f BOGARD I PASCUA
<br /> ENGINEERS,PS
<br /> CONSULTING ENGINEERS
<br /> 7212117w Awns SE,aM 111
<br /> Panel MDP-EXISTING PANEL SCHEDULE PROJECT. PmjectName Panel MDP-REVISED PANEL SCHEDULE PROJECT: Project Name eux,w„nromneaz,
<br /> 4254156100
<br /> 277148OV,3Ph,4W. 1000ABus 100GAGFI M.C.B. FLOOR MOUNTED DIST.PANEL CONSTR. 1-Feb-23 277/48OV,3Ph,4W. 1000A Bus 1000A GFI M.C.B. FLOOR MOUNTED DIST.PANEL CONSTR. 1-Feb-23
<br /> Ckt. Description/ Load Load C.B. C_B. C_B. C.B. Load Load Description Ckt. Ckt. Description/ Load Load C.B. C.B. C.B. C.B. Load Load Description Ckt.
<br /> No. Location (VA) Type Amp Pole Phase Amp Pole (VA) Type Location No. No. Location (VA) Type Amp Pole Phase Amp Pole (VA) Type Location No.
<br /> 1 PANELA112A 43,633 SL 400 3 A 10D 3 3,132 SL PANELE7 2 1 PANELA112A 43,633 SL 400 3 A 100 3 3,172 SL PANELEI 2
<br /> 3 - 43,633 SL - - B - - 3,039 SL - 4 3 - 43,633 SL - - B - - 2,749 SL - 4 Qv op weep,-''UU�
<br /> S - 43.633 SL - - C - - 1,095 SL - 6 5 - 43,633 SL - - C - - 1,135 SL - 6
<br /> 7 PANEL MI 63,028 SL 400 3 A 40D 3 SPARE 8 7 PANEL M1 66,417 SL 400 3 A 400 3 SPARE 8 3
<br /> 9 - 61,542 SL - - -B 10 9 - 64,931 SL - B 10 PA
<br /> 11 - 58,878 SL C - - - 12 11 - 62,267 SL - C - - 12
<br /> 13 PANEL MIA 59,716 SL 400 3 A 20D 3 14,2321 SL PANELLP2 14 13 PANELMIA 68,668 SL 400 3 A 200 3 13,956 SL PANEL LP2 14 ,
<br /> 1s - 59,716 SL - - 8 - - 11,796 SL - 16 15 -- 68,668 SL - B - - 11,363 SL - 16
<br /> 17 - 59,716 SL C 10.794 SL - 18 17 -- 68,668 1 SL - C - 10,830 SL - 18 b6
<br /> 19 PANEL SLI(VIA%FRMR T3) 71,433 SL 400 3 A 200 3 SPARE 20 19 PANEL SLI(VIA)FRMRT3) 71,433 SL 400 3 A 200 3 SPARE 20
<br /> 21 - 71,433 SL B 22 21 -- 71,433 SL - B 22
<br /> 23 - 71.433 SL C - 24 23 -- 71,433 SL C 24
<br /> 25 PANELLPI 37,219 SL 400 3 A 26 25 PANELLPI 37,287 SL 400 3 A 26
<br /> 27 - 40,045 SL 8 28 27 - 40,253 SL B 28
<br /> 29 - 34,352 SL C 30 29 - 34,463 SL - C 30
<br /> 31 A 32 31 A 32
<br /> 33 B 34 33 B 34
<br /> 37 A 38 37 A 36 Electrical Consultants,Inc
<br /> 39 B 40 39 B 40 19015 36th Avenue West,Suite E
<br /> 41 C 42 41 C 42 Lynnwood,Washington 98036
<br /> Phone(425)775-1799 FAX(425)774-981
<br /> Total Connected Load: Ph A 292,392 VA 1,055 A Total Connected Load: Ph A 304,566 VA 1,099 A
<br /> Total Connected Load: Ph B 291,205 VA 1.051 A Total Connected Load: Ph B 303,031 VA 1,093 A
<br /> Total Connected Load: Ph C 279,901 VA 1,010 A Total Connected Load: Ph C 292,430 VA 1,055 A LOAD INCREASE:
<br /> Total Connected Load: 863 5 KVA Total Demand Load: 724.9 KVA Total Connected Load: 900.0 KVA Total Demand Load: 777.0 KVA 52,143 VA
<br /> 1,0366 AMPS 871.9 AMPS 1,082.6 AMPS 934.6 AMPS 62.72 AMPS
<br /> Connected Subfed Total Demand Demand Connected Subfed Total Demand Demand N
<br /> Loads Loads(S) Loads Factor Load Loads Loads(S) Loads Factor Load
