
<br />SPRINKLER VK102 (K5.6)
<br />The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
<br />Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
<br />Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com
<br />Approval Chart 1 (UL)
<br />Temperature KEY
<br />Micromatic° Standard Response Pendent Sprinkler VK102
<br />•+ Finish
<br />AlXFEscutcheon (if applicable)
<br />Maximum 175 PSI 12 bar WWP
<br />Sprinkler
<br />Thread Size
<br />Nominal
<br />Overall Length
<br />Listings and Approvals3
<br />Base Part
<br />SIN
<br />K-factor
<br />(Refer also to UL Design Criteria.)
<br />Number'
<br />NPT
<br />BSPT
<br />U.S.
<br />metricz
<br />Inches
<br />mm
<br />cULus°
<br />VdS
<br />LPCB
<br />CE$
<br />MED9
<br />China
<br />Approval
<br />12987
<br />VK102
<br />1/2"
<br />15 mm
<br />5.6
<br />80.6
<br />2-1/4"
<br />57
<br />Al, B3, B1Y, C4, D2, E5, G5Z
<br />Al
<br />Al, B3, B1Y
<br />F164 2Y'
<br />F2X
<br />12989
<br />VK102
<br />--
<br />15 mm
<br />5.6
<br />80.6
<br />2-1/4"
<br />57
<br />Al, B3, B1Y, C4, D2, E5, G5Z
<br />Al
<br />Al, B3, B1Y
<br />F1B4 ZY'
<br />F2X
<br />2022910
<br />1 VK102
<br />--
<br />1 15 mm
<br />1 5.6
<br />80.6
<br />2-1/4"
<br />57
<br />E6
<br />E6
<br />•
<br />-
<br />10139
<br />VK102
<br />1/2"
<br />15 mm
<br />5.6
<br />80.6
<br />2-1/4"
<br />57
<br />A1, B3, B1 Y, C4, D2, E5, G5Z
<br />10173
<br />VK102
<br />--
<br />15 mm
<br />5.6
<br />80.6
<br />2-1/4"
<br />57
<br />Al, B3, B1Y, C4, D2, G5Z
<br />Al
<br />Al, B3, BlYj
<br />F2X
<br />18020
<br />1 VK102
<br />1/2"
<br />1 15 mm
<br />1 5.6
<br />1 80.6
<br />2-1/4"
<br />57
<br />Al, B3, B1Y, C4, D2, I G5Z
<br />Al
<br />Al, B3, B1Y
<br />F1, G1X
<br />F2X
<br />Approved Temperature Rating Codes
<br />A = 135 °F (57 °C), 155 °F (68 °C), 175 °F (79 °C), 200 °F (93 °C), 286 °F (141 °C), and 360 °F (182 °C)
<br />B = 135 °F (57 °C), 155 °F (68 °C), 175 °F (79 °C), and 200 °F (93 °C)
<br />C = 286 °F (141 °C)
<br />D = 500 °F (260 °C)'
<br />E = 155 °F (68 °C), 175 °F (79 °C), 200 °F (93 °C), 286 °F (141 °C), 360 °F (182 °C), and 500 °F (260 °C)'
<br />F = 155 °F (68 °C), 175 °F (79 °C), 200 °F (93 °C), 286 °F (141 °C), and 360 °F (182 °C)
<br />G=155°F 68°C,175°F 79°C, and 200°F 93°C
<br />Approved Finish Codes
<br />1 = Brass, Chrome, White Polyester56 and Black Polyestere,s
<br />2 = Brass and Chrome
<br />3 = Wax -Coated Brass and Wax Over Polyesters
<br />4 = High Temperature 200 °F (93 °C) Wax Coating (corrosion resistant); maximum ambient temperature allowed at ceiling = 150 °F (65 °C)
<br />5 = ENT'
<br />6 = Chrome
<br />Approved Escutcheon Codes
<br />X = Recessed with the Viking Model E-1, E-2, or E-3 Recessed Escutcheon
<br />Y = Standard surface -mounted escutcheon or recessed with the Viking Model E-1, E-2, or E-3 Recessed Escutcheon
<br />Z = Standard surface -mounted escutcheon or recessed with the Viking Model E-1 Recessed Escutcheon
<br />Footnotes
<br />I. Base part number is shown. For complete part number, refer to Viking's current price schedule.
<br />2. Metric K-factor shown is for use when pressure is measured in bar. When pressure is measured in kPa, divide the metric K-factor shown by 10.0.
<br />3. This table shows the listings and approvals available at the time of printing. Check with the manufacturer for any additional approvals.
<br />a. Listed by Underwriters Laboratories Inc. for use in the U.S. and Canada.
<br />5. cULus Listed as corrosion resistant.
<br />I.Other colors are available on request with the same Listings and Approvals as the standard colors.
<br />1. Sprinklers of Ultra -High temperature rating are intended for use inside ovens, dryers, or similar enclosures with normal operating temperatures above 300 °F (149 °C).
<br />Where the ambient temperature around the Ultra -High temperature rated sprinkler is significantly reduced below 300 °F (149 °C), the response time of the Ultra -High
<br />temperature rated sprinkler may be severely retarded.
<br />e. CE: Standard EN 12259-1, EC -certificate of conformity 0832-CPD-0021.
<br />9. MED Certified, Standard EN 12259-1, EC -certificate of conformity 0832-MED-1003 and 0832-MED-1008.
<br />1°.Approved according to China GB standard.
<br />11-CE: Standard EC 12259-1, Declaration of Performance DOP_Sprinklers _LPCB 5-2-19 & DOP VK102WAX 2-12-19
<br />DESIGN CRITERIA - UL
<br />(Also refer to Approval Chart 1.)
<br />cULus Listing Requirements:
<br />The Viking Micromatic0° Standard Response Pendent Sprinkler VK102 is cULus Listed as indicated in Approval Chart 1 for installation in accordance
<br />with the latest edition of NFPA 13 for standard spray sprinklers.
<br />• Designed for use in Light, Ordinary, and Extra Hazard occupancies.
<br />• The sprinkler installation rules contained in NFPA 13 for standard spray pendent sprinklers must be followed.
<br />IMPORTANT: Always refer to Bulletin Form No. F 091699 - Care and Handling of Sprinklers. Also refer to Form No. F 080614
<br />for general care, installation, and maintenance information. Viking sprinklers are to be installed in accordance with the latest
<br />edition of Viking technical data, the appropriate standards of NFPA, LPCB, APSAD, VdS or other similar organizations, and
<br />also with the provisions of governmental codes, ordinances, and standards, whenever applicable.
<br />Form No. F_031414 20.10.20 Rev 20.1