<br />C MICROMATICO STANDARD
<br />RESPONSE PENDENT
<br />SPRINKLER VK102 (K5.6)
<br />The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
<br />Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
<br />Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com
<br />Approval Chart 2 (FM) Temperature KEY
<br />Micromatic° Standard Response Pendent Sprinkler VK102 Finish
<br />p p A1X F Escutcheon (if applicable)
<br />Maximum 175 PSI (12 bar) WWP
<br />Sprinkler Base
<br />Thread Size
<br />Nominal K-Factor
<br />Overall Length
<br />FM Approvals3
<br />Part Number'
<br />SIN
<br />(Refer also to Design Criteria below.)
<br />NPT
<br />BSPT
<br />U.S.
<br />metricz
<br />Inches
<br />mm
<br />12987
<br />VK102
<br />1/2"
<br />15 mm
<br />5.6
<br />80.6
<br />2-1/4"
<br />57
<br />Al, B2, C3, D1, E4, G1Y, G4Z
<br />12989
<br />VK102
<br />15 mm
<br />5.6
<br />80.6
<br />2-1/4"
<br />57
<br />Al, B2, C3, D1, E4, G1Y, G4Z
<br />202297
<br />VK102
<br />15 mm
<br />5.6
<br />80.6
<br />2-1/4"
<br />57
<br />E5
<br />•I -
<br />10139 VK102 1/2"
<br />15 mm
<br />5.6
<br />80.6
<br />2-1/4"
<br />57
<br />Al, B2, C3, D1, E4, G1Y, G4Z
<br />10173
<br />VK102
<br />15 mm
<br />5.6
<br />80.6
<br />2-1/4"
<br />57
<br />Al, B2, C3, D1, E4, G1Y, G4Z
<br />18020
<br />VK102
<br />1/2"
<br />15 mm
<br />5.6
<br />80.6
<br />2-1/4"
<br />57
<br />Al, B2, C3, D1, G1Y
<br />Approved Temperature Rating Codes
<br />A = 135 °F (57 °C), 155 °F (68 °C), 175 °F (79 °C), 200 °F (93 °C), 212 °F (100 °C), 286 °F (141 °C), and 360 °F (182 °C)
<br />B = 135 °F (57 °C), 155 °F (68 °C), 175 °F (79 °C), 200 °F (93 °C), and 212 °F (100 °C)
<br />C = 286 °F (141 °C)
<br />D = 500 °F (260 °C)5
<br />E = 155 °F (68 °C), 175 °F (79 °C), 200 °F (93 °C), 286 °F (141 °C), 360 °F (182 °C), and 500 °F (260 °C)5
<br />F = 135 °F (57 °C), 155 °F (68 °C), 175 °F (79 °C), and 200 °F (93 °C)
<br />G = 155 °F (68 °C), 175 °F (79 °C), and 200 °F (93 °C)
<br />Approved Finish Codes
<br />1 = Brass, Chrome, White Polyester56 and Black Polyesters,s
<br />2 = Wax -Coated Brass (corrosion resistant)
<br />3 = High Temperature 200 °F (93 °C) Wax Coating (corrosion resistant); maximum ambient temperature allowed at the ceiling = 150 °F (65 °C)
<br />4 = ENT6
<br />5 = Chrome
<br />Approved Escutcheon Codes
<br />Y = Standard surface -mounted escutcheon or recessed with the Viking Model E-1, E-2, or E-3 Recessed Escutcheon
<br />Z = Standard surface -mounted escutcheon or recessed with the Viking Model E-1 Recessed Escutcheon
<br />Footnotes
<br />I. Base part number is shown. For complete part number, refer to Viking's current price schedule.
<br />2. Metric K-factor shown is for use when pressure is measured in bar. When pressure is measured in kPa, divide the metric K-factor shown by 10.0.
<br />3. This table shows the listings and approvals available at the time of printing. Check with the manufacturer for any additional approvals.
<br />4. Other colors are available on request with the same Approvals as the standard colors.
<br />5. Sprinklers of Ultra -High temperature rating are intended for use inside ovens, dryers, or similar enclosures with normal operating temperatures above 300 T (149 °C).
<br />Where the ambient temperature around the Ultra -High temperature rated sprinkler is significantly reduced below 300 T (149 °C), the response time of the Ultra -High
<br />temperature rated sprinkler may be severely retarded.
<br />I.FM approved as corrosion resistant.
<br />1. Approved according to China GB standard.
<br />DESIGN CRITERIA - FM
<br />(Also refer to Approval Chart 2.)
<br />FM Approval Reauirements:
<br />The Viking Micromatic° Standard Response Pendent Sprinkler VK102 is is FM Approved as standard response Non -Storage pendent sprinkler as
<br />indicated in the FM Approval Guide. For specific application and installation requirements, reference the latest applicable FM Loss Prevention Data
<br />Sheets (including Data Sheet 2-0). FM Global Loss Prevention Data Sheets contain guidelines relating to, but not limited to: minimum water supply
<br />requirements, hydraulic design, ceiling slope and obstructions, minimum and maximum allowable spacing, and deflector distance below the ceiling.
<br />NOTE: The FM installation guidelines may differ from cULus and/or NFPA criteria.
<br />IMPORTANT: Always refer to Bulletin Form No. F 091699 - Care and Handling of Sprinklers. Also refer to Form No. F 080614
<br />for general care, installation, and maintenance information. Viking sprinklers are to be installed in accordance with the latest
<br />edition of Viking technical data, the appropriate standards of NFPA, FM Global, LPCB, APSAD, VdS or other similar organiza-
<br />tions, and also with the provisions of governmental codes, ordinances, and standards, whenever applicable.
<br />Form No. F_031414 20.10.20 Rev 20.1