<br /> G General IN on-Continuou s) 0 188,970 188,970 100% 188,970 G General(Non-Continuous) 0 0 188,970 100% 188,970
<br /> L Lightng 0 35,333 35,333 125% 44,166 L Lighting 0 0 35,333 125% 44,166 7
<br /> R Receptades-to 10 KVA 0 32,293 10,000 100% 10,000 Accessores: R Receptacles-to 10 KVA 0 0 32,293 100% 32,293 Accessories:
<br /> wer 10 KVA 34,020 56,313 50% 28,157 Geer 10 KVA 0 34,020 50% 17,010
<br /> K IGtchen 0 128,100 128,100 100% 128,100 K Kitchen 0 0 128,100 100% 128,100
<br /> H Heating 0 831 831 100% B31 H Heating 0 0 200 100% 200 1.4
<br /> M Motors 0 320,152 320,152 100% 320,152 M Motors 0 0 357,887 100% 357,887 I--I
<br /> LM Largest MlWr 0 0 0 125% 0 LM Largest Motor 0 0 0 125% 0 O
<br /> 1�--J1 U
<br /> WH Water Heater 0 3,000 3,000 125% 3,750 WH Water Heater 0 0 6,114 125% 7,643
<br /> C Continu ou s General Load 0 606 606 125% 758 C Continuous General Load 0 0 606 125% 758
<br /> 0 VA 743,3D5 VA 743,305 VA 724,883 VA 0 VA 0 VA 783,523 VA 777,027 VA FBI
<br /> C)
<br /> r�
<br /> r~
<br /> U U �
<br /> � z
<br /> xx WW
<br /> W U
<br /> DW�1I o
<br /> 1-1/4" C. - 4 #3 2" C. - 4 #3/0 ] TO PANEL CP2
<br /> 1" C. - 3 #4 1-1/4" C. - 4 #3 �1
<br /> 1" C. - 3 #4 �4
<br /> _E
<br /> PNL LP2 PNL DP2 PNL ADP PNL M2A PNL M1A PNL M1 U
<br /> 200A 100A 400A 100A 400A 400A
<br /> 277/480V 120/208V 120/208V 120/208V 277/480V 277/480V 2"C. - 4 #3/0
<br /> 4" C. - 4
<br /> #600KCMIL 1-1/4"C. - 4 #3 &
<br /> TRANS. TRANS. 475KVA
<br /> TRANS.
<br /> T2 Ti 400/400 200/200 100/100 T2A
<br /> ATTIC LEVEL 45KVA 150KVA 45KVA
<br /> MAIN SWITCHBOARD 'MDP' - - -
<br /> 1000A, 277/48OV, 31l:t, 4W
<br /> (65,000 AID RATING)
<br /> 2" C. - 4 #3/0 4"C. - 4 #500KCMIL 2" C. - 3 #4/0 1-1/4"C. - 4 #3 & PRM NO, 21015.00
<br /> DmwN BY: LRD
<br /> 400A 400A o�sy:BA
<br /> TO PANEL
<br /> ATI2A DATE 08-30-2022
<br /> 400A 400A RR19ol1s REVISION IISSUE DATE
<br /> 0
<br /> 400A 400A
<br /> GFI \ 1000 AMP 300A 400A
<br /> RELAY MAIN TO PANELS 2"C. - 4 #3/0
<br /> BREAKER ] SL1, C, S,
<br /> 400A 400A HLDB, BBDB, SDB 1"C. - 3 #3
<br /> 100A 100A 1-1/2"C. - 4 #2
<br /> 0
<br /> TO PANELS CP1, P1
<br /> 1"C. - 3 #4
<br /> 400A SPACE PNL E1 PNL E2 PNL LP1 PNL DP1 PNL DP1A PNL DP2A PNL B112
<br /> 200A 200A
<br /> 100A 100/100 100A 400A 200A 200A 100A 200A
<br /> 277/480V 120/208V 277/480V 120/208V 120/208V 120/208V 120/208V
<br /> 200A SPACE TRANS.
<br /> TE
<br /> GROUND LEVEL 45KVA
<br /> I 1 #3/0 GND
<br /> TO EXIST. DISTR. _ � _
<br /> BOARD IN BLDG. 5
<br /> NOTE - REFERENCE ONLY: SHEET TITLE
<br /> " CONDUIT
<br /> (a) 4 #SooKCMIL STUB & BUSH 2 RISER DIAGRAM
<br /> B DG. (NORTH) ALL EQUIPMENT & FEEDERS SHOWN ARE
<br /> 10'-0" BEYOND
<br /> EXISTING, UNLESS NOTED OTHERWISE.
<br /> RISER DIAGRAM SHEET NUMBER
<br /> SCALE: NONE
<br /> E2mO
<br /> CLIE-ETNo SHEET3 OF 1
<br />
|