HVAC EQUIPMENT CONNECTION SCHEDULE GENERAL NOTES I-- BOGARD I PASCUA
<br /> EQUIPMENT CONNECTION TYPE FEEDER ENGINEERS,PS
<br /> CONSULTING ENGINEERS
<br /> 1. FIELD VERIFY EXISTING CONDITIONS PRIOR TO BID. FIELD VERIFY EXISTING PANELCIRCUITS INTENDEDTO 22121 17w Avenue SE,Sups 111
<br /> DISC. DISC. RECEPT. CONN. BEUSED. ADJUST ACCORDINGLY AND RECORD ON AS-BUILT DRAWINGS. eouw,waeneomnNDz1
<br /> TAG VOLTAGE PH HP KW FLA MCA FRAME FUSE COMBO (NEMA) MANUAL ONLY CONDUIT WIRE(Cu) 4a5H581W
<br /> LP-1 480 3 15 21 26.3 [USE EXISTING] 314" 4#10,1#10GND 2. NOT ALL CONDUIT AND CONDUCTORS FOR BRANCH CIRCUITS HAVE BEEN SHOWN. IT IS THE RESPONSIBILITY
<br /> LP-2 480 3 15 - 21 26.3 [USE EXISTING] 314" 4#10,1#10GND OF THE CONTRACTOR SHALL INSTALL ALL REQUIRED CONDUIT AND WIRE FORA COMPLETE INSTALLATION.
<br /> BP-1 480 3 1-1/2 - 3 3.8 [USE EXISTING] 314" 4#12,1#12GND 3. FIELD LOCATE ALL DEVICES AND COORDINATE LOCATIONS WITH FURNITURE,ARCHITECTURAL DRAWINGS,
<br /> BP-2 480 3 1-1/2 - 3 3.8 [PROVIDE NEW DISCONNECT FEEDER] 314" 4#12,1#12GND AND ARCHITECT/OWNER PRIOR TO ROUGH-IN.
<br /> B-1 208 3 - - - 9 [USE EXISTING] 314" 2#12,1#12GND 4. PROVIDE NEW CIRCUIT DIRECTORIES FOR PANELS BEING AFFECTED. v �
<br /> B-2 208 3 - - - 9 [PROVIDE NEW DISCONNECT FEEDER] 314" 2#12,1#12GND 5. PATCH,REPAIR,AND PAINT EXSTING SURFACES THATARE AFFECTED BY NEW WORK. , `R
<br /> HP-1 1 460 3 1 1 1 16.6 [USE EXISTING] 314" 4#12,1#12GND 6. LIGHTING FDCiURE TEMPERATURE SHALL BE 3500K,AS BASIS OF DESIGN.TO BE CONFIRMED DURING
<br /> HP-2 208 1 - - - 3.6 [USE EXISTING] 314" 3#12,1#12GND SUBMITTAL REVIEW.
<br /> 8
<br /> HP-3 208 1 18.5 [PROVIDE NEW DISCONNECT FEEDER] 314" 3#12,1#12GND 7 ALL WIRING SHALL BE TYPE THHN COPPER CONDUCTORS ONLY. dg
<br /> ENGLISH HP4 460 3 - - - 16.9 [USE EXISTING] 314" 4#12,1#12GND
<br /> W w W W W W W W BUILDING NO. 9 DEMOLITION:
<br /> HP-5460 3 - - - 16.9 [USE EXISTING] 3/4" 3#12,1#12GND
<br /> w W W w w w m w HP-6 208 1 18.5 [USE EXISTING] 3/4" 3#12,1#12GND
<br /> 1. REMOVE ALL EXISTING ELECTRICAL EQUIPMENT,CONDUIT AND WIRE BACK TO SOURCE,
<br /> - - -
<br /> W HP-7 208 1 - - - 7.8 [USE EXISTING] 314" 4#12,1#12GND OR NEAREST UPSTREAM DEVICE NOT BEING REMOVED,ON SURFACES(WALLS,CEILINGS,FLOORS) I
<br /> HP-8 460 3 - - - 14 [USE EXISTING] 314" 4#12,1#12GND BEING REMOVED AS PART OF THE CONTRACT.
<br /> HP-9 460 3 - - - 10.3 [PROVIDE NEW DISCONNECT FEEDER] 314" 4#12,1#12GND 2. LEGALLY DISPOSE OF AND/OR RECYCLE MATERIAL BEING REMOVED AS REQUIRED BY STATE AND LOCAL
<br /> SCIENCE HP-10 460 3 - - - 14 [USE EXISTING] 314" 4#12,1#12GND JURISDICTIONALAUTHORITIES.
