Page 7 of 8 <br /> R QUICK RESPONSE <br /> DRY HORIZONTAL <br /> N41KJNG4 SIDEWALL SPRINKLERS <br /> The Viking Corporation,210 N Industrial Park Drive, Hastings MI 49058 <br /> Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com <br /> Visit the Viking website for the latest edition of this technical data page: www.vikinggroupinc.com <br /> For "A" Dimension: <br /> 1, Determine the distance from the face of <br /> the tee to the base of the sprinkler. Ceiling <br /> 2 Round to next highest 1/2' (12.7 mm) <br /> increment, between 3" (76.2 mm) and f�Wall <br /> 47' (1,194 mm). 4" (102 mm) Minimum <br /> 6" (152 mm) Maximumx <br /> q 2-3/16" <br /> (51 mm)� <br /> 5/8' (16 mm) <br /> Outside diameter; 1-5/16" <br /> (33A mm), (Same as 1" Do not exceed 6" (152 mm), <br /> (25 mm) Schedule 40 pipe Do not recess wrench boss. <br /> x May be allowed up to 18' (457 mm) for certain <br /> FM installations, Refer to the appropriate installation <br /> standards, including NPPA 13 and/or PM Loss <br /> Prevention Data Sheet 2-0. <br /> Figure 7: Quick Response Plain Barrel Dry Horizontal Sidewall Sprinkler <br /> Form No. F_031993 20.04.16 Rev 20.1 <br />