<br /> HP-11 460 3 - - - 7.6 [USE EXISTING] 3/4" 4#12,1#12GND
<br /> BUILDING NO. 5 3. FOR THE REPLACEMENT OF ANY EXISTING DEVICES WITH NEW-THE CONTRACTOR SHALL MODIFY,PATCH,
<br /> HP-12 460 3 - - - 14 [PROVIDE NEW DISCONNECT FEEDER] 314" 4#12,1#12GND Electrical Consultants,lnc
<br /> COOLING TOWER HP-13 460 3 - 21.7 [USE EXISTING] 314" 4#10,1#10GND AND REPAIR THE EXISTING SURFACE TO ACCOMMODATE NEW DEVICE OR LIGHTING FIXNRE. PROVIDE NEW 19015 36th Avenue West,Suite E
<br /> HP-14 460 3 - - - 217 [USE EXISTING] 3/4" 4#10,1#10GND MOUNTING EQUIPMENT AND SUPPORT,AS REQUIRED. EXTEND CONDUIT AND WIRE TO NEW DEVICE Lynnwood,Washington 98036
<br /> SOCIAL STUDIES . AS REQUIRED. Phone(425)775-1799 FAX(425)774-981
<br /> BUILDING NO.6 HP-15 460 3 21.7 [USE EXISTING] 314" 4#10,1#10GND
<br /> w CT-1 HP-16 460 3 - - - 14 [USE EXISTING] 314" 4#12,1#12GND 4. PATCH,REPAIR,AND PAINT EXISTING SURFACES THATARE AFFECTED BY REMOVAL OF EQUIPMENT,TO
<br /> w M1A-32,34,36,
<br /> HP-17 208 1 3.6 [USE EXISTING] 314" 3#12,1#12GND ORIGINAL CONDITION. FIRE SEAL PENETRATIONS THROUGH FIRE RATED ASSEMBLIES. COORDINATE
<br /> HP-18 460 3 16.9 [USE EXISTING] 314" 4#12,1#12GND PAINT COLOR WITH OWNER. REPAIR IS SUBJECT TO APPROVAL BY OWNER AND ARCHITECT.
<br /> HP-19 460 3 - - - 15.1 [USE EXISTING] 314" 4#12,1#12GND
<br /> HP-20 460 3 - - - 7.6 [USE EXISTING] 314" 4#12,1#12GND
<br /> w W W W HP-21 460 3 - - - 10.3 [USE EXISTING] 314" 4#12,1#12GND (�
<br /> W W W w W W W W HP-22 460 3 = _ = 10.3 [PROVIDE NEW DISCONNECT FEEDER] 3/4" 4#12,1#12GND T11
<br /> HP-23 208 1 18.5 [USE EXISTING] 3/4' 3#12,1#12GND �•/
<br /> 7
<br /> HP-24 460 3 0. [USE EXISTING] 3/4" 4#12,1#12GND SYMBOL LEGEND IH�
<br /> w W HP-25 480 3 - - - 10.3 [PROVIDE NEW DISCONNECT FEEDER] 3/4' 4#12,1#12GND
<br /> BOILER ROOM HP-28 480 3 - - - 18.9 [USE EXISTING] 3/4' 4#12,1#12GND rT,
<br /> HP-27 208 1 - - - 7.9 [USE EXISTING] 3/4" 3#12,1#12GND
<br /> POWER
<br /> CAFETERIA CT-1 460 3 42 1 9 66.2 82.8 100 80 - - - - 1-1/2" 4#2,1#8GND W �/
<br /> DUPLEX RECEPTACLE, GFCI TYPE,WITH WEATHERPROOF COVER. � O
<br /> BUILDING NO.2 l rF� W
<br /> EF-1 120 1 1/2 1.2 9.8 12.25 [USE EXISTING] 3/4" 3#12,1#12GND ® EQUIPMENT CONNECTION(INCLUDES CONDUCTORS,
<br /> EF-2 120 1 1/4 0.7 5.8 7.25 [USE EXISTING] 3/4" 3#12,1#12GND TERMINATIONS,GROUNDING CONDUCTOR,ETC.) O O K
<br /> EF-3 120 1 - 0.2 4.1 [USE EXISTING] 3/4" 3#12,1#12GND
<br /> EFA 120 1 1/2 0.2 9.8 12.25 [USE EXISTING] 3/4" 3#12,1#12GND ❑-' DISCONNECT SWITCH OR COMBINATION MOTOR STARTER/ 1)
<br /> LIBRARY
<br /> EF-5 120 1 0.3 3.3 [USE EXISTING] 3/4" 3#12,1#12GND DISCONNECT SWITCH.SEE EQUIPMENT SCHEDULES.SWITCH
<br /> W EF-6 120 1 - 0.1 - 1.5 [USE EXISTING] 3/4" 3#12,1#12GND SHALL INCLUDE ALL REQUIRED CONNECTIONS. (60)INDICATES r 1 ~
<br /> EF-7 120 1 - 0.1 - 1.5 [USE EXISTING] 3/4" 3#12,1#12GND SWITCH AMPERAGE/(40)INDICATES FUSE AMPERAGE.
<br /> EF-8 120 1 - 0.4 - 3.3 [USE EXISTING] 3/4" 3#12,1#12GND U
<br /> 1^' n[� EF-9 120 1 - 0.006 - .29 [USE EXISTING] 3/4" 3#12,1#12GND G 208/120V PANELBOARD. I—(
<br /> COOLINGTOWER ENLARGED VIEW VIEW © EF-10 120 1 0.348 - 3.3 [USE EXISTING] 3/4" 3#12,1#12GND x
<br /> SCALE: 1/4"=1-0' V EF-11 208 3 1-1/2 - - 6.5 [USE EXISTING] 3/4" 3#12,1#12GND $ MANUAL MOTOR STARTER. SEE EQUIPMENT SCHEDULES.
<br /> ~ x wW
<br /> EF-12 208 3 2.0 - - 7.5 [USE EXISTING] 3/4" 3#12,1#12GND
<br /> EF-13 120 1 - 0.0 - .46 [USE EXISTING] 3/4" 3#12,1#12GND
<br /> EF-14 120 1 - 0.0 - .46 [USE EXISTING] 314" 3#12,1#12GND W rTl 1--I
<br /> TF-1 208 3 3.0 - - - [USE EXISTING] 314" 3#12,1#12GND ^ F+I O
<br /> NOTES:
<br /> 1 DISCONNECT,CONNECTION TYPE FEEDER ANDALL CONNECTIONS BY ELECTRICAL CONTRACTOR,UNLESS NOTED OTHERWISE. U
<br /> 2 COORDINATE EXACT EQUIPMENT LOCATIONS,LOADS AND CONNECTION TYPE WITH MECHANICAL CONTRACTOR PRIORTO ROUGH-N.
<br /> 3 OUTDOOR EQUIPMENT SHALL BE NEMA 3R SHEET INDEX
<br /> 4. 120V CONTROL WIRING AND INTERLOCK WIRING BY ELECTRICAL CONTRACTOR.
<br /> 5. 120V THERMOSTATS,CONDUIT,WIRE AND CONNECTIONS BY ELECTRICAL CONTRACTOR. U
<br /> 6. LOW VOLTAGE THERMOSTATS&WIRING BY MECHANICAL CONTRACTOR.
<br /> KEY: EO.0 COVER SHEET
<br /> MANUAL 120V MANUAL MOTOR STARTER WITH THERMAL OVERLOAD E1.0 POWER PLAN
<br /> COMBO COMBINATION FUSED DISCONNECT/MAGNETIC MOTOR STARTER WITH PDA,COIL VOLTAGE 12DV.
<br /> RECEPT. RECEPTACLE. COORDINATE TYPE WITH EQUIPMENT SUPPLIER E2.0 RISER DIAGRAM
<br /> CONN.ONLY EQUIPMENT CONNECTION
<br /> AREA OF WORK - - E2.1 PANEL SCHEDULES
<br /> E2.2 PANEL SCHEDULES
<br /> E2.3 PANEL SCHEDULES
<br /> E2.4 PANEL SCHEDULES
<br /> E2.5 PANEL SCHEDULES
<br /> SEE ENLARGED
<br /> VIEW THIS
<br /> SHEET
<br /> ��u„wG xn e GGGGCGG/1LLLLLLLLd
<br /> PRW No: 21015.00
<br /> DRAWN er. LRD
<br /> I -- ----- CHECKS)m.BA
<br /> (. DA1E 08-30-2022
<br /> M.
<br /> ---� REmm REVISION I ISSUE DATE
<br /> aoo.e.e<
<br /> 0
<br /> 0
<br /> 0
<br /> SITE PLAN /©
<br /> SCALE: 1"=40'-0" V
<br /> SHEET TITLE
<br /> COVER SHEET
<br /> SHEET NUMBER
<br /> EOmO
<br /> CLIE—E— SHEETI OF 1
<br />